View larger
MSC-DE-32-M17(230V50HZ)
121747
Y7-121747
EATON - MOELLER
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
The DOL starter (complete devices) consists of a PKE motor protective circuit breaker and a DILM contactor.
With the adapter-less top-hat rail mounting of starters up to 15 A, only the motor-protective circuit-breaker on the top-hat rail requires an adapter.
The contactors are provided with mechanical support via a mechanical connection element.
Control wire guide with max. 6 conductors up to 2.5°mm external diameter or 4 conductors up to 3.5°mm external diameter.
From 16 A, the motor-protective circuit-breaker and contactor are mounted on the top-hat rail adapter plate.
The connection of the main circuit between PKE and contactor is established with electrical contact modules.
When using DILA-XHIT… auxiliary contacts with MSC-DE-... DOL starters, the plug-in electrical connectors can be removed without removing the front-mounted auxiliary contact.
Cannot be combined with NHI‐E…PKZ0‐C.
MSC-DEA... DOL starters are prepared for communications via SmartWire-DT. In order to be used this way, they first need to be expanded with the PKE-SWD-32 communications module.
Motor output | Rated motor current | |||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AC-3 | ||||||||||||||
| 220 V 230 V 240 V | 380 V 400 V | 415 V | 440 V | 500 V | 500 V with CL-PKZ0 | 660 V 690 V | ||||||||
| Iq= 100 kA | Iq=100 kA | Iq= 65 kA | Iq= 65 kA | Iq= 50 kA | Iq= 100 kA | Iq= 3 kA | ||||||||
| P | I | I | I | I | I | I | I | |||||||
| kW | A | A | A | A | A | A | A | |||||||
| 2.2 | 8.7 | - | - | - | - | - | - | |||||||
| 3 | 11.5 | - | - | - | - | - | - | |||||||
| 4 | 14.8 | 8.5 | 8.5 | - | - | - | - | |||||||
| 5.5 | - | 11.3 | 11.3 | 10.2 | 9 | 9 | - | |||||||
| 7.5 | - | 15.2 | 15.2 | 13.8 | 12.1 | 12.1 | 8.8 |