EATON - MOELLER EASY-E4-DC-4PE1 EASY-E4-DC-4PE1 197224 Y7-197224 EATON ELECTRIC I/O expansion, For use with easyE4 with temperature measurin.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

EASY-E4-DC-4PE1 197224 Y7-197224 EATON ELECTRIC I/O expansion, For use with easyE4 with temperature measurin..

EASY-E4-DC-4PE1

197224

Y7-197224

EATON - MOELLER

1 Pcs.

I/O expansion, For use with easyE4 with temperature measuring Pt100, Pt1000 oder Ni1000, 24 V DC, 24 V DC, Inputs expansion (number) analog: 4, screw terminal EASY-E4-DC-4PE1 Eaton Moeller® series EASY I/O expansion, For use with easyE4, 24 V DC, Inputs expansion (number) analog: 4, screw terminal EASY-E4-DC-4PE1 I/O expansion, Supply voltage: 24 V DC, Can be used via easyConnect, Connection type: Screw terminal, Mounting position: Vertical or horizontal, Protection type (IEC/EN 60529, EN50178, VBG 4): IP20, Standards: EN 61000-6-2, EN 61000-6-3, IEC 60068-2-6, IEC 60068-2-27, IEC 60068-2-30, IEC 60664, IEC 61131-2, EN 61010, EN 50178, cULus per UL 61010, CSA C22.2 No.61010

Automation > Logic module
Easy E4 Nanocontrollers

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General specifications

Product Name
Eaton Moeller® series EASY I/O expansion
Catalog Number
197224
Model Code
EASY-E4-DC-4PE1
EAN
4015080892854
Product Length/Depth
58 mm
Product Height
90 mm
Product Width
36 mm
Product Weight
0.1 kg
Certifications
IEC/EN 61000-6-3
IEC 60068-2-30
CULus per UL 61010
IEC/EN 61131-2
IEC 60068-2-6
IEC 60068-2-27
IEC/EN 61000-6-2
EN 61010
EN 50178
CSA-C22.2 No. 61010
IEC 60664
IEC/EN 61000-4-2
UL Listed
UL Category Control No.: NRAQ, NRAQ7
UL File No.: E205091
DNV GL
CE
UL hazardous location class I
UL hazardous location division 2
UL hazardous location group A (acetylene)
UL hazardous location group B (hydrogen)
UL hazardous location group C (ethylene)
UL hazardous location group D (propane)

Features & Functions

Features
Additional measurement aids: Filtering (software), smoothing of analog input signal (PT1 behavior), only with set sampling time, selectable per sensor: yes
Expandable
Expansion device
Measuring principle: Two or three wire per sensor, selectable by connection of sensor
Functions
Card diagnostic
Diagnostics below lower measurement range

General

Degree of protection
IP20
Insulation resistance
According to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Mounting method
Rail mounting possible
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Wall mounting/direct mounting
Screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Front build in possible
Overvoltage category
III
Pollution degree
2
Product category
Control relays easyE4
Protocol
TCP/IP
MODBUS
Residual ripple
≤ 5 %
Resolution
12 Bit (0- 4095, digital, scaling per sensor)
Software
EASYSOFT-SWLIC/easySoft7
Type
easyE4 extension
Voltage type
DC

Ambient conditions, mechanical

Drop and topple
50 mm Drop height, Drop to IEC/EN 60068-2-31
Height of fall (IEC/EN 60068-2-32) - max
0.3 m
Mounting position
Horizontal
Vertical
Shock resistance
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts
Vibration resistance
57 - 150 Hz, 2 g constant acceleration
10 - 57 Hz, 0.15 mm constant amplitude
According to IEC/EN 60068-2-6

Climatic environmental conditions

Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
70 °C
Environmental conditions
Condensation: prevent with appropriate measures
Clearance in air and creepage distances according to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Relative humidity
5 - 95 % (IEC 60068-2-30, IEC 60068-2-78)

Electro magnetic compatibility

Air discharge
8 kV
Burst impulse
2 kV, Signal cable
According to IEC/EN 61000-4-4
2 kV, Supply cable
Contact discharge
6 kV
Electromagnetic fields
10 V/m at 0.8 - 1.0 GHz (according to IEC EN 61000-4-3)
1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3)
3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3)
Immunity to line-conducted interference
10 V (according to IEC/EN 61000-4-6)
Radio interference class
Class B (EN 61000-6-3)
Surge rating
According to IEC/EN 61000-4-5, power pulses (Surge), EMC
0.5 kV, Supply cables, symmetrical, EASY…DC, power pulses (Surge), EMC
1 kV, Supply cables, asymmetrical, power pulses (Surge), EMC
Voltage dips
20 ms
≤ 10 ms, Bridging voltage dips

Terminal capacities

Terminal capacity
0.2 - 2.5 mm² (22 - 12 AWG), flexible with ferrule
0.2 - 4 mm² (AWG 22 - 12), solid
Screwdriver size
3.5 x 0.8 mm, Terminal screw
Tightening torque
0.6 Nm, Screw terminals

Electrical rating

Heat dissipation
3.4 W (at 24 V DC)
Inrush current
12.5 A (for 6 ms)
Power consumption
1 W
Power loss
1 W
Rated operational voltage
24 V DC (-15 %/+ 20 % - power supply)
20.4 - 28.8 V DC
Supply voltage at AC, 50 Hz - min
0 VAC
Supply voltage at AC, 50 Hz - max
0 VAC
Supply voltage at DC - min
20.4 VDC
Supply voltage at DC - max
28.8 VDC

Short-circuit rating

Short-circuit protection
≥ 1A (T), Fuse, Power supply

Communication

Connection type
Screw terminal

Cable

Cable length
≤ 30 m, unscreened, Analog inputs temperature resistance Pt100 or Ni1000 sensors

Input/Output

Input
Input type resistance sensor: Platinum sensor Pt100 (according to DIN EN 60751, IEC 751)
Input type resistance sensor: Nickel sensor Ni1000 (according to DIN 43760)
Input current
40 mA
Number of inputs (analog)
4
Number of inputs (digital)
0
Number of outputs (analog)
0
Number of outputs (digital)
0

Safety

Explosion safety category for gas
None
Potential isolation
Between Analog inputs PT100 or Ni1000 and Power supply: no
Between Analog inputs PT100 or Ni1000 and expansion units: yes
Between Analog inputs PT100 or Ni1000 and Inputs: no
Protection against polarity reversal
Yes, for supply voltage (Siemens MPI optional)
Explosion safety category for dust
None

Design verification

Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
1 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

ETIM for 197224 PLC's (EC001417)
Feature Name Feature Value
Supply voltage AC 50 Hz (EF007532) 0 V
Supply voltage AC 60 Hz (EF007533) 0 V
Supply voltage DC (EF007534) 20.4 V
Voltage type (supply voltage) (EF002991) DC
Switching current (EF000188) 0 A
Power consumption (EF000346) 1 W
Number of analogue inputs (EF001994) 4
Number of analogue outputs (EF001995) 0
Number of digital inputs (EF001992) 0
Number of digital outputs (EF001993) 0
With relay output (EF003198) No
Number of HW-interfaces industrial Ethernet (EF003020) 0
Number of interfaces PROFINET (EF006932) 0
Number of HW-interfaces RS-232 (EF003021) 0
Number of HW-interfaces RS-422 (EF003022) 0
Number of HW-interfaces RS-485 (EF003023) 0
Number of HW-interfaces serial TTY (EF003024) 0
Number of HW-interfaces USB (EF003025) 0
Number of HW-interfaces parallel (EF003026) 0
Number of HW-interfaces wireless (EF006933) 0
Number of HW-interfaces other (EF003027) 0
With optical interface (EF003028) No
Supporting protocol for EtherCAT (EF017564) No
Supporting protocol for TCP/IP (EF003050) Yes
Supporting protocol for PROFIBUS (EF003052) No
Supporting protocol for CAN (EF003053) No
Supporting protocol for INTERBUS (EF003054) No
Supporting protocol for ASI (EF003051) No
Supporting protocol for KNX (EF003055) No
Supporting protocol for Modbus (EF003057) Yes
Supporting protocol for Data-Highway (EF003058) No
Supporting protocol for DeviceNet (EF003059) No
Supporting protocol for SUCONET (EF003060) No
Supporting protocol for LON (EF003017) No
Supporting protocol for PROFINET IO (EF007525) No
Supporting protocol for PROFINET CBA (EF007524) No
Supporting protocol for SERCOS (EF006657) No
Supporting protocol for Foundation Fieldbus (EF007522) No
Supporting protocol for EtherNet/IP (EF007521) No
Supporting protocol for AS-Interface Safety at Work (EF007519) No
Supporting protocol for DeviceNet Safety (EF007520) No
Supporting protocol for INTERBUS-Safety (EF006662) No
Supporting protocol for PROFIsafe (EF007526) No
Supporting protocol for SafetyBUS p (EF007527) No
Supporting protocol for other bus systems (EF003062) No
Radio standard Bluetooth (EF007178) No
Radio standard WLAN 802.11 (EF007179) No
Radio standard GPRS (EF008523) No
Radio standard GSM (EF008524) No
Radio standard UMTS (EF008525) No
IO link master (EF007298) No
Redundancy (EF003156) No
With display (EF000458) No
Degree of protection (IP) (EF005474) IP20
Basic device (EF007279) No
Expandable (EF000119) Yes
Expansion device (EF007163) Yes
With time switch clock (EF000256) No
Suitable for rail mounting (EF003972) Yes
Wall mounting/direct mounting (EF007020) Yes
Front built-in possible (EF007016) Yes
Rack-assembly possible (EF007018) No
Suitable for safety functions (EF001597) No
SIL according to IEC 61508 (EF009889) None
Performance level according to EN ISO 13849-1 (EF007399) None
Appendant operation agent (Ex ia) (EF004141) No
Appendant operation agent (Ex ib) (EF004142) No
Explosion safety category for gas (EF003997) None
Explosion safety category for dust (EF003998) None
Certified for UL hazardous location class I (EF017622) Yes
Certified for UL hazardous location class II (EF017625) No
Certified for UL hazardous location class III (EF017627) No
Certified for UL hazardous location division 1 (EF017628) No
Certified for UL hazardous location division 2 (EF017629) Yes
Certified for UL hazardous location group A (acetylene) (EF017632) Yes
Certified for UL hazardous location group B (hydrogen) (EF017633) No
Certified for UL hazardous location group C (ethylene) (EF017635) Yes
Certified for UL hazardous location group D (propane) (EF017636) Yes
Certified for UL hazardous location group E (metal dusts) (EF017637) No
Certified for UL hazardous location group F (carbonaceous dusts) (EF017638) No
Certified for UL hazardous location group G (non-conductive dusts) (EF017639) No
Width (EF000008) 36 mm
Height (EF000040) 90 mm
Depth (EF000049) 58 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.