EATON - MOELLER EMR6-F500-G-1 EMR6-F500-G-1 184789 Y7-184789 EATON ELECTRIC Phase sequence relays, 200 500 V AC, 50/60 Hz View larger
Images are for illustrative purposes only. Please refer to data sheet for details

EMR6-F500-G-1 184789 Y7-184789 EATON ELECTRIC Phase sequence relays, 200 500 V AC, 50/60 Hz

EMR6-F500-G-1

184789

Y7-184789

EATON - MOELLER

1 Pcs.

Phase sequence relays, 200 - 500 V AC, 50/60 Hz EMR6-F500-G-1 Eaton Moeller® series EMR6 Phase sequence relays, 200 - 500 V AC, 50/60 Hz Phase sequence relays, Product range: EMR Measuring and monitoring relays, Monitoring of three-phase networks, Phase failure detection at < 0.6 x Ue, Power supply from the measuring circuit, Fixed response delay, Monitoring voltage per phase: UN= 200 - 500 V AC, 50/60 Hz V AC, Monitoring of: Phase failure, Phase sequence, Supply voltage: 200 - 500 V AC, 50/60 Hz, Mounting position: As required, Fixing: Snap fixing, top-hat rail IEC/EN 60715, Width: 22.5 mm, Standards: IEC/EN 60255-6,

Automation > Phase monitoring relay
Relay timers (KETR, KEMR, KESR)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General specifications

Product Name
Eaton Moeller® series EMR6 Phase sequence relay
Catalog Number
184789
Model Code
EMR6-F500-G-1
EAN
4015081788255
Product Length/Depth
103.7 mm
Product Height
85.6 mm
Product Width
22.5 mm
Product Weight
0.16 kg
Certifications
IEC/EN 60255-6

Features & Functions

Electric connection type
Screw connection
Features
Fixed response delay
Functions
Phase failure detection
Monitoring of three-phase networks
Monitoring function
Phase failure
Phase sequence monitoring
Phase sequence
Voltage measurement - min
200 V
Voltage measurement - max
500 V

General

Degree of protection
Enclosure: IP50
Terminals: IP20
Lifespan, mechanical
30,000,000 Operations
Mounting position
As required
Overvoltage category
III
Pollution degree
3
Product category
EMR Measuring and monitoring relays
Rated impulse withstand voltage (Uimp)
4000 V AC
Shock resistance
Class 2
LED indicator
Status indication of energized output relay: Yellow LED
Status indication of Phase failure: Red, solid light
Status indication of Phase sequence fault: Red, flashing light
Type
Phase sequence relay
Voltage type
AC
Voltage type
AC

Climatic environmental conditions

Ambient operating temperature - min
-20 °C
Ambient operating temperature - max
60 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
85 °C
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30

Electro magnetic compatibility

Air discharge
Air/contact discharge, according to IEC/EN 61000-4-2, level 3
Burst impulse
According to IEC/EN 61000-4-4, level 3
Electromagnetic compatibility
According to IEC/EN 60947-6-2
Immunity to line-conducted interference
Level 3 (according to IEC/EN 61000-4-6)
Immunity to radiation
Level 3 (according to IEC/EN 61000-4-3)
Surge rating
According to IEC/EN 61000-4-5 Level 4

Terminal capacities

Connection type
Snap fixing, top-hat rail IEC/EN 60715
Terminal capacity
2 x 2.5 mm², solid
2 x 2.5 mm², (2 x 14 AWG), flexible with ferrule
Screwdriver size
5.5 x 0.8 mm, Terminal screw
Tightening torque
Min. 0.5 Nm, Screw terminals
0.8 Nm, Screw terminals

Timing cycle

Timing cycle
0.5 % Error within supply voltage (Measuring circuits)

Power supply

Duty factor
100 %, Power supply
Power consumption
11 VA
Rated control supply voltage (Us) at AC, 50 Hz - min
200 V
Rated control supply voltage (Us) at AC, 50 Hz - max
500 V
Rated control supply voltage (Us) at AC, 60 Hz - min
200 V
Rated control supply voltage (Us) at AC, 60 Hz - max
500 V
Rated control supply voltage (Us) at DC - min
0 V
Rated control supply voltage (Us) at DC - max
0 V
Rated frequency - min
50 Hz
Rated frequency - max
60 Hz
Supply voltage
200 - 500 V AC, 50/60 Hz
Voltage tolerance
0.85 x Uc
1.1 x Uc

Measuring circuits

Measuring cycle
500 ms
Temperature error
0.06 %/°C, Measuring circuits

Relay output contacts

Number of contacts (change-over contacts)
2
Number of contacts (normally closed contacts)
0
Number of contacts (normally open contacts)
0
Lifespan, electrical
300,000 Operation (at 230 V, AC-12, 4 A)
Rated operational current (Ie)
2 A at DC-13, 24 V
4 A at AC-12, 230 V
4 A at DC-12, 24 V
3 A at AC-15, 230 V
Rated operational voltage (Ue) at AC - max
250 V
Short-circuit protection rating
Max. 10 A Fast/gL, Fuse, Relay output contacts
Short-circuit protection rating
Max. 10 A Fast/gL, Fuse, Relay output contacts

ETIM for 184789 Relays (EC001441)
Feature Name Feature Value
Type of electric connection (EF003961) Screw connection
With detachable clamps (EF003340) No
External power supply required (EF003292) No
Voltage type (supply voltage) (EF002991) AC
Supply voltage AC 50 Hz (EF007532) 200 V
Supply voltage AC 60 Hz (EF007533) 200 V
Phase sequence monitoring (EF003412) Yes
Phase failure detection (EF003413) Yes
Function under voltage detection (EF003414) No
Function over voltage detection (EF003415) No
Phase imbalance monitoring (EF003416) No
Voltage measuring range (EF002486) 200 V
Min. adjustable delay-on energization time (EF008190) 0 s
Max. permitted delay-on energization time (EF008189) 0 s
Min. adjustable off-delay time (EF008192) 0 s
Max. permitted off-delay time (EF008191) 0 s
Number of contacts as normally closed contact (EF008255) 0
Number of contacts as normally open contact (EF008256) 0
Number of contacts as change-over contact (EF008257) 2
Voltage type (operating voltage) (EF005294) AC
Operating voltage AC 50 Hz (EF008206) 200 V
Operating voltage AC 60 Hz (EF008207) 200 V
Rated switch current (EF006706) 4 A
Width (EF000008) 22.5 mm
Height (EF000040) 85.6 mm
Depth (EF000049) 103.7 mm