View larger
DILMP45-11(220V50/60HZ)-PI 199677 EATON ELECTRIC 4-pole contactor,45A/AC-1,action. AC. Push-in
DILMP45-11(220V50/60HZ)-PI
199677
Y7-199677
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Featuring push-in terminal connections for rapid installation, the Eaton Moeller DILMP45-11(220V50/60HZ)-PI four-pole contactor is built for switching AC-1 resistive and non-inductive loads. Such contactors are frequently utilized in power distribution networks, lighting systems, and heating applications where secure connections and reliable switching are paramount.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 220 V
- Rated control supply voltage AC 60 Hz (EF003979): 220 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 4
- Type of electrical connection of main circuit (EF006819): Spring clamp connection
- Operating voltage AC 50 Hz (EF008206): 24 V
- Operating voltage AC 60 Hz (EF008207): 24 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 45 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 25 A
- Rated operation power at AC-3, 400 V (EF001364): 11 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 15 A
- Rated operation power at AC-4, 400 V (EF008496): 7 kW
- Rated operation power NEMA (EF011960): 0 kW
- Modular version (EF001126): No
- Width (EF000008): 61 mm
More info
▲General specifications
VDE 0660
Features & Functions
General
AC-3: Normal AC induction motors: starting, switch off during running
Ambient conditions, mechanical
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
2 x (1 - 4) mm², Main cables
2 x (0.5 - 1.5) mm², Control circuit cables
1 x (0.5 - 2.5) mm², Control circuit cables
1 x (0.5 - 2.5) mm², Control circuit cables
2 x (0.5 - 2.5) mm², Control circuit cables
1 x (1 - 10) mm², Main cables
1 x (1 - 6) mm², Main cables
2 x (1 - 6) mm², Main cables
1 x (0.5 - 2.5) mm², Control circuit cables
20 - 14, Control circuit cables
Electrical Rating
Short-circuit rating
125 A, max. Fuse, SCCR (UL/CSA)
5 kA, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
32 A, max. CB, SCCR (UL/CSA)
70 A, Class J, max. Fuse, SCCR (UL/CSA)
100 A, Class J, max. Fuse, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
10 A, 600 V AC, (UL/CSA)
Switching time
Magnet system
AC operated: 0.6 - 0.4 x UC, AC operated
0.8 - 1.1 V AC x Uc
50 VA, Dual-frequency coil in a cold state and 1.0 x Us
8 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Motor Rating
Communication
Contacts
Safety
400 V AC, Between the contacts, According to EN 61140