EATON - MOELLER XVTL-MP/BF-8/3/20-IVS XVTL-MP/BF-8/3/20-IVS 118944 EATON ELECTRIC Distribution cabinet, IVS, HxWxD 2000x800x300mm, IP55 View larger
Images are for illustrative purposes only. Please refer to data sheet for details

XVTL-MP/BF-8/3/20-IVS 118944 EATON ELECTRIC Distribution cabinet, IVS, HxWxD 2000x800x300mm, IP55

XVTL-MP/BF-8/3/20-IVS

118944

EATON - MOELLER

1 Pcs.

Distribution cabinet, IVS, HxWxD=2000x800x300mm, IP55 Fragment basic equipment for XVTL-MP/BF...-IVS (IP55), consisting of frame, rear panel, door (slim door) with XALP (rotary lever) and XALA (conversion kit for half cylinder), top cover (prepared for F3A gland plate insert), mounting system for the IVS mounting units, insulating surround with installed insulated support brackets. For IVS mounting units, refer to the IVS service system catalog. Sheet steel, with powder coating RAL 7035

Automation > Enclosure/switchgear cabinet (empty)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The Eaton Moeller distribution cabinet, part number XVTL-MP/BF-8/3/20-IVS (118944), serves as a robust electrical enclosure designed for centralized power distribution and sub-circuit management. IVS system cabinets provide organized, safe housing for modular switching and metering assemblies.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Rated operational voltage: U e
  • Rated frequency: f
  • Rated operational current: I e
  • Individual enclosure, free-standing: P V
  • Starting enclosure, free-standing: P V
  • Middle enclosure, free-standing: P V
  • Individual enclosure for wall mounting: P V
  • Starting enclosure for wall mounting: P V
  • Middle enclosure for wall mounting: P V
  • Individual enclosure, free-standing: P V
  • Starting enclosure, free-standing: P V
  • Middle enclosure, free-standing: P V
  • Individual enclosure for wall mounting: P V
  • Starting enclosure for wall mounting: P V
  • Middle enclosure for wall mounting: P V
  • Width (EF000008): 308.5 mm

More info

▲
Delivery programme
Product range
Service distribution board IVS
Basic function
Combination enclosures
Single unit/Complete unit
Complete housing
Degree of Protection
IP55 (with door and flange)
Description
Basic enclosure xVtl
Including open cable entries top, prepared for F3A flange
Material
Sheet steel
Surface finish
Polyester powder coating
Phosphated
RAL 7035, light grey
Colour
RAL 7035, light grey
Information about equipment supplied
including frame, doors, back plate, top plate and branding strip
Including support frame for the IVS mounting units
including insulating surround and mounted insulated support bracket
Without side walls
Width
mm 800
Height
mm 2000
Depth
mm 300
Technical data
General
Standards
EN 60439-1/3
IEC 62208
Protection class
1
Degree of Protection
IP55 (with door and flange)
Power loss
Max. admissible heat dissipation, ambient air temperature +35 °C
W 429
Weight
kg 111
Material characteristics
Material
Sheet steel
Surface treatment
Painting, phosphated and polyester powder coating
Surface finish
Polyester powder coating
Phosphated
RAL 7035, light grey
Colour
RAL 7035, light grey
Material characteristics
Type Door
Doors with covered hinges
Can be removed from 90°
door opening angle
120° (single mounting)
120° (combination mounting)
Door interlock
Roller lever lock
Three-point interlock
Material properties
Mechanical
Impact resistance
IK07
Cable entry
Various covers allow cable entry from above and/or below
Electrical
Rated operational voltage
Ue V 690
Rated frequency
f Hz 50
Rated operational current
Ie CSA 630
Max. admissible heat dissipation, ambient air temperature +35 °C
W 429
Earthings
Screw M10 (base frame)
M6 weld stud (enclosure side plate, top, bottom panel)
Taptite screw M6 (door)
Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data for design verification
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees, calculated as per IEC 60890
Individual enclosure, free-standing
PV CO 208
Starting enclosure, free-standing
PV CO 201
Middle enclosure, free-standing
PV CO 195
Individual enclosure for wall mounting
PV CO 191
Starting enclosure for wall mounting
PV CO 193
Middle enclosure for wall mounting
PV CO 174
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees, calculated as per IEC 60890
Individual enclosure, free-standing
PV CO 417
Starting enclosure, free-standing
PV CO 404
Middle enclosure, free-standing
PV CO 392
Individual enclosure for wall mounting
PV CO 382
Starting enclosure for wall mounting
PV CO 387
Middle enclosure for wall mounting
PV CO 348
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Not applicable.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Not applicable.
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
Met; assembled and secured as per the latest applicable instruction leaflet.
10.2.6 Mechanical impact
IK10
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
IP55
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
< 0.1 Ω; meets the product standard's requirements.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength
Ui= 690 V AC
10.9.3 Impulse withstand voltage
6 kV
10.9.4 Testing of enclosures made of insulating material
Does not apply to metal enclosures.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.