View larger
DS7-340SX007N0-L 171741 Y7-171741 EATON ELECTRIC Soft starter, 7 A, 200 480 V AC, 24 V AC/DC, Frame size FS1..
DS7-340SX007N0-L
171741
Y7-171741
EATON - MOELLER
1 Pcs.
Automation > Soft starter
Standard Soft Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for smooth motor starting, this Eaton Moeller DS7-340SX007N0-L soft starter limits inrush current to prevent premature wear on industrial drivetrains. Engineers rely on these components to protect gearboxes, belts, and connected machinery across diverse manufacturing environments.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated operation current Ie at 40 °C Tu (EF007039): 7 A
- Rated operating voltage Ue (EF002418): 230 V
- Rated power three-phase motor, inline, at 230 V (EF007053): 1.5 kW
- Rated power three-phase motor, inline, at 400 V (EF007054): 3 kW
- Function (EF000030): Single direction
- Internal bypass (EF009214): Yes
- With display (EF000458): No
- Torque control (EF009215): No
- Rated surrounding temperature without derating (EF007074): 40 °C
- Rated control supply voltage AC 50 Hz (EF003978): 24 V
- Rated control supply voltage AC 60 Hz (EF003979): 24 V
- Rated control supply voltage DC (EF003980): 24 V
- Voltage type for actuating (EF008242): AC/DC
- Integrated motor overload protection (EF007297): No
- Degree of protection (IP) (EF005474): IP20
- Degree of protection (NEMA) (EF011959): 1
More info
▲General specifications
CSA22.2-14
GB 14048.6
CSA File No.: 2511305
UkrSEPRO
UL File No.: E251034
CE
CSA Class No.: 321106
CSA-C22.2 No 14-05
IEC/EN 60947-4-2
CSA
UL
UL 508
C-Tick
Features & Functions
Internal bypass contacts
Potential isolation between power and control sections
Soft start function
Suppression of closing transients
Single direction
Min. ramp time 1 s - fast switching (semiconductor contactor)
General
NEMA 1
Ambient conditions, mechanical
Climatic environmental conditions
Max. 2000 m
Damp heat, constant, to IEC 60068-2-3
Damp heat, cyclic, to IEC 60068-2-30
Main conducting paths
3 x 170M1361, Type „2“ coordination (additional with the fuses for coordination type „1“), Main conducting paths
Motor rating
Terminal capacities
1 x (0.75 - 2.5) mm², Main cables
2 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Main cables
1 x (0.75 - 4) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Main cables
1 x (0.75 - 4) mm², Main cables
18 - 10, Control circuit cables
0.6 x 5.5 mm/1 x 6 mm, Terminal screws, Control circuit cables
1.2 Nm, Screw terminals, Control circuit cables
Control circuit
1.6 mA, Control circuit, Digital inputs, External 24 V
AC operated: 0 - 3 V, AC operated
Input/Output
24 V DC
24 V AC
Soft start function
Max. 100 %, Soft start function, Start voltage = turn-off voltage