EATON - MOELLER DX-EMC34-019-FS3 DX-EMC34-019-FS3 179611 EATON ELECTRIC EMC filter for variable frequency drives 3-phase 520 V 19 A View larger
Images are for illustrative purposes only. Please refer to data sheet for details

DX-EMC34-019-FS3 179611 EATON ELECTRIC EMC filter for variable frequency drives 3-phase 520 V 19 A

DX-EMC34-019-FS3

179611

EATON - MOELLER

1 Pcs.

EMC filter for variable frequency drives; 3-phase 520 V; 19 A EMC filter for frequency converter. Three-phase 600 V. 19 A Radio interference suppression filter, three-phase, ULN= max. 520 + 10% V, 19 A, For use with: DE1, DE11, DC1, DA1 Radio interference suppression filter, Description: three-phase, Mains voltage (50/60Hz): ULN= max. 520 + 10% V, Rated operational current: Ie= 19 A, For use with: DE1, DE11, DC1, DA1, Degree of Protection: IP00, IP20 when connected, Connection type: Connection terminal, PE stud, prefabricated cables, Weight: m 3,5 kg, Notes: Base-mounted filter, side-mounting filter, Standards: EN 50178, IEC 61800-3, EN 61800-3 incl. A11

Automation > Accessories/spare parts for frequency controller
Power XL Frequency Converters

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Radio interference suppression filter, three-phase, ULN= max. 520 + 10% V, 19 A, For use with: DE1, DE11, DC1, DA1
Radio interference suppression filter, Description: three-phase, Mains voltage (50/60Hz): ULN= max. 520 + 10% V, Rated operational current: Ie= 19 A, For use with: DE1, DE11, DC1, DA1, Degree of Protection: IP00, IP20 when connected, Connection type: Connection terminal, PE stud, prefabricated cables, Weight: m 3,5 kg, Notes: Base-mounted filter, side-mounting filter, Standards: EN 50178, IEC 61800-3, EN 61800-3 incl. A11

Delivery program

Description
three-phase
Mains voltage (50/60Hz) [ULN]
max. 520 + 10% V
Rated operational current [Ie]
19 A
For use with
DE1, DE11, DC1, DA1
Degree of Protection
IP00
IP20 when connected
Connection type
Connection terminal, PE stud, prefabricated cables
Weight [m]
3,5 kg
Notes
Base-mounted filter, side-mounting filter

Technical data

General
Standards
EN 50178, IEC 61800-3, EN 61800-3 incl. A11
Environmental conditionsAltitude
Up to 2000 m a.s.l.; observe derating at higher altitudes m
Degree of Protection
IP00
IP20 when connected

Design verification as per IEC/EN 61439

Technical data for design verification
Degree of Protection
IP20
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 7.0

Low-voltage industrial components (EG000017) / Accessories for frequency controller (EC002025)
Electric engineering, automation, process control engineering / Electrical drive / Static frequency converter / Static frequency converter (accessory) ([email protected] [AFR303003])
Type of accessory
Filter

ETIM for 179611 Low-voltage industrial controls and switchgear (EC002025)
Feature Name Feature Value
Type of accessory/spare part (EF000215) Filter
Accessory (EF013236) Yes