View larger
EASY-E4-UC-8RE1 197217 Y7-197217 EATON ELECTRIC I/O expansion, For use with easyE4, 12/24 V DC, 24 V AC, Inp..
EASY-E4-UC-8RE1
197217
Y7-197217
EATON - MOELLER
1 Pcs.
Automation > Logic module
Easy E4 Nanocontrollers
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller part number EASY-E4-UC-8RE1 is an I/O expansion unit designed to extend the input and output capacity of compatible controller systems in automated industrial applications. Such expansion modules enable systems to monitor additional signals and govern more loads without requiring a complete controller replacement. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Supply voltage AC 50 Hz (EF007532): 85 V
- Supply voltage AC 60 Hz (EF007533): 85 V
- Supply voltage DC (EF007534): 10.2 V
- Voltage type (supply voltage) (EF002991): AC/DC
- Switching current (EF000188): 5 A
- Power consumption (EF000346): 2 W
- Number of analogue inputs (EF001994): 0
- Number of analogue outputs (EF001995): 0
- Number of digital inputs (EF001992): 4
- Number of digital outputs (EF001993): 4
- With relay output (EF003198): Yes
- Number of HW-interfaces industrial Ethernet (EF003020): 0
- Number of interfaces PROFINET (EF006932): 0
- Number of HW-interfaces RS-232 (EF003021): 0
- Number of HW-interfaces RS-422 (EF003022): 0
- Number of HW-interfaces RS-485 (EF003023): 0
More info
▲General specifications
IEC 60068-2-6
IEC 60068-2-27
IEC/EN 61000-6-3
CSA-C22.2 No. 61010
IEC 60068-2-30
EN 61010
IEC/EN 61131-2
EN 50178
IEC/EN 61000-4-2
IEC/EN 61000-6-2
UL Listed
UL Category Control No.: NRAQ, NRAQ7
UL File No.: E205091
DNV GL
CE
UL hazardous location class I
UL hazardous location division 2
UL hazardous location group A (acetylene)
UL hazardous location group B (hydrogen)
UL hazardous location group C (ethylene)
UL hazardous location group D (propane)
Features & Functions
Expansion device
LCD-display base unit used as status indication of Digital inputs 24 V DC
General
25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, uncompensated)
25,000 Operations (Fluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated)
25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, with upstream electrical device)
25,000 Operations (Filament bulb load at 1000 W, 230/240 V AC)
Rail mounting possible
Screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Wall mounting/direct mounting
Front build in possible
MODBUS
10 Hz, Relay outputs
0.5 Hz, Inductive load, Relay outputs
R 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes DC
Ambient conditions, mechanical
Horizontal
10 - 57 Hz, 0.15 mm constant amplitude
57 - 150 Hz, 2 g constant acceleration
Climatic environmental conditions
Clearance in air and creepage distances according to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Electro magnetic compatibility
2 kV, Supply cable
According to IEC/EN 61000-4-4
3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3)
10 V/m at 0.8 - 1.0 GHz (according to IEC EN 61000-4-3)
1 kV, Supply cables, symmetrical, power pulses (Surge), EMC
According to IEC/EN 61000-4-5, power pulses (Surge), EMC
10 ms
Terminal capacities
0.2 - 2.5 mm² (22 - 12 AWG), flexible with ferrule
Electrical rating
200000 Operations at DC-13, 24 V DC, 1 A (500 Ops./h)
24 V AC (digital inputs)
12/24 V DC (-15 %/+ 20 % - power supply)
Max. 300 V DC
10.2 - 28.8 V DC
240 V AC
24 V DC (digital inputs)
24 V AC (-15 %/+10 % - power supply)
12 V DC (digital inputs)
20.4 - 26.4 V AC
10 A AC, at 240 V AC (UL/CSA)
1 A DC, at R 300 (UL/CSA)
5 A AC, max. thermal continuous current cos ϕ = 1 at B 300 (UL/CSA)
Short-circuit rating
Communication
Cable
100 m, unscreened, Digital inputs 24 V DC
100 m, unscreened, Digital inputs 12 V DC
40 m (max. per input), Digital inputs 24 V DC
Input/Output
0.015 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 0 to 1, Debounce OFF
0.015 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 1 to 0, Debounce OFF
20 ms, Digital Inputs 12 V DC, Delay time from 1 to 0, Debounce ON
0.1 ms typ., Digital inputs 24 V DC (I1 - I4), Delay time from 0 to 1, Debounce OFF
25 ms typ., Digital Inputs 24 V AC 50 Hz (I1 - I4), Delay time from 1 to 0, Debounce OFF
21 ms typ., Digital Inputs 24 V AC 60 Hz (I1 - I4), Delay time from 0 to 1, Debounce OFF
21 ms typ., Digital Inputs 24 V AC 60 Hz (I1 - I4), Delay time from 1 to 0, Debounce OFF
20 ms, Digital Inputs 12 V DC, Delay time from 0 to 1, Debounce ON
0.2 ms typ., Digital inputs 24 V DC (I1 - I4), Delay time from 1 to 0, Debounce OFF
80 mA
Signal 1: ≥ 15 V DC (I1 - I4, Digital inputs, 24 V DC)
At signal 0: ≤ 5 V (I1 - I8, sinusoidal, Digital inputs, 24 V DC)
Signal 0: ≤ 5 V DC (I1 - I4, Digital inputs, 24 V DC)
At signal 1: ≥ 15 V (I1 - I8, sinusoidal, Digital inputs, 24 V DC)
Status 0: ≤ 15 V DC (I1 - I4, Digital inputs, 24 V DC)
3600/360 VA (AC, at B 300)
4 Relay Outputs
> 500 mA (Relay outputs, Recommended for load: 12 V AC/DC)
Voltage
Current
Safety
Between Relay outputs and expansion devices: yes
Between Digital inputs 24 V DC and Outputs: yes
Between Digital inputs 12 V DC and expansion devices: yes
Between Digital inputs 24 V AC and expansion devices: yes
Between Digital inputs 24 V AC and base unit: yes
Between Digital inputs 12 V DC and base unit: yes
Between Digital inputs 24 V DC and expansion devices: yes
Safe isolation according to EN 50178: 300 V AC (Relay outputs)
Between Relay outputs and Power supply: yes
Between Digital inputs 12 V DC and Outputs: yes
Between Digital inputs 24 V AC and Outputs: yes
Between Digital inputs 24 V DC and base unit: yes
Between Relay outputs and Inputs: yes
Basic isolation: 600 V AC (Relay outputs)
300 V AC, Between two contacts, According to EN 50178