View larger
DMM-80/1 199969 Y8-199969 EATON ELECTRIC DMM-80/1
DMM-80/1
199969
Y8-199969
EATON - MOELLER
1 Pcs.
Connectors > Switch disconnector
DUMECO Switch-Disconnectors
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton DMM-80/1 switch-disconnector offers reliable manual circuit interruption capabilities within space-constrained distribution assemblies. Toggle-operated disconnectors are widely utilized across industrial applications to provide safe local power isolation.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product Name: Eaton DMM Switch-disconnector
- Catalog Number: 199969
- Model Code: DMM-80/1
- EAN: 5027590528719
- Product Length/Depth: 152 mm
- Product Height: 108 mm
- Product Width: 132 mm
- Product Weight: 0.916 kg
- Compliances: CE
- Features: Version as main switch Version as maintenance-/service switch
- Number of poles: Three-pole
- Actuator color: Black
- Actuator type: Toggle
- Degree of protection (front side): IP20
- Suitable for: Distribution board installation Ground mounting
- Rated operational power at AC-23A, 400 V, 50 Hz: 30 kW
More info
▲General specifications
| Product Name | Eaton DMM Switch-disconnector |
| Catalog Number | 199969 |
| Model Code | DMM-80/1 |
| EAN | 5027590528719 |
| Product Length/Depth | 152 mm |
| Product Height | 108 mm |
| Product Width | 132 mm |
| Product Weight | 0.916 kg |
| Compliances | CE |
Features & Functions
| Features | Version as main switch Version as maintenance-/service switch |
| Number of poles | Three-pole |
General information
| Actuator color | Black |
| Actuator type | Toggle |
| Degree of protection | Other |
| Degree of protection (front side) | IP20 |
| Suitable for | Distribution board installation Ground mounting |
Electrical rating
| Rated operational power at AC-23A, 400 V, 50 Hz | 30 kW |
| Rated operational power at AC-3, 380/400 V, 50 Hz | 0 kW |
| Rated operational voltage (Ue) at AC - max | 690 V |
| Rated uninterrupted current (Iu) | 80 A |
Short-circuit rating
| Rated conditional short-circuit current (Iq) | 50 kA |
| Rated short-time withstand current (Icw) | 2.5 kA |
Contacts
| Number of auxiliary contacts (change-over contacts) | 0 |
| Number of auxiliary contacts (normally closed contacts) | 0 |
| Number of auxiliary contacts (normally open contacts) | 0 |
Design verification
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | UV resistance only in connection with protective shield. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |