View larger
EMR6-W500-D-1 184779 Y7-184779 EATON ELECTRIC Phase monitoring relays, On- and Off-delayed, 300 500 V AC, 50..
EMR6-W500-D-1
184779
Y7-184779
EATON - MOELLER
1 Pcs.
Automation > Phase monitoring relay
Relay timers (KETR, KEMR, KESR)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Protecting three-phase electrical systems from abnormal line conditions, the Eaton Moeller EMR6-W500-D-1 phase monitoring relay actively checks for phase failure, over-voltage, and under-voltage scenarios. These safety relays are standard in manufacturing automation setups to protect expensive rotating equipment from electrical faults.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Type of electric connection (EF003961): Screw connection
- With detachable clamps (EF003340): No
- External power supply required (EF003292): No
- Voltage type (supply voltage) (EF002991): AC
- Supply voltage AC 50 Hz (EF007532): 300 V
- Supply voltage AC 60 Hz (EF007533): 300 V
- Phase sequence monitoring (EF003412): Yes
- Phase failure detection (EF003413): Yes
- Function under voltage detection (EF003414): Yes
- Function over voltage detection (EF003415): Yes
- Phase imbalance monitoring (EF003416): No
- Voltage measuring range (EF002486): 300 V
- Min. adjustable delay-on energization time (EF008190): 0.1 s
- Max. permitted delay-on energization time (EF008189): 30 s
- Min. adjustable off-delay time (EF008192): 0.1 s
- Max. permitted off-delay time (EF008191): 30 s
More info
▲General specifications
CCC
IEC
CSA
GL
Features & Functions
On- and Off-delayed
Under voltage detection
Over voltage detection
Phase sequence monitoring
Phase failure
Undervoltage
Phase sequence (can be deactivated)
General
Terminals: IP20
Status indication of Undervoltage: Red LED (F2 on)
Status indication of Supply voltage: Yellow, solid light
Status indication of Phase sequence fault: Red, flashing light (F1 and F2 alternating)
Status indication of Relay energized: Yellow, solid light (R/T)
Status indication of Overvoltage: F1 red, solid light
Status indication of Undervoltage: F2 red, solid light
Status indication of Delay time running: Yellow, flashing light (R/T)
Status indication of Supply voltage: Yellow LED
Status indication of Overvoltage: Red LED (F1 on)
Climatic environmental conditions
Electro magnetic compatibility
Terminal capacities
2 x (0.5-1.5) mm², (2 x (18-16) AWG), flexible with ferrule
Min. 0.6 Nm, Screw terminals
Timing cycle
0.2 s, Response delay time
0.5 % Error within supply voltage (Measuring circuits)
Adjustable from 0.1 – 30 s, Reset delay/Off-delay time
0.5 %, Time error within supply voltage
Power supply
0.85 x Uc
Measuring circuits
Relay output contacts
4 A at AC-12, 230 V
4 A at DC-12, 24 V
3 A at AC-15, 230 V