View larger
EASY-E4-AC-12RCX1P 197509 Y7-197509 EATON ELECTRIC EASY-E4-AC-12RCX1P
EASY-E4-AC-12RCX1P
197509
Y7-197509
EATON - MOELLER
1 Pcs.
Automation > Logic module
Easy E4 Nanocontrollers
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller EASY-E4-AC-12RCX1P serves as an advanced control relay used to automate processes, manage sequential operations, and monitor parameters in machinery installations. This controller processes input signals to execute programmed logic and drive output components reliably.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Supply voltage AC 50 Hz (EF007532): 85 V
- Supply voltage AC 60 Hz (EF007533): 85 V
- Supply voltage DC (EF007534): 85 V
- Voltage type (supply voltage) (EF002991): AC
- Switching current (EF000188): 8 A
- Power consumption (EF000346): 4 W
- Number of analogue inputs (EF001994): 0
- Number of analogue outputs (EF001995): 0
- Number of digital inputs (EF001992): 8
- Number of digital outputs (EF001993): 4
- With relay output (EF003198): Yes
- Number of HW-interfaces industrial Ethernet (EF003020): 1
- Number of interfaces PROFINET (EF006932): 0
- Number of HW-interfaces RS-232 (EF003021): 0
- Number of HW-interfaces RS-422 (EF003022): 0
- Number of HW-interfaces RS-485 (EF003023): 0
More info
▲General specifications
IEC 60068-2-27
IEC/EN 61000-4
EN 55011
EN 55022
IEC 60068-2-6
UL Listed
UL Category Control No.: NRAQ, NRAQ7
IEC/EN 61131-2
IEC 60068-2-30
EN 61010
IEC/EN 61000-6-3
IEC/EN 61000-6-2
EN 50178
UL File No.: E205091
DNV GL
CE
UL hazardous location class I
UL hazardous location division 2
UL hazardous location group A (acetylene)
UL hazardous location group B (hydrogen)
UL hazardous location group C (ethylene)
UL hazardous location group D (propane)
Features & Functions
Networkable (Ethernet)
Timer
Real time clock
General
50/60 Hz (Digital inputs, at 24 V DC)
25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, with upstream electrical device)
25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, uncompensated)
25,000 Operations (Filament bulb load at 500 W, 115/120 V AC)
25,000 Operations (Filament bulb load at 1000 W, 230/240 V AC)
Screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Front build in possible
Rail mounting possible
TCP/IP
≤ 5 %
10 Hz, Relay outputs
2 Hz, Resistive load/lamp load, Relay outputs
R 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes DC
Ambient conditions, mechanical
Vertical
10 - 57 Hz, 0.15 mm constant amplitude
57 - 150 Hz, 2 g constant acceleration
Climatic environmental conditions
Condensation: prevent with appropriate measures
Electro magnetic compatibility
2 kV, Supply cable
According to IEC/EN 61000-4-4
10 V/m at 0.08 - 1.0 GHz (according to IEC EN 61000-4-3)
3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3)
2 kV, Supply cables, asymmetrical, power pulses (Surge), EMC
According to IEC/EN 61000-4-5 Level 4
Terminal capacities
0.2 - 4 mm² (AWG 22 - 12), solid
Electrical rating
300000 Operations at AC-15, 250 V AC, 3 A (600 Ops./h)
Max. 300 V DC
85 - 264 V AC
100/110/115/120/230/240 AC (-15 %/+10 %)
10 A AC, at 240 V AC (UL/CSA)
8 A DC, at 24 V DC (UL/CSA)
5 A AC, max. thermal continuous current cos ϕ = 1 at B 300 (UL/CSA)
Short-circuit rating
Communication
Push in terminals
Status indication of Ethernet: LED
Cable
40 m (max. permissible per input I1 to I6), Digital inputs 115/230 V AC
Input/Output
± 1 %, Repetition accuracy of timing relays (of values)
21 ms typ., Digital Inputs 100 - 240 V AC 60 Hz (I1 - I8), Delay time from 1 to 0, Debounce OFF
16⅔ ms, Digital inputs 115/230 V AC 60 Hz (I7, I8), Delay time from 1 to 0, Debounce OFF
0.03 ms typ., Digital Inputs 100 - 240 V DC (I1 - I8), Delay time from 0 to 1, Debounce OFF
0.03 ms typ., Digital Inputs 100 - 240 V DC (I1 - I8), Delay time from 1 to 0, Debounce OFF
20 ms typ., Digital Inputs 100 - 240 V DC (I1 - I8), Delay time from 0 to 1, Debounce ON
20 ms, Digital inputs 115/230 V AC 50 Hz (I7, I8), Delay time from 1 to 0, Debounce OFF
20 ms typ., Digital Inputs 100 - 240 V DC (I1 - I8), Delay time from 1 to 0, Debounce ON
2 x 4 mA (I7 - I8, at 115 V AC, 60 Hz, at signal 1)
6 x 0.25 mA (I1 - I8, at 115 V AC, 60 Hz, at signal 1)
Condition 0: 0 - 40 V AC, Digital inputs, 115/230 V AC)
3600/360 VA (AC, at B 300)
Relay outputs in groups of 1
> 500 mA (Relay outputs, Recommended for load: 12 V AC/DC)
Current
4 Relay Outputs
Safety
Between Analog inputs and Digital inputs: no
Between Relay outputs: yes
Between Digital inputs 115/230 V AC and Interface: yes
Between Digital inputs 115/230 V AC and Memory card: no
300 V AC, Between two contacts, According to EN 50178