Phase imbalance monitoring relays, 160 - 300 V AC, 50/60 Hz EMR6-A300-C-1 Eaton Moeller® series EMR6 Phase imbalance monitoring relays, 160 - 300 V AC, 50/60 Hz

Automation > Phase monitoring relay
Relay timers (KETR, KEMR, KESR)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General specifications

Product Name
Eaton Moeller® series EMR6 Asymmetry monitoring relay
Catalog Number
184761
Model Code
EMR6-A300-C-1
EAN
4015081787975
Product Length/Depth
103.7 mm
Product Height
85.6 mm
Product Width
22.5 mm
Product Weight
0.16 kg
Certifications
UL
CE
IEC/EN 60255-6
IEC255-6

Features & Functions

Electric connection type
Screw connection
Features
Imbalance threshold values adjustable 2 - 25 % of mean value of phase voltages
Functions
Phase failure detection
Monitoring function
Phase imbalance monitoring
Phase failure
Imbalance
Phase sequence
Phase sequence monitoring
Voltage measurement - min
160 V
Voltage measurement - max
300 V

General

Degree of protection
Terminals: IP20
Enclosure: IP50
Lifespan, mechanical
30,000,000 Operations
Mounting position
As required
Overvoltage category
III
Pollution degree
3
Product category
EMR Measuring and monitoring relays
Rated impulse withstand voltage (Uimp)
4000 V AC
Shock resistance
Class 2
LED indicator
Status indication of Relay energized: Yellow, solid light
Status indication of Imbalance: Red, solid light (F1 and F2)
Status indication of Delay time running: Yellow, flashing light
Status indication of Phase failure: F1 red, solid light and F2 red, flashing light
Status indication of Phase sequence fault: Red, flashing light (F1 and F2 alternating)
Status indication of Supply voltage: Green, solid light
Status indication of energized output relay: Yellow LED
Status indication of errors: Red LED
Type
Phase imbalance monitoring relay
Voltage type
AC
Voltage type
AC

Climatic environmental conditions

Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
60 °C
Ambient storage temperature - min
40 °C
Ambient storage temperature - max
85 °C
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30

Electro magnetic compatibility

Air discharge
Air/contact discharge, according to IEC/EN 61000-4-2, level 3
Burst impulse
According to IEC/EN 61000-4-4, level 3
Electromagnetic compatibility
According to IEC/EN 60947-6-2
Immunity to line-conducted interference
Level 3 (according to IEC/EN 61000-4-6)
Immunity to radiation
Level 3 (according to IEC/EN 61000-4-3)
Surge rating
According to IEC/EN 61000-4-5 Level 4

Terminal capacities

Connection type
Snap fixing, top-hat rail IEC/EN 60715
Terminal capacity
2 x (0.5-1.5) mm², (2 x (18-16) AWG), flexible with ferrule
1 x (0.5-2.5) mm², (1 x (18-14) AWG), solid
Screwdriver size
5.5 x 0.8 mm, Terminal screw
Tightening torque
Min. 0.5 Nm, Screw terminals
0.8 Nm, Screw terminals

Timing cycle

Delay time
0.2 s, Response delay time
On delay: None = 0 or adjustable from 0.1 to 30 s
Timing cycle
0.5 %, Time error within supply voltage
Adjustable from 0.1 – 30 s, Reset delay/Off-delay time
0.06 %/°C, Time error within temperature range
0.5 % Error within supply voltage (Measuring circuits)

Power supply

Duty factor
100 %, Power supply
Power consumption
15 VA
Rated control supply voltage (Us) at AC, 50 Hz - min
160 V
Rated control supply voltage (Us) at AC, 50 Hz - max
300 V
Rated control supply voltage (Us) at AC, 60 Hz - min
160 V
Rated control supply voltage (Us) at AC, 60 Hz - max
300 V
Rated control supply voltage (Us) at DC - min
0 V
Rated control supply voltage (Us) at DC - max
0 V
Rated frequency - min
50 Hz
Rated frequency - max
60 Hz
Supply voltage
160 - 300 V AC, 50/60 Hz
Voltage tolerance
0.85 x Uc
1.1 x Uc

Measuring circuits

Hysteresis
20 %
Switching hysteresis of Sn
20 %
Temperature error
0.06 %/°C, Measuring circuits
Threshold value
Imbalance, Adjustable

Relay output contacts

Number of contacts (change-over contacts)
2
Number of contacts (normally closed contacts)
0
Number of contacts (normally open contacts)
0
Lifespan, electrical
100,000 Operation (at 230 V, AC-12, 4 A)
Rated operational current (Ie)
4 A at AC-12, 230 V
2 A at DC-13, 24 V
4 A at DC-12, 24 V
3 A at AC-15, 230 V
Rated operational voltage (Ue) at AC - max
500 V
Short-circuit protection rating
Max. 10 A Fast/gL, Fuse, Relay output contacts
Short-circuit protection rating
Max. 10 A Fast/gL, Fuse, Relay output contacts

Product Datasheet