View larger
EASY-E4-DC-16TE1P 197513 Y7-197513 EATON ELECTRIC EASY-E4-DC-16TE1P
EASY-E4-DC-16TE1P
197513
Y7-197513
EATON - MOELLER
1 Pcs.
Automation > Logic module
Easy E4 Nanocontrollers
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The EASY-E4-DC-16TE1P 197513 Y7-197513 EATON ELECTRIC EASY-E4-DC-16TE1P serves as a specialized control device designed to integrate into modular industrial automation setups. Control units of this classification manage operational signals and execute programmed instructions to keep automated manufacturing cells running reliably. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Supply voltage AC 50 Hz (EF007532): 0 V
- Supply voltage AC 60 Hz (EF007533): 0 V
- Supply voltage DC (EF007534): 20.4 V
- Voltage type (supply voltage) (EF002991): DC
- Switching current (EF000188): 0.5 A
- Power consumption (EF000346): 1 W
- Number of analogue inputs (EF001994): 0
- Number of analogue outputs (EF001995): 0
- Number of digital inputs (EF001992): 8
- Number of digital outputs (EF001993): 8
- With relay output (EF003198): No
- Number of HW-interfaces industrial Ethernet (EF003020): 0
- Number of interfaces PROFINET (EF006932): 0
- Number of HW-interfaces RS-232 (EF003021): 0
- Number of HW-interfaces RS-422 (EF003022): 0
- Number of HW-interfaces RS-485 (EF003023): 0
More info
▲General specifications
UL Category Control No.: NRAQ, NRAQ7
IEC/EN 61000-4-2
IEC/EN 61131-2
IEC 60068-2-6
IEC 60068-2-30
IEC 60068-2-27
EN 61010
IEC/EN 61000-6-3
IEC/EN 61000-6-2
EN 50178
UL File No.: E205091
DNV GL
CE
UL hazardous location class I
UL hazardous location division 2
UL hazardous location group A (acetylene)
UL hazardous location group B (hydrogen)
UL hazardous location group C (ethylene)
UL hazardous location group D (propane)
Features & Functions
Parallel connection of transistor outputs with resistive load, inductive load with external suppressor circuit, combination within a group - Group 1 Q1 to Q4
General
≤ 5 %
Ambient conditions, mechanical
Vertical
10 - 57 Hz, 0.15 mm constant amplitude
According to IEC/EN 60068-2-6
Climatic environmental conditions
Clearance in air and creepage distances according to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Electro magnetic compatibility
2 kV, Supply cable
According to IEC/EN 61000-4-4
10 V/m at 0.08 - 1.0 GHz (according to IEC EN 61000-4-3)
3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3)
1 kV, Supply cables, asymmetrical, power pulses (Surge), EMC
According to IEC/EN 61000-4-5 Level 4
Terminal capacities
Electrical rating
20.4 - 28.8 V DC (Transistor outputs)
24 V DC (-15 %/+ 20 % - power supply)
24 V DC (transistor outputs)
24 V DC (digital inputs)
Short-circuit rating
Communication
Cable
100 m, unscreened, Digital inputs 24 V AC
Input/Output
20 ms, Digital Inputs 12 V DC, Delay time from 1 to 0, Debounce ON
0.1 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 0 to 1, Debounce OFF
20 ms, Digital Inputs 12 V DC, Delay time from 0 to 1, Debounce ON
Current
8 Transistor Outputs
U = Uₑ - 1 V (signal 1 at Iₑ = 0.5 A, transistor outputs)