View larger
EMS-RO-T-2,4-SWD 170108 EMS-RO-T-2P4-SWD EATON ELECTRIC Reversing starters 2, 4 A, SWD
EMS-RO-T-2,4-SWD
170108
EMS-RO-T-2P4-SWD
EATON - MOELLER
1 Pcs.
Automation > Motor starter/Motor starter combination
Standard Soft Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller EMS-RO-T-2,4-SWD is a reversing starter with SmartWire-DT connectivity designed for efficient motor control and bi-directional operation. Electronic motor starters offer compact footprints and integrated bus communication for modern automated industrial systems.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of motor starter (EF009598): Reversing starter
- With short-circuit release (EF006691): No
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 0 V
- Rated control supply voltage DC (EF003980): 24 V
- Voltage type for actuating (EF008242): DC
- Rated operation power at AC-3, 230 V, 3-phase (EF009599): 0.37 kW
- Rated operation power at AC-3, 400 V (EF001364): 0.75 kW
- Rated power, 460 V, 60 Hz, 3-phase (EF009600): 0.736 kW
- Rated power, 575 V, 60 Hz, 3-phase (EF009601): 0 kW
- Rated operation current Ie (EF001443): 2.4 A
- Rated operation current at AC-3, 400 V (EF009602): 2.4 A
- Overload release current setting (EF002336): 0.18 A
- Ambient temperature, upper operating limit (EF009603): 60 °C
- Temperature compensated overload protection (EF009604): Yes
- Release class (EF006668): CLASS 10
More info
▲Delivery program
Reversing start
Motor protection
Circuit design: safety output stage with bypass, three-phase disconnect.
Motor current additionally adjustable via SmartWire-DT.
Operating direction feedback
Motor current in %
Motor current in A
Thermal motor image in %
Overload prewarning
Trip indications (overload, phase failure, etc.)
Set short-circuit release value
Device Type
Manual reset
Automatic reset
Technical data
1 x AWG20 - 14 mm2
1 x AWG24 - 14 mm2
2 x AWG24 - 16 mm2
20 (automatic restart) min.
If ≧ 67, pick-up time of 1.8 s %
If ≧ 67, pick-up time of 1.8 s %
50 kA, 500 V AC: fuse 30 A CCMR
50 kA, 415 V AC: PKM0-4
15 kA, 415 V AC: PKM0-6,3
2.5 kA, 400 V AC: FAZ-B16/3
1.4 - 2 GHz: 10
2.0 - 2.7 GHz: 3 V/m
EN 61000-6-3, Class A (emitted interference, radiated)
IEC/EN 61000-4-4, level 3 kV
2 kV (asymmetrical)
according to IEC/EN 61000-4-5