An Eaton Moeller electronic soft starter provides reliable control over motor acceleration ramps, protecting industrial drive trains from sudden torque impacts and reducing peak electrical demand. These units are standard equipment in modern HVAC, pump, and conveyor control panels. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Rated operation current Ie at 40 °C Tu (EF007039): 200 A
- Rated operating voltage Ue (EF002418): 230 V
- Rated power three-phase motor, inline, at 230 V (EF007053): 55 kW
- Rated power three-phase motor, inline, at 400 V (EF007054): 110 kW
- Function (EF000030): Single direction
- Internal bypass (EF009214): Yes
- With display (EF000458): No
- Torque control (EF009215): No
- Rated surrounding temperature without derating (EF007074): 40 °C
- Rated control supply voltage AC 50 Hz (EF003978): 24 V
- Rated control supply voltage AC 60 Hz (EF003979): 24 V
- Rated control supply voltage DC (EF003980): 24 V
- Voltage type for actuating (EF008242): AC/DC
- Integrated motor overload protection (EF007297): No
- Degree of protection (IP) (EF005474): IP20
- Degree of protection (NEMA) (EF011959): 1
More info
▲General specifications
GB 14048.6
CSA-C22.2 No 0-M91
UL
UkrSEPRO
CSA Class No.: 321106
CSA-C22.2 No 14-05
CE
C-Tick
IEC/EN 60947-4-2
CSA22.2-14
UL 508
UL File No.: E251034
CSA File No.: 2511305
Features & Functions
Internal bypass contacts
Soft start function
Suppression of DC components for motors
Single direction
Suppression of closing transients
Potential isolation between power and control sections
General
IP20
Ambient conditions, mechanical
Climatic environmental conditions
Above 1000 m with 1 % derating per 100 m
Damp heat, cyclic, to IEC 60068-2-30
Cold to EN 60068-2-1
Main conducting paths
3 x 170M5008, Type „2“ coordination (additional with the fuses for coordination type „1“), Main conducting paths
Motor rating
Terminal capacities
10 x 16 x 0.8 mm, Main cables
1 x (0.5 - 1.5) mm², Control circuit cables
2 x (4 - 70) mm², Main cables
2 x (0.5 - 1.0) mm², Control circuit cables
1 x (4 - 185) mm², Main cables
2 x (21 - 18), Control circuit cables
1 x (21 - 14), Control circuit cables
1 x (12 - 350 kcmil), Main cables
1 x (0.5 - 1.5) mm², Control circuit cables
1 x (25 - 70) mm², Main cables
2 x (6 - 25) mm², Main cables
0.6 x 3.5 mm, Terminal screws, Control circuit cables
6 Nm (≤ 10 mm²)
0.4 Nm, Screw terminals, Control circuit cables
Control circuit
0,6 A/50 ms, Control circuit, Regulator supply at peak performance (close bypass) at 24 V DC
50 mA, Control circuit, Regulator supply
0 - 3 V, DC operated
Input/Output
24 V DC (-15 %/+10 %)
24 V AC
Soft start function
Max. 100 %, Soft start function, Start voltage = turn-off voltage