View larger
EASY-E4-UC-16RE1 197218 Y7-197218 EATON ELECTRIC I/O expansion, For use with easyE4, 12/24 V DC, 24 V AC, In..
EASY-E4-UC-16RE1
197218
Y7-197218
EATON - MOELLER
1 Pcs.
Automation > Logic module
Easy E4 Nanocontrollers
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller part number EASY-E4-UC-16RE1 is an I/O expansion module utilized to increase digital input and output points within modular automation setups. Expansion blocks allow growing control systems to scale up capacity cleanly without changing the base controller hardware. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Supply voltage AC 50 Hz (EF007532): 85 V
- Supply voltage AC 60 Hz (EF007533): 85 V
- Supply voltage DC (EF007534): 10.2 V
- Voltage type (supply voltage) (EF002991): AC/DC
- Switching current (EF000188): 5 A
- Power consumption (EF000346): 3 W
- Number of analogue inputs (EF001994): 0
- Number of analogue outputs (EF001995): 0
- Number of digital inputs (EF001992): 8
- Number of digital outputs (EF001993): 8
- With relay output (EF003198): Yes
- Number of HW-interfaces industrial Ethernet (EF003020): 0
- Number of interfaces PROFINET (EF006932): 0
- Number of HW-interfaces RS-232 (EF003021): 0
- Number of HW-interfaces RS-422 (EF003022): 0
- Number of HW-interfaces RS-485 (EF003023): 0
More info
▲General specifications
IEC 60068-2-27
IEC/EN 61000-6-2
IEC 60068-2-30
IEC/EN 61000-4-2
IEC/EN 61131-2
CSA-C22.2 No. 61010
IEC 60068-2-6
CULus per UL 61010
EN 50178
EN 61010
UL Listed
UL Category Control No.: NRAQ, NRAQ7
UL File No.: E205091
DNV GL
CE
UL hazardous location class I
UL hazardous location division 2
UL hazardous location group A (acetylene)
UL hazardous location group B (hydrogen)
UL hazardous location group C (ethylene)
UL hazardous location group D (propane)
Features & Functions
Expandable
LCD-display base unit used as status indication of Digital inputs 24 V DC
General
25,000 Operations (Filament bulb load at 1000 W, 230/240 V AC)
25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, with upstream electrical device)
25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, uncompensated)
25,000 Operations (Fluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated)
Wall mounting/direct mounting
Screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Front build in possible
Rail mounting possible
TCP/IP
0.5 Hz, Inductive load, Relay outputs
2 Hz, Resistive load/lamp load, Relay outputs
R 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes DC
Ambient conditions, mechanical
Horizontal
10 - 57 Hz, 0.15 mm constant amplitude
57 - 150 Hz, 2 g constant acceleration
Climatic environmental conditions
Condensation: prevent with appropriate measures
Electro magnetic compatibility
2 kV, Supply cable
2 kV, Signal cable
3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3)
1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3)
2 kV, Supply cables, asymmetrical, power pulses (Surge), EMC
According to IEC/EN 61000-4-5, power pulses (Surge), EMC
10 ms
Terminal capacities
0.2 - 2.5 mm² (22 - 12 AWG), flexible with ferrule
Electrical rating
200000 Operations at DC-13, 24 V DC, 1 A (500 Ops./h)
10.2 - 28.8 V DC
24 V DC (digital inputs)
Max. 300 V DC
12 V DC (digital inputs)
Max. 300 V AC
240 V AC
12/24 V DC (-15 %/+ 20 % - power supply)
20.4 - 26.4 V AC
24 V AC (digital inputs)
10 A AC, at 240 V AC (UL/CSA)
8 A DC, at 24 V DC (UL/CSA)
5 A AC, max. thermal continuous current cos ϕ = 1 at B 300 (UL/CSA)
Short-circuit rating
Communication
Cable
100 m, unscreened, Digital inputs 24 V AC
100 m, unscreened, Digital inputs 24 V DC
40 m (max. per input), Digital inputs 24 V DC
Input/Output
20 ms, Digital Inputs 12 V DC, Delay time from 1 to 0, Debounce ON
0.2 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 1 to 0, Debounce OFF
20 ms, Digital Inputs 12 V DC, Delay time from 0 to 1, Debounce ON
0.2 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 1 to 0, Debounce OFF
0.15 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 0 to 1, Debounce OFF
200 mA
Signal 0: ≤ 5 V DC (I1 - I4, Digital inputs, 12 V DC)
At signal 0: ≤ 5 V (I1 - I8, sinusoidal, Digital inputs, 24 V DC)
At signal 1: ≥ 15 V (I1 - I8, sinusoidal, Digital inputs, 24 V DC)
Signal 0: ≤ 5 V DC (I1 - I8, Digital inputs, 24 V DC)
Status 0: ≤ 15 V DC (I1 - I4, Digital inputs, 24 V DC)
28/28 VA (DC, at R 300)
Relay outputs in groups of 1
> 500 mA (Relay outputs, Recommended for load: 12 V AC/DC)
Voltage
Current
Safety
Between Digital inputs 24 V DC and Outputs: yes
Between Digital inputs 24 V DC and expansion devices: yes
Between Relay outputs and Inputs: yes
Basic isolation: 600 V AC (Relay outputs)
Safe isolation according to EN 50178: 300 V AC (Relay outputs)
Between Digital inputs 24 V AC and base unit: yes
Between Digital inputs 12 V DC and Outputs: yes
Between Digital inputs 24 V AC and expansion devices: yes
Between Digital inputs 12 V DC and expansion devices: yes
Between Relay outputs and Power supply: yes
Between Relay outputs and expansion devices: yes
Between Digital inputs 12 V DC and base unit: yes
Between Digital inputs 24 V AC and Outputs: yes
Between Relay outputs: yes
300 V AC, Between coil and contact, According to EN 50178