View larger
DILMS150-22(RAC240) 191752 Y7-191752 EATON ELECTRIC Safety device, 3 pole + 2 N/O + 2 N/C, 75 kW/400V/AC3
DILMS150-22(RAC240)
191752
Y7-191752
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller DILMS150-22(RAC240) Safety device is an industrial switching unit designed with integrated safety features to protect personnel and machinery during emergency shutdowns and automated operational sequences. Safety contactors are critical elements in certified machine safety architectures.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 230 V
- Rated control supply voltage AC 60 Hz (EF003979): 240 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Screw connection
- Operating voltage AC 50 Hz (EF008206): 230 V
- Operating voltage AC 60 Hz (EF008207): 230 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 190 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 150 A
- Rated operation power at AC-3, 400 V (EF001364): 75 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 65 A
- Rated operation power at AC-4, 400 V (EF008496): 33 kW
- Rated operation power NEMA (EF011960): 93 kW
- Modular version (EF001126): No
- Width (EF000008): 90 mm
More info
▲General specifications
CSA-C22.2 No. 60947-4-1-14
UL
CSA
IEC/EN 60947-4-1
CSA Class No.: 2411-03, 3211-04
UL 60947-4-1
UL File No.: E29096
VDE 0660
CE
UL Category Control No.: NLDX
IEC/EN 60947
General
Suppressor circuit in actuating electronics
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
2 x (10 - 70) mm², Main cables
2 x (0.75 - 2.5) mm², Control circuit cables
1 x (10 - 95) mm², Main cables
2 x (0.75 - 2.5) mm², Control circuit cables
Single 8…3/0, double 8…2/0, Main cables
2 x (16 - 70) mm², Main cables
5 mm AF, Hexagon socket-head spanner, Terminal screw, Main cables
M10, Terminal screw, Main cables
0.8 x 5.5/1 x 6 mm, Terminal screw, Control circuit cables, Standard screwdriver
1.2 Nm, Screw terminals, Control circuit cables
Electrical rating
Short-circuit rating
600 A, max. CB, SCCR (UL/CSA)
10 kA, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
250 A, max. CB, SCCR (UL/CSA)
300/300 A, Class J, max. Fuse, SCCR (UL/CSA)
350 A, max. CB, SCCR (UL/CSA)
30 kA, CB, SCCR (UL/CSA)
300/600 A, Class J, max. Fuse, SCCR (UL/CSA)
Conventional thermal current Ith
Switching capacity
1 A, 250 V DC, (UL/CSA)
P300, DC operated (UL/CSA)
Magnet system
2.3 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
3.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Motor rating
Contacts
Special purpose ratings
160 A (600V 60Hz 3phase, 347V 60Hz 1phase)
900 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
99 A, 600 V 60 Hz 3-ph, (UL/CSA)
100 HP, 600 V 60 Hz 3-ph, (UL/CSA)
92 A, 200 V 60 Hz 3-ph, (UL/CSA)
30 HP, 200 V 60 Hz 3-ph, (UL/CSA)
104 A, 240 V 60 Hz 3-ph, (UL/CSA)
96 A, 480 V 60 Hz 3-ph, (UL/CSA)
75 HP, 480 V 60 Hz 3-ph, (UL/CSA)
540 A, LRA 480 V 60 Hz 3phase; (CSA)
90 A, FLA 480 V 60 Hz 3phase; (CSA)
90 A, FLA 600 V 60 Hz 3phase; (CSA)
160 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
160 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)