View larger
DILMS12-R23(110V50HZ,120V60HZ) 191735 Y7-191735 EATON ELECTRIC Safety device, 3 pole + 2 N/O + 3 N/C, electr..
DILMS12-R23(110V50HZ,120V60HZ)
191735
Y7-191735
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller DILMS12-R23(110V50HZ,120V60HZ) safety contactor is specifically engineered to protect personnel and machinery by providing failsafe power disconnection in automated safety circuits. Safety contactors combine standard load switching with monitored auxiliary contacts to ensure compliance with functional safety standards.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product Name: Eaton Moeller® series DILMS Safety contactor
- Catalog Number: 191735
- Model Code: DILMS12-R23(110V50HZ,120V60HZ)
- EAN: 4015081922482
- Product Length/Depth: 117 mm
- Product Height: 69 mm
- Product Width: 45 mm
- Product Weight: 0.296 kg
- Application: Contactors for Motors
- Degree of protection: IP20
- Emitted interference: According to EN 60947-1
- Interference immunity: According to EN 60947-1
- Lifespan, mechanical: 10,000,000 Operations (AC operated)
- Operating frequency: 9000 mechanical Operations/h (AC operated)
- Overvoltage category: III
- Pollution degree: 3
More info
▲General specifications
| Product Name | Eaton Moeller® series DILMS Safety contactor |
| Catalog Number | 191735 |
| Model Code | DILMS12-R23(110V50HZ,120V60HZ) |
| EAN | 4015081922482 |
| Product Length/Depth | 117 mm |
| Product Height | 69 mm |
| Product Width | 45 mm |
| Product Weight | 0.296 kg |
| Certifications | UL File No.: E29096 IEC/EN 60947 UL Category Control No.: NLDX CSA Class No.: 2411-03, 3211-04 UL 60947-4-1 VDE 0660 CE CSA-C22.2 No. 60947-4-1-14 CSA File No.: 012528 CSA UL IEC/EN 60947-4-1 |
| Catalog Notes |
|
General information
| Application | Contactors for Motors |
| Degree of protection | IP20 |
| Emitted interference | According to EN 60947-1 |
| Fitted with: | Electronically compatible microswitch N/C Electronically compatible microswitch N/O Mirror contact |
| Interference immunity | According to EN 60947-1 |
| Lifespan, mechanical | 10,000,000 Operations (AC operated) |
| Operating frequency | 9000 mechanical Operations/h (AC operated) |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product category | Safety contactors |
| Protection | Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274) |
| Rated impulse withstand voltage (Uimp) | 8000 V AC |
| Resistance per pole | 2.5 mΩ |
| Shock resistance | 5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 3.4 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 5.7 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 3.4 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms |
| Suitable for | Also motors with efficiency class IE3 |
| Utilization category | AC-1: Non-inductive or slightly inductive loads, resistance furnaces AC-4: Normal AC induction motors: starting, plugging, reversing, inching AC-3: Normal AC induction motors: starting, switch off during running |
| Voltage type | AC |
Climatic environmental conditions
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature - max | 60 °C |
| Ambient operating temperature (enclosed) - min | -25 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
| Ambient storage temperature - min | -40 °C |
| Ambient storage temperature - max | 80 °C |
| Climatic proofing | Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
Terminal capacities
| Terminal capacity (flexible with ferrule) | 1 x (0.75 - 2.5) mm² 2 x (0.75 - 2.5) mm² |
| Terminal capacity (solid) | 1 x (0.75 - 2.5) mm² 2 x (0.75 - 2.5) mm² 1 x (0.75 - 4) mm² |
| Terminal capacity (solid/stranded AWG) | Single 18 - 10, double 18 - 14 18 - 14 |
| Stripping length (main cable) | 10 mm |
| Stripping length (control circuit cable) | 10 mm |
| Screw size | M3.5, Terminal screw |
| Screwdriver size | 0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver 2, Terminal screw, Pozidriv screwdriver |
| Tightening torque | 1.2 Nm, Screw terminals |
Electrical rating
| Rated breaking capacity at 220/230 V | 120 A |
| Rated breaking capacity at 380/400 V | 120 A |
| Rated breaking capacity at 500 V | 100 A |
| Rated breaking capacity at 660/690 V | 70 A |
| Rated insulation voltage (Ui) | 690 V |
| Rated making capacity up to 690 V (cos phi to IEC/EN 60947) | 144 A |
| Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V | 22 A |
| Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V | 12 A |
| Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V | 12 A |
| Rated operational current (Ie) at AC-3, 440 V | 12 A |
| Rated operational current (Ie) at AC-3, 500 V | 10 A |
| Rated operational current (Ie) at AC-3, 660 V, 690 V | 7 A |
| Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V | 7 A |
| Rated operational current (Ie) at AC-4, 440 V | 7 A |
| Rated operational current (Ie) at AC-4, 500 V | 6 A |
| Rated operational current (Ie) at AC-4, 660 V, 690 V | 5 A |
| Rated operational current (Ie) at DC-1, 110 V | 20 A |
| Rated operational current (Ie) at DC-1, 220 V | 15 A |
| Rated operational current (Ie) at DC-1, 60 V | 20 A |
| Rated operational power at AC-3, 240 V, 50 Hz | 4 kW |
| Rated operational power at AC-3, 380/400 V, 50 Hz | 5.5 kW |
| Rated operational power at AC-3, 415 V, 50 Hz | 7 kW |
| Rated operational power at AC-4, 220/230 V, 50 Hz | 2 kW |
| Rated operational power at AC-4, 240 V, 50 Hz | 2.2 kW |
| Rated operational power at AC-4, 415 V, 50 Hz | 3.4 kW |
| Rated operational power at AC-4, 440 V, 50 Hz | 3.6 kW |
| Rated operational power at AC-4, 500 V, 50 Hz | 3.5 kW |
| Rated operational power at AC-4, 660/690 V, 50 Hz | 4.4 kW |
| Rated operational voltage (Ue) at AC - max | 690 V |
| Safe isolation | 400 V AC, Between the contacts, According to EN 61140 400 V AC, Between coil and contacts, According to EN 61140 |
Short-circuit rating
| Short-circuit current rating (basic rating) | 5 kA, 45 A max. fuse, SCCR (UL/CSA) 5 kA, 45 A max. CB, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 480 V) | 100 kA, 45 A CLASS J max. fuse, SCCR (UL/CSA) 30 kA, 25 A CLASS RK5 max. fuse, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 600 V) | 100 kA, 45 A CLASS J max. fuse, SCCR (UL/CSA) 30 kA, 25 A CLASS RK5 max. fuse, SCCR (UL/CSA) |
| Short-circuit protection rating (type 1 coordination) at 400 V | 35 A gG/gL |
| Short-circuit protection rating (type 1 coordination) at 690 V | 25 A gG/gL |
| Short-circuit protection rating (type 2 coordination) at 400 V | 20 A gG/gL |
| Short-circuit protection rating (type 2 coordination) at 690 V | 20 A gG/gL |
Conventional thermal current Ith
| Conventional thermal current Ith (1-pole, enclosed) | 45 A |
| Conventional thermal current Ith (3-pole, enclosed) | 18 A |
| Conventional thermal current Ith at 55°C (3-pole, open) | 21 A |
| Conventional thermal current Ith of main contacts (1-pole, open) | 50 A |
Switching capacity
| Switching capacity (main contacts, general use) | 20 A, Maximum motor rating (UL/CSA) |
| Switching capacity (auxiliary contacts, general use) | 10 A, 600 V AC, (UL/CSA) 1 A, 250 V DC, (UL/CSA) |
| Switching capacity (auxiliary contacts, pilot duty) | P300, DC operated (UL/CSA) A600, AC operated (UL/CSA) |
Magnet system
| Arcing time | 10 ms |
| Drop-out voltage | AC operated: 0.6 - 0.3 x UC, AC operated |
| Duty factor | 100 % |
| Pick-up voltage | 0.8 - 1.1 V AC x Uc |
| Power consumption, pick-up, 50 Hz | 24 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz |
| Power consumption, pick-up, 60 Hz | 30 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz |
| Power consumption, sealing, 50 Hz | 1.4 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz 3.4 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz |
| Power consumption, sealing, 60 Hz | 4.4 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz 1.4 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz |
| Rated control supply voltage (Us) at AC, 50 Hz - min | 110 V |
| Rated control supply voltage (Us) at AC, 50 Hz - max | 110 V |
| Rated control supply voltage (Us) at AC, 60 Hz - min | 120 V |
| Rated control supply voltage (Us) at AC, 60 Hz - max | 120 V |
| Switching time (AC operated, make contacts, closing delay) - min | 15 ms |
| Switching time (AC operated, make contacts, closing delay) - max | 21 ms |
| Switching time (AC operated, make contacts, opening delay) - min | 9 ms |
| Switching time (AC operated, make contacts, opening delay) - max | 18 ms |
Motor rating
| Assigned motor power at 115/120 V, 60 Hz, 1-phase | 1 HP |
| Assigned motor power at 200/208 V, 60 Hz, 3-phase | 3 HP |
| Assigned motor power at 230/240 V, 60 Hz, 1-phase | 2 HP |
| Assigned motor power at 230/240 V, 60 Hz, 3-phase | 3 HP |
| Assigned motor power at 460/480 V, 60 Hz, 3-phase | 10 HP |
| Assigned motor power at 575/600 V, 60 Hz, 3-phase | 10 HP |
Contacts
| Number of auxiliary contacts (normally closed contacts) | 3 |
| Number of auxiliary contacts (normally open contacts) | 2 |
| Number of contacts (normally closed contacts) | 3 |
| Number of contacts (normally open contacts) | 2 |
Special purpose ratings
| Special purpose rating of ballast electrical discharge lamps | 20 A (600V 60Hz 3phase, 347V 60Hz 1phase) 20 A (480V 60Hz 3phase, 277V 60Hz 1phase) |
| Special purpose rating of definite purpose rating | 72 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA) 12 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA) |
| Special purpose rating of elevator control | 2 HP, 200 V 60 Hz 3-ph, (UL/CSA) 2 HP, 240 V 60 Hz 3-ph, (UL/CSA) 9 A, 600 V 60 Hz 3-ph, (UL/CSA) 7.5 HP, 600 V 60 Hz 3-ph, (UL/CSA) 7.5 HP, 480 V 60 Hz 3-ph, (UL/CSA) 11 A, 480 V 60 Hz 3-ph, (UL/CSA) 6.8 A, 240 V 60 Hz 3-ph, (UL/CSA) 7.8 A, 200 V 60 Hz 3-ph, (UL/CSA) |
| Special purpose rating of refrigeration control (CSA only) | 60 A, LRA 480 V 60 Hz 3phase; (CSA) 10 A, FLA 600 V 60 Hz 3phase; (CSA) 60 A, LRA 600 V 60 Hz 3phase; (CSA) 10 A, FLA 480 V 60 Hz 3phase; (CSA) |
| Special purpose rating of resistance air heating | 20 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA) 20 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA) |
| Special purpose rating of tungsten incandescent lamps | 14 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA) 14 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA) |
Design verification
| Equipment heat dissipation, current-dependent Pvid | 0 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 0.3 W |
| Rated operational current for specified heat dissipation (In) | 12 A |
| Static heat dissipation, non-current-dependent Pvs | 1.4 W |
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |