View larger
EMR6-W380-L-1 184777 Y7-184777 EATON ELECTRIC Phase monitoring relays, On- and Off-delayed, 380 V AC, 50/60 ..
EMR6-W380-L-1
184777
Y7-184777
EATON - MOELLER
1 Pcs.
Automation > Phase monitoring relay
Relay timers (KETR, KEMR, KESR)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller EMR6-W380-L-1 is a phase monitoring relay configured to track incoming 380V AC utility lines for voltage fluctuations, phase loss, and sequence errors. Incorporating these protective relays into control cabinets ensures that manufacturing machinery halts safely before electrical imbalances cause severe damage to motors.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Type of electric connection (EF003961): Screw connection
- With detachable clamps (EF003340): No
- External power supply required (EF003292): No
- Voltage type (supply voltage) (EF002991): AC
- Supply voltage AC 50 Hz (EF007532): 380 V
- Supply voltage AC 60 Hz (EF007533): 380 V
- Phase sequence monitoring (EF003412): Yes
- Phase failure detection (EF003413): Yes
- Function under voltage detection (EF003414): Yes
- Function over voltage detection (EF003415): Yes
- Phase imbalance monitoring (EF003416): No
- Voltage measuring range (EF002486): 380 V
- Min. adjustable delay-on energization time (EF008190): 0.1 s
- Max. permitted delay-on energization time (EF008189): 30 s
- Min. adjustable off-delay time (EF008192): 0.1 s
- Max. permitted off-delay time (EF008191): 30 s
More info
▲General specifications
CSA
IEC
CCC
UL
Features & Functions
Under voltage detection
Over voltage detection
Phase failure detection
Overvoltage
Undervoltage
Phase sequence (can be deactivated)
Phase sequence monitoring
General
Enclosure: IP50
Status indication of Supply voltage: Yellow, solid light
Status indication of Overvoltage: Red LED (F1 on)
Status indication of Phase failure: F1 red, solid light and F2 red, flashing light
Status indication of Undervoltage: Red LED (F2 on)
Status indication of Overvoltage: F1 red, solid light
Status indication of Phase sequence fault: Red, flashing light (F1 and F2 alternating)
Status indication of Relay energized: Yellow, solid light (R/T)
Status indication of Supply voltage: Yellow LED
Status indication of Delay time running: Yellow, flashing light (R/T)
Climatic environmental conditions
Electro magnetic compatibility
Terminal capacities
2 x (0.5-1.5) mm², (2 x (18-16) AWG), flexible with ferrule
Min. 0.6 Nm, Screw terminals
Timing cycle
On-delay/off-delay: none = 0 or adjustable between 0.1 - 30 s
0.5 %, Time error within supply voltage
Adjustable from 0.1 – 30 s, Reset delay/Off-delay time
0.5 % Error within supply voltage (Measuring circuits)
Power supply
1.1 x Uc
Measuring circuits
Relay output contacts
3 A at AC-15, 230 V
4 A at DC-12, 24 V
4 A at AC-12, 230 V