View larger
ZEB150-175-GF/KK 164306 Y7-164306 EATON ELECTRIC Overload relay, 35-175A, electronic, 1N/O+1N/C, +earth faul..
ZEB150-175-GF/KK
164306
Y7-164306
EATON - MOELLER
1 Pcs.
Automation > Electronic overload relay
Electronic Circuit Breakers
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
This Eaton Moeller ZEB150-175-GF/KK overload relay provides electronic motor protection against phase failure, thermal overload, and earth faults in industrial environments. Overload relays are integrated into control panels to safely interrupt motor circuits when excessive current draws are detected, preventing costly damage to machinery.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Mounting method (EF000003): Separate positioning
- Type of electrical connection of main circuit (EF006819): Screw connection
- Adjustable current range (EF008211): 0 A
- External power supply required (EF003292): No
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 0 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type (operating voltage) (EF005294): AC
- Operating voltage AC 50 Hz (EF008206): 230 V
- Operating voltage AC 60 Hz (EF008207): 230 V
- Operating voltage DC (EF008208): 0 V
- Release class (EF006668): Adjustable
- Reset function automatic (EF011941): Yes
- Reset function input (EF011940): No
- Reset function push-button (EF011942): Yes
- Width (EF000008): 108 mm
More info
▲General specifications
UL File No.: E1230
VDE 0660
CSA
CSA-C22.2 No. 14
IEC/EN 60947-4-1
CSA Class No.: 3211-03
UL Category Control No.: NKCR
CE
UL 508
CSA File No.: 2290956
IEC/EN 60947
Features & Functions
Trip at approx. > 0.5 x Ir in 2 s
Trip at approx. > 1.5 x Ir in 1 s
General
Separate mounting
6000 V (auxiliary circuits)
Mechanical, According to IEC/EN 60068-2-27
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
2 x (0.75 - 4) mm², Control circuit cables
2 x (18 - 12), Control circuit cables
1 x 6 mm, Terminal screw, Control circuit cables, Standard screwdriver
0.8 - 1.2 Nm, Screw terminals, Control circuit cables
Electrical rating
400 A, Class J, max. Fuse, SCCR (UL/CSA)
R300, DC operated (UL/CSA)
Contacts
Design verification
ETIM only
Push-button