View larger
EMR6-IF1-A-1 184782 Y7-184782 EATON ELECTRIC Current monitoring relays, 3 30 mA, 10 100 mA, 0.1 1 A, 24 240 ..
EMR6-IF1-A-1
184782
Y7-184782
EATON - MOELLER
1 Pcs.
Automation > Current monitoring relay
Relay timers (KETR, KEMR, KESR)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Identified by part number EMR6-IF1-A-1, this current monitoring relay is manufactured by Eaton Moeller to provide precise electrical protection across various automated processes. Devices in this category guard critical loads against overcurrent and undercurrent scenarios by continuously measuring operating currents and switching output contacts when parameters drift past established limits.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of electric connection (EF003961): Screw connection
- With detachable clamps (EF003340): No
- External power supply required (EF003292): No
- Voltage type (supply voltage) (EF002991): AC/DC
- Supply voltage AC 50 Hz (EF007532): 24 V
- Supply voltage AC 60 Hz (EF007533): 24 V
- Supply voltage DC (EF007534): 24 V
- Voltage measuring range (EF002486): 24 V
- Type of current (EF000143): AC/DC
- Current measuring range (EF000417): 0.01 A
- Response value amperage 1 (EF008204): 0.1 A
- Response value amperage 2 (EF008205): 0.003 A
- Single-phase under current possible (EF003405): Yes
- Three-phase under current possible (EF003406): No
- Single-phase overcurrent possible (EF003407): Yes
- Three-phase overcurrent possible (EF003408): No
More info
▲General specifications
CSA-C22.2 No. 14
RMRS
CCC
GL
UL 508
RCM
Features & Functions
Single-phase over current possible
Monitoring of single-phase DC and AC networks
DC-voltage under current
DC-voltage over current
Overcurrent
Undercurrent
General
Terminals: IP20
Status indication of measured value: Red LED
Status indication of energized output relay: Yellow LED
Status indication of Supply voltage: Green, solid light
Other states depending on fault (see IL): Measured value
Climatic environmental conditions
Electro magnetic compatibility
Terminal capacities
Min. 0.6 Nm, Screw terminals
Timing cycle
Switch-on delay: none = 0 or adjustable from 0.1 to 30 s
0.06 %/°C, Time error within temperature range
30 s, Reset delay/Off-delay time
0.5 % Error within supply voltage (Measuring circuits)
Power supply
24 - 240 V DC
0.85 x Uc
Measuring circuits
Input B1-C: 0.003 - 0.03 A
Input B2-C: 0.01 - 0.1 A
Relay output contacts
4 A at DC-12, 24 V