View larger
EMR6-W400-M-1 184778 Y7-184778 EATON ELECTRIC Phase monitoring relays, On- and Off-delayed, 400 V AC, 50/60 ..
EMR6-W400-M-1
184778
Y7-184778
EATON - MOELLER
1 Pcs.
Automation > Phase monitoring relay
Relay timers (KETR, KEMR, KESR)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Supervise industrial power lines accurately with this Eaton Moeller EMR6-W400-M-1 phase monitoring relay, designed to detect multi-phase voltage faults and phase loss. Control system builders deploy these versatile components to protect heavy machinery from unstable electrical supplies.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of electric connection (EF003961): Screw connection
- With detachable clamps (EF003340): No
- External power supply required (EF003292): No
- Voltage type (supply voltage) (EF002991): AC
- Supply voltage AC 50 Hz (EF007532): 400 V
- Supply voltage AC 60 Hz (EF007533): 400 V
- Phase sequence monitoring (EF003412): Yes
- Phase failure detection (EF003413): Yes
- Function under voltage detection (EF003414): Yes
- Function over voltage detection (EF003415): Yes
- Phase imbalance monitoring (EF003416): No
- Voltage measuring range (EF002486): 400 V
- Min. adjustable delay-on energization time (EF008190): 0.1 s
- Max. permitted delay-on energization time (EF008189): 30 s
- Min. adjustable off-delay time (EF008192): 0.1 s
- Max. permitted off-delay time (EF008191): 30 s
More info
▲General specifications
CSA
GL
UL
IEC
Features & Functions
Under voltage detection
Over voltage detection
Phase failure detection
Phase failure
Overvoltage
Phase sequence (can be deactivated)
Undervoltage
General
Terminals: IP20
Status indication of Undervoltage: Red LED (F2 on)
Status indication of Overvoltage: Red LED (F1 on)
Status indication of Supply voltage: Yellow, solid light
Status indication of Phase sequence fault: Red, flashing light (F1 and F2 alternating)
Status indication of Delay time running: Yellow, flashing light (R/T)
Status indication of Overvoltage: F1 red, solid light
Status indication of Relay energized: Yellow, solid light (R/T)
Status indication of Undervoltage: F2 red, solid light
Status indication of Supply voltage: Yellow LED
Climatic environmental conditions
Electro magnetic compatibility
Terminal capacities
1 x (0.5-2.5) mm², (1 x (18-14) AWG), solid
Min. 0.6 Nm, Screw terminals
Timing cycle
On-delay/off-delay: none = 0 or adjustable between 0.1 - 30 s
0.5 % Error within supply voltage (Measuring circuits)
0.5 %, Time error within supply voltage
0.06 %/°C, Time error within temperature range
Power supply
1.1 x Uc
Measuring circuits
Relay output contacts
4 A at AC-12, 230 V
3 A at AC-15, 230 V
2 A at DC-13, 24 V