View larger
Images are for illustrative purposes only. Please refer to data sheet for details
DS7-340SX160N0-L 171753 Y7-171753 EATON ELECTRIC Soft starter, 160 A, 200 480 V AC, 24 V AC/DC, Frame size F..
DS7-340SX160N0-L
171753
Y7-171753
EATON - MOELLER
1 Pcs.
Soft starter, 160 A, 200 - 480 V AC, 24 V AC/DC, Frame size FS4, Ambient temperature Operation -40 - +40 °C
DS7-340SX160N0-L
Soft starter, Description: With internal bypass contacts, Function: Soft starters for three-phase loads, Mains supply voltage (50/60 Hz): ULN= 200 - 480 V AC, Supply voltage: Us= 24 V AC/DC, Control voltage: UC= 24 V AC, 24 V DC, Assigned motor rating (Standard connection, In-Line) at 400 V, 50 Hz: P= 90 kW, at 460 V, 60 Hz: P= 125 HP, Rated operational current AC-53: Ie= 160 A, Rated operational voltage: Ue= 200 V, 230 V, 400 V, 480 V, Connection to SmartWire-DT: no, Frame size: FS4, Standards: IEC/EN 60947-4-2, UL 508, CSA22.2-14
Automation > Soft starter
Standard Soft Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller DS7-340SX160N0-L electronic soft starter provides smooth motor starting performance, reducing mechanical strain in industrial production lines.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated operation current Ie at 40 °C Tu (EF007039): 160 A
- Rated operating voltage Ue (EF002418): 230 V
- Rated power three-phase motor, inline, at 230 V (EF007053): 54 kW
- Rated power three-phase motor, inline, at 400 V (EF007054): 90 kW
- Function (EF000030): Single direction
- Internal bypass (EF009214): Yes
- With display (EF000458): No
- Torque control (EF009215): No
- Rated surrounding temperature without derating (EF007074): 40 °C
- Rated control supply voltage AC 50 Hz (EF003978): 24 V
- Rated control supply voltage AC 60 Hz (EF003979): 24 V
- Rated control supply voltage DC (EF003980): 24 V
- Voltage type for actuating (EF008242): AC/DC
- Integrated motor overload protection (EF007297): No
- Degree of protection (IP) (EF005474): IP20
- Degree of protection (NEMA) (EF011959): 1
More info
▲General specifications
Product Name
Eaton DS7 Soft starter
Catalog Number
171753
Model Code
DS7-340SX160N0-L
EAN
4015081680771
Product Length/Depth
178 mm
Product Height
215 mm
Product Width
105 mm
Product Weight
3.799 kg
Certifications
CSA-C22.2 No 14-05
GB 14048.6
CSA-C22.2 No 0-M91
UL 508
CSA File No.: 2511305
CSA22.2-14
C-Tick
UL
CSA
CSA Class No.: 321106
UL File No.: E251034
IEC/EN 60947-4-2
CE
UkrSEPRO
GB 14048.6
CSA-C22.2 No 0-M91
UL 508
CSA File No.: 2511305
CSA22.2-14
C-Tick
UL
CSA
CSA Class No.: 321106
UL File No.: E251034
IEC/EN 60947-4-2
CE
UkrSEPRO
Features & Functions
Fitted with:
Internal bypass
Internal bypass contacts
Internal bypass contacts
Functions
Suppression of closing transients
Soft start function
Potential isolation between power and control sections
Min. ramp time 1 s - fast switching (semiconductor contactor)
Suppression of DC components for motors
Single direction
Soft start function
Potential isolation between power and control sections
Min. ramp time 1 s - fast switching (semiconductor contactor)
Suppression of DC components for motors
Single direction
General
Class
Other
Connection to SmartWire-DT
No
Degree of protection
IP20
NEMA 1
NEMA 1
Frame size
FS4
Mains voltage - max
480 V
Mains voltage - min
200 V
Overvoltage category
II
Pollution degree
2
Radio interference class
Class B (EN 55011)
Suitable for
Branch circuits, (UL/CSA)
Type
Soft starter for three-phase loads
Voltage type
AC/DC
Ambient conditions, mechanical
Mounting position
Vertical
Shock resistance
8 g, 11 ms, Mechanical
Vibration resistance
2M2 to EN 60721-3-2
Climatic environmental conditions
Altitude
Above 1000 m with 1 % derating per 100 m
Max. 2000 m
Max. 2000 m
Ambient operating temperature - max
40 °C
Ambient operating temperature - min
-40 °C
Climatic proofing
Damp heat, constant, to IEC 60068-2-3
Cold to EN 60068-2-1
Damp heat, cyclic, to IEC 60068-2-30
Cold to EN 60068-2-1
Damp heat, cyclic, to IEC 60068-2-30
Main conducting paths
Overload cycle
AC-53a: 3 - 5: 75 - 10
Rated operational current (Ie) at AC-53
160 A
Rated operational voltage (Ue) - max
480 V
Rated operational voltage (Ue) - min
230 V
Short-circuit protection rating
3 x 170M5008, Type „2“ coordination (additional with the fuses for coordination type „1“), Main conducting paths
NZMN2-M200, Type “1” coordination, Main conducting paths
NZMN2-M200, Type “1” coordination, Main conducting paths
Supply frequency
50/60 Hz, fLN, Main circuit
Voltage rating - max
480 V
Motor rating
Assigned motor power at 200/208 V, 60 Hz, 3-phase
50 HP
Assigned motor power at 220/230 V, 60 Hz, 3-phase
60 HP
Assigned motor power at 460/480 V, 60 Hz, 3-phase
125 HP
Rated operational power at 220/230 V, 50 Hz
45 kW
Rated operational power at 400 V, 50 Hz
90 kW
Terminal capacities
Terminal capacity (copper band)
2 x 9 x 0.8 mm, Main cables
10 x 16 x 0.8 mm, Main cables
10 x 16 x 0.8 mm, Main cables
Terminal capacity (flexible with ferrule)
2 x (0.5 - 0.75) mm², Control circuit cables
1 x (0.5 - 1.5) mm², Control circuit cables
1 x (0.5 - 1.5) mm², Control circuit cables
Terminal capacity (solid)
2 x (0.5 - 1.0) mm², Control circuit cables
2 x (4 - 70) mm², Main cables
1 x (4 - 185) mm², Main cables
1 x (0.5 - 2.5) mm², Control circuit cables
2 x (4 - 70) mm², Main cables
1 x (4 - 185) mm², Main cables
1 x (0.5 - 2.5) mm², Control circuit cables
Terminal capacity (solid/stranded AWG)
2 x (12 - 00), Main cables
1 x (12 - 350 kcmil), Main cables
2 x (21 - 18), Control circuit cables
1 x (21 - 14), Control circuit cables
1 x (12 - 350 kcmil), Main cables
2 x (21 - 18), Control circuit cables
1 x (21 - 14), Control circuit cables
Terminal capacity (stranded)
1 x (25 - 70) mm², Main cables
2 x (6 - 25) mm², Main cables
2 x (0.5 - 1.0) mm², Control circuit cables
1 x (0.5 - 1.5) mm², Control circuit cables
2 x (6 - 25) mm², Main cables
2 x (0.5 - 1.0) mm², Control circuit cables
1 x (0.5 - 1.5) mm², Control circuit cables
Screwdriver size
0.6 x 3.5 mm, Terminal screws, Control circuit cables
PZ2, 1 x 6 mm, Terminal screw, Standard screwdriver
PZ2, 1 x 6 mm, Terminal screw, Standard screwdriver
Tightening torque
6 Nm (≤ 10 mm²)
0.4 Nm, Screw terminals, Control circuit cables
9 Nm (> 10 mm²)
0.4 Nm, Screw terminals, Control circuit cables
9 Nm (> 10 mm²)
Control circuit
Current consumption
0,6 A/50 ms, Control circuit, Regulator supply at peak performance (close bypass) at 24 V DC
1.6 mA, Control circuit, Digital inputs, External 24 V
50 mA, Control circuit, Regulator supply
1.6 mA, Control circuit, Digital inputs, External 24 V
50 mA, Control circuit, Regulator supply
Drop-out time
350 ms, Control circuit, Digital Inputs, DC operated
Drop-out voltage
0 - 3 V, DC operated
AC operated: 0 - 3 V, AC operated
AC operated: 0 - 3 V, AC operated
Rated control supply voltage (Us) at AC, 50 Hz - min
24 V
Rated control supply voltage (Us) at AC, 50 Hz - min
24 V
Rated control supply voltage (Us) at AC, 60 Hz - max
24 V
Rated control supply voltage (Us) at AC, 60 Hz - min
24 V
Rated control supply voltage (Us) at DC - max
24 V
Rated control supply voltage (Us) at DC - min
24 V
Input/Output
Number of outputs
2 Relay Outputs (TOR, Ready)
Output voltage
250 V AC (relay outputs)
Protection
Finger and back-of-hand proof, Protection against direct contact
Rated control voltage (Uc)
24 V DC (-15 %/+10 %)
24 V AC
24 V DC
24 V AC
24 V DC
Rated operational current (Ie) at AC-11
1 A
Soft start function
Application
Delay time
0 - 30 s, Soft start function, Ramp times
Ramp/run-up time
30 s
Start voltage
Min. 30 %, Soft start function, Start voltage = turn-off voltage
Max. 100 %, Soft start function, Start voltage = turn-off voltage
Max. 100 %, Soft start function, Start voltage = turn-off voltage
Design verification
Equipment heat dissipation, current-dependent Pvid
30 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
160 A
Static heat dissipation, non-current-dependent Pvs
30 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.