View larger
EASY-E4-UC-12RC1 197211 Y7-197211 EATON ELECTRIC Control relays, easyE4 (expandable, Ethernet), 12/24 V DC, ..
EASY-E4-UC-12RC1
197211
Y7-197211
EATON - MOELLER
1 Pcs.
Automation > Logic module
Easy E4 Nanocontrollers
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Expandable Ethernet control relays like the Eaton Moeller EASY-E4-UC-12RC1 provide flexible automation logic, timing control, and networked communication for industrial and building management systems. These devices process multiple inputs to execute programmed operational sequences and interface with broader control networks. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Supply voltage AC 50 Hz (EF007532): 20.4 V
- Supply voltage AC 60 Hz (EF007533): 20.4 V
- Supply voltage DC (EF007534): 10.2 V
- Voltage type (supply voltage) (EF002991): AC/DC
- Switching current (EF000188): 8 A
- Power consumption (EF000346): 3 W
- Number of analogue inputs (EF001994): 0
- Number of analogue outputs (EF001995): 0
- Number of digital inputs (EF001992): 4
- Number of digital outputs (EF001993): 4
- With relay output (EF003198): Yes
- Number of HW-interfaces industrial Ethernet (EF003020): 1
- Number of interfaces PROFINET (EF006932): 0
- Number of HW-interfaces RS-232 (EF003021): 0
- Number of HW-interfaces RS-422 (EF003022): 0
- Number of HW-interfaces RS-485 (EF003023): 0
More info
▲General specifications
IEC 60068-2-6
IEC/EN 61000-4-2
CSA-C22.2 No. 61010
CULus per UL 61010
EN 61010
IEC/EN 61000-6-3
IEC/EN 61131-2
IEC/EN 61000-6-2
EN 50178
IEC 60068-2-27
UL Listed
UL Category Control No.: NRAQ, NRAQ7
UL File No.: E205091
DNV GL
CE
UL hazardous location class I
UL hazardous location division 2
UL hazardous location group A (acetylene)
UL hazardous location group B (hydrogen)
UL hazardous location group C (ethylene)
UL hazardous location group D (propane)
Features & Functions
Display indication of 6 lines x 16 characters
Networkable (Ethernet)
Real time clock
Relay output
Keypad
Timer
LCD-display used as status indication of Digital inputs 12 V DC
General
Cable length: ≤ 20 m (screened, Digital inputs 24 V DC)
Number: 4 (I1, I2, I3, I4 - Digital inputs 24 V DC)
Pulse pause ratio: 1:1 (Digital inputs 24 V DC)
Counter frequency: 5 kHz (Digital inputs 24 V DC)
25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, uncompensated)
25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, with upstream electrical device)
25,000 Operations (Filament bulb load at 500 W, 115/120 V AC)
25,000 Operations (Fluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated)
Front build in possible
Rail mounting possible
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Wall mounting/direct mounting
MODBUS
2 Hz, Resistive load/lamp load, Relay outputs
0.5 Hz, Inductive load, Relay outputs
R 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes DC
Ambient conditions, mechanical
Horizontal
According to IEC/EN 60068-2-6
57 - 150 Hz, 2 g constant acceleration
Climatic environmental conditions
Condensation: prevent with appropriate measures
Electro magnetic compatibility
2 kV, Signal cable
According to IEC/EN 61000-4-4
1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3)
3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3)
According to IEC/EN 61000-4-5, power pulses (Surge), EMC
2 kV, Supply cables, asymmetrical, power pulses (Surge), EMC
10 ms
Terminal capacities
0.2 - 2.5 mm² (22 - 12 AWG), flexible with ferrule
Electrical rating
200000 Operations at DC-13, 24 V DC, 1 A (500 Ops./h)
12 V DC (digital inputs)
Max. 300 V AC
240 V AC
24 V AC (-15 %/+10 % - power supply)
24 V DC (digital inputs)
12/24 V DC (-15 %/+ 20 % - power supply)
10.2 - 28.8 V DC
24 V AC (digital inputs)
20.4 - 26.4 V AC
8 A DC, at 24 V DC (UL/CSA)
5 A AC, max. thermal continuous current cos ϕ = 1 at B 300 (UL/CSA)
10 A AC, at 240 V AC (UL/CSA)
Short-circuit rating
Communication
Ethernet: RJ45 plug, 8-pole
Cable
100 m, unscreened, Digital inputs 24 V AC
≤ 30 m, screened, Analog inputs
100 m, unscreened, Digital inputs 12 V DC
40 m (max. per input), Digital inputs 24 V DC
Input/Output
± 2 %, (I7, I8) ± 0.12 V, of actual value, within a single device (Analog Inputs)
± 1 %, Repetition accuracy of timing relays (of values)
± 3 %, of actual value, two easy devices (Analog Inputs)
0.015 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 1 to 0, Debounce OFF
0.015 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 0 to 1, Debounce OFF
20 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 1 to 0, Debounce ON
20 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 0 to 1, Debounce ON
20 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 0 to 1, Debounce ON
20 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 1 to 0, Debounce ON
0.015 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 0 to 1, Debounce OFF
Value range: -2147483648 to +2147483647
Pulse shape: Square
Pulse pause ratio: 1:1
Signal offset: 90°
Counter frequency: ≤ 5 kHz
2.2 mA (I5 - I8, at 24 V DC, at signal 1)
1 mA (Analog inputs)
200 mA
Status 0: ≤ 8 V DC (I5 - I8, Digital inputs, 24 V DC)
Status 1: ≥ 8 V DC (I5 - I8, Digital inputs, 24 V DC)
Signal 0: ≤ 5 V DC (I1 - I4, Digital inputs, 12 V DC)
Status 0: ≤ 15 V DC (I1 - I4, Digital inputs, 24 V DC)
At signal 0: ≤ 5 V (I1 - I8, sinusoidal, Digital inputs, 24 V DC)
Status 1: ≥ 15 V DC (I1 - I4, Digital inputs, 24 V DC)
3600/360 VA (AC, at B 300)
4
8
> 500 mA (Relay outputs, Recommended for load: 12 V AC/DC)
Relay outputs in groups of 1
Voltage
Current
-2147483648 - 2147483647 (value range)
≤ 20 m (cable length, screened)
1:1 (Pulse pause ratio)
Square (pulse shape)
Number: 4 (I1, I2, I3, I4 - Digital inputs 24 V DC)
Safety
Between Analog inputs and Outputs: yes
Between Digital inputs 12 V DC and expansion devices: yes
Between Digital inputs 24 V DC and Outputs: yes
Between Relay outputs and expansion devices: yes
Between Digital inputs 24 V AC and Outputs: yes
Between Relay outputs and Power supply: yes
Between Digital inputs 24 V DC and expansion devices: yes
Between Digital inputs 24 V DC and Ethernet: yes
Basic isolation: 600 V AC (Relay outputs)
Between Analog inputs and expansion devices: yes
Between Relay outputs: yes
Between Relay outputs and Inputs: yes
Between Digital inputs 12 V DC and Ethernet: yes
Between Relay outputs and Ethernet: yes
Safe isolation according to EN 50178: 300 V AC (Relay outputs)
Between Digital inputs 24 V AC and expansion devices: yes
Between Digital inputs 24 V AC and Ethernet: yes
300 V AC, Between two contacts, According to EN 50178