View larger
EMS-DO-T-9-SWD 170107 EATON ELECTRIC Starter Direct 9 SWD
EMS-DO-T-9-SWD
170107
EATON - MOELLER
1 Pcs.
Automation > Motor starter/Motor starter combination
Standard Soft Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Direct motor starter from Eaton Moeller (EMS-DO-T-9-SWD) provides reliable switching and operational control for standard industrial electric motors. Direct-on-line starters are commonly integrated into machine automation to manage continuous running cycles and basic motor protection.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of motor starter (EF009598): Direct starter
- With short-circuit release (EF006691): No
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 0 V
- Rated control supply voltage DC (EF003980): 24 V
- Voltage type for actuating (EF008242): DC
- Rated operation power at AC-3, 230 V, 3-phase (EF009599): 1.5 kW
- Rated operation power at AC-3, 400 V (EF001364): 3 kW
- Rated power, 460 V, 60 Hz, 3-phase (EF009600): 2.2 kW
- Rated power, 575 V, 60 Hz, 3-phase (EF009601): 0 kW
- Rated operation current Ie (EF001443): 9 A
- Rated operation current at AC-3, 400 V (EF009602): 7 A
- Overload release current setting (EF002336): 1.5 A
- Ambient temperature, upper operating limit (EF009603): 40 °C
- Temperature compensated overload protection (EF009604): Yes
- Release class (EF006668): CLASS 10
More info
▲Delivery program
Motor protection
Circuit design: safety output stage with bypass, three-phase disconnect.
Motor current additionally adjustable via SmartWire-DT.
Operating direction feedback
Motor current in %
Motor current in A
Thermal motor image in %
Overload prewarning
Trip indications (overload, phase failure, etc.)
Set short-circuit release value
Device Type
Manual reset
Automatic reset
Technical data
1 x AWG20 - 14 mm2
1 x AWG24 - 14 mm2
2 x AWG24 - 16 mm2
10A (Ir > 4 A) CLASS
20 (automatic restart) min.
If ≧ 67, pick-up time of 1.8 s %
If ≧ 67, pick-up time of 1.8 s %
50 kA, 500 V AC: fuse 30 A CCMR
50 kA, 415 V AC: PKM0-4
15 kA, 415 V AC: PKM0-6,3
2.5 kA, 400 V AC: FAZ-B16/3
1.4 - 2 GHz: 10
2.0 - 2.7 GHz: 3 V/m
EN 61000-6-3, Class A (emitted interference, radiated)
IEC/EN 61000-4-4, level 3 kV
2 kV (asymmetrical)
according to IEC/EN 61000-4-5