View larger
EASY-E4-AC-12RC1 197215 Y7-197215 EATON ELECTRIC Control relays, easyE4 (expandable, Ethernet), 100 240 V AC..
EASY-E4-AC-12RC1
197215
Y7-197215
EATON - MOELLER
1 Pcs.
Automation > Logic module
Easy E4 Nanocontrollers
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller EASY-E4-AC-12RC1 control relay provides flexible logic processing and signal routing for small automation tasks. Control relays of this type are widely integrated into electrical panels to sequence machinery, manage building services, and execute interlocking safety routines.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Manufacturer: Eaton Moeller
- Manufacturer part number: EASY-E4-AC-12RC1
- Catalogue code: 197215
- Catalogue title: EASY-E4-AC-12RC1 197215 Y7-197215 EATON ELECTRIC Control relays, easyE4 (expandable, Ethernet), 100 240 V AC..
- Product description: General specifications Product Name Eaton Moeller® series EASY Control relay Catalog Number 197215 Model Code EASY-E4-AC-12RC1 EAN 4015081939442 Product Length/Depth 58 mm Product Height 90 mm Product Width 72 mm Product;
- Manufacturer summary: Control relays, easyE4 (expandable, Ethernet), 100 - 240 V AC, 110 - 240 V DC, Inputs Digital: 8, Outputs Digital: 4 relais, screw terminal EASY-E4-AC-12RC1 Eaton Moeller® series EASY Control relays easyE4 with display (
More info
▲General specifications
IEC/EN 61000-6-2
CULus per UL 61010
IEC/EN 61000-4-2
IEC/EN 61131-2
IEC 60068-2-30
CSA-C22.2 No. 61010
EN 50178
IEC 60664
IEC 60068-2-27
IEC 60068-2-6
IEC/EN 61000-6-3
UL Listed
UL Category Control No.: NRAQ, NRAQ7
UL File No.: E205091
DNV GL
CE
UL hazardous location class I
UL hazardous location division 2
UL hazardous location group A (acetylene)
UL hazardous location group B (hydrogen)
UL hazardous location group C (ethylene)
UL hazardous location group D (propane)
Features & Functions
Expandable
Display indication of 6 lines x 16 characters
Timer
Keypad
Display
Real time clock
General
50/60 Hz (Digital inputs, at 24 V DC)
25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, with upstream electrical device)
25,000 Operations (Filament bulb load at 1000 W, 230/240 V AC)
25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, uncompensated)
25,000 Operations (Filament bulb load at 500 W, 115/120 V AC)
Rail mounting possible
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Wall mounting/direct mounting
Front build in possible
MODBUS
2 Hz, Resistive load/lamp load, Relay outputs
0.5 Hz, Inductive load, Relay outputs
R 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes DC
Ambient conditions, mechanical
Vertical
57 - 150 Hz, 2 g constant acceleration
10 - 57 Hz, 0.15 mm constant amplitude
Climatic environmental conditions
Clearance in air and creepage distances according to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Electro magnetic compatibility
According to IEC/EN 61000-4-4
2 kV, Supply cable
1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3)
10 V/m at 0.8 - 1.0 GHz (according to IEC EN 61000-4-3)
According to IEC/EN 61000-4-5, power pulses (Surge), EMC
2 kV, Supply cables, asymmetrical, power pulses (Surge), EMC
Terminal capacities
0.2 - 2.5 mm² (22 - 12 AWG), flexible with ferrule
Electrical rating
200000 Operations at DC-13, 24 V DC, 1 A (500 Ops./h)
100/110/115/120/230/240 AC (-15 %/+10 %)
85 - 264 V AC
Max. 300 V AC
110/120 V DC (power supply)
240 V AC
8 A AC, at 240 V AC (UL/CSA)
8 A DC, at 24 V DC (UL/CSA)
1 A DC, at R 300 (UL/CSA)
Short-circuit rating
Communication
Ethernet: RJ45 plug, 8-pole
Cable
40 m (max. permissible per input I1 to I6), Digital inputs 115/230 V AC
Input/Output
± 2 s/day, Real-time clock to inputs (± 0.2 h⁄Year)
20 ms typ., Digital Inputs 100 - 240 V DC (I1 - I8), Delay time from 0 to 1, Debounce ON
20 ms, Digital inputs 115/230 V AC 50 Hz (I7, I8), Delay time from 1 to 0, Debounce OFF
21 ms typ., Digital Inputs 100 - 240 V AC 60 Hz (I1 - I8), Delay time from 1 to 0, Debounce OFF
16⅔ ms, Digital inputs 115/230 V AC 60 Hz (I7, I8), Delay time from 1 to 0, Debounce OFF
0.03 ms typ., Digital Inputs 100 - 240 V DC (I1 - I8), Delay time from 0 to 1, Debounce OFF
0.03 ms typ., Digital Inputs 100 - 240 V DC (I1 - I8), Delay time from 1 to 0, Debounce OFF
20 ms typ., Digital Inputs 100 - 240 V DC (I1 - I8), Delay time from 1 to 0, Debounce ON
6 x 0.25 mA (I1 - I6, at 115 V AC, 60 Hz, at signal 1)
2 x 6 mA (I7 - I8, at 230 V AC, 50 Hz, at signal 1)
6 x 0.5 mA (I1 - I6, at 230 V AC, 50 Hz, at signal 1)
Condition 1: 79 - 264 V AC, Digital inputs, 115/230 V AC)
28/28 VA (DC, at R 300)
4 Relay Outputs
> 500 mA (Relay outputs, Recommended for load: 12 V AC/DC)
Voltage
Current
Safety
Between Relay outputs and expansion devices: yes
Between Digital inputs 115/230 V AC: no
Between Relay outputs and Inputs: yes
Between Digital inputs 115/230 V AC and base unit: yes
Between Digital inputs 115/230 V AC and Outputs: yes
Between Digital inputs 115/230 V AC and Ethernet: yes
Between Relay outputs and Ethernet: yes
Basic isolation: 600 V AC (Relay outputs)
Between Digital inputs 115/230 V AC and expansion devices: yes
Safe isolation according to EN 50178: 300 V AC (Relay outputs)
Between Relay outputs: yes
Between Digital inputs 115/230 V AC and Memory card: no
Between Relay outputs and Power supply: yes
Between Digital inputs 115/230 V AC and Interface: yes
300 V AC, Between coil and contact, According to EN 50178