View larger
EMR6-AW500-D-1 184764 Y7-184764 EATON ELECTRIC Phase monitoring relays, Multi-functional, 300 500 V AC, 50/6..
EMR6-AW500-D-1
184764
Y7-184764
EATON - MOELLER
1 Pcs.
Automation > Phase monitoring relay
Relay timers (KETR, KEMR, KESR)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller EMR6-AW500-D-1 monitoring relay acts as a versatile multi-functional device for safeguarding complex three-phase industrial systems. Electrical engineers incorporate such relays to monitor voltage bands, phase asymmetry, and network faults, ensuring safe electrical operation. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of electric connection (EF003961): Screw connection
- With detachable clamps (EF003340): No
- External power supply required (EF003292): No
- Voltage type (supply voltage) (EF002991): AC
- Supply voltage AC 50 Hz (EF007532): 300 V
- Supply voltage AC 60 Hz (EF007533): 300 V
- Phase sequence monitoring (EF003412): Yes
- Phase failure detection (EF003413): Yes
- Function under voltage detection (EF003414): Yes
- Function over voltage detection (EF003415): Yes
- Phase imbalance monitoring (EF003416): Yes
- Voltage measuring range (EF002486): 300 V
- Min. adjustable delay-on energization time (EF008190): 0.1 s
- Max. permitted delay-on energization time (EF008189): 30 s
- Min. adjustable off-delay time (EF008192): 0.1 s
- Max. permitted off-delay time (EF008191): 30 s
More info
▲General specifications
UL
IEC
CSA
CCC
Features & Functions
Phase failure detection
Over voltage detection
Multi-functional
Phase failure
Undervoltage
Phase sequence monitoring
Phase sequence (can be deactivated)
Overvoltage
Imbalance
General
Terminals: IP20
Status indication of energized output relay: Green flashing (R)
Status indication of Phase sequence error: Red LEDs (F1 and F2 flashing)
Status indication of Overvoltage: F1 red, solid light
Status indication of Relay energized: Yellow, solid light
Status indication of Phase failure: F1 red, solid light and F2 red, flashing light
Status indication of Supply voltage: Green, solid light
Status indication of Delay time running: Yellow, flashing light
Status indication of Phase failure: Red LEDs (F1 on, F2 flashes)
Status indication of Imbalance: Red, solid light (F1 and F2)
Status indication of Supply voltage: Green LED (R on)
Status indication of Undervoltage: F2 red, solid light
Status indication of Overvoltage: Red LED (F1 on)
Status indication of Undervoltage: Red LED (F2 on)
Climatic environmental conditions
Electro magnetic compatibility
Terminal capacities
2 x (0.5-1.5) mm², (2 x (18-16) AWG), flexible with ferrule
Min. 0.6 Nm, Screw terminals
Timing cycle
On-delay/off-delay: none = 0 or adjustable between 0.1 - 30 s
0.5 % Error within supply voltage (Measuring circuits)
0.5 %, Time error within supply voltage
Adjustable from 0.1 – 30 s, Reset delay/Off-delay time
Power supply
1.1 x Uc
Measuring circuits
Relay output contacts
3 A at AC-15, 230 V
2 A at DC-13, 24 V
4 A at DC-12, 24 V