View larger
DILMP20(48VDC) 276986 Y7-276986 EATON ELECTRIC Industrial Automation Bussines and Industrial Control Devices..
DILMP20(48VDC)
276986
Y7-276986
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller DILMP20(48VDC) is an industrial contactor designed to handle resistive and inductive loads safely within automated control systems and motor starter assemblies. These devices are foundational elements in manufacturing plants for opening and closing electrical power circuits reliably.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 0 V
- Rated control supply voltage DC (EF003980): 48 V
- Voltage type for actuating (EF008242): DC
- Number of normally open contacts as main contact (EF001374): 4
- Type of electrical connection of main circuit (EF006819): Screw connection
- Operating voltage AC 50 Hz (EF008206): 24 V
- Operating voltage AC 60 Hz (EF008207): 24 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 22 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 12 A
- Rated operation power at AC-3, 400 V (EF001364): 5.5 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 10 A
- Rated operation power at AC-4, 400 V (EF008496): 4.5 kW
- Rated operation power NEMA (EF011960): 0 kW
- Modular version (EF001126): No
- Width (EF000008): 45 mm
More info
▲General specifications
IEC/EN 60947-4-1
CSA-C22.2 No. 60947-4-1-14
CSA File No.: 012528
UL 60947-4-1
CE
UL File No.: E29096
UL
IEC/EN 60947
VDE 0660
CSA
CSA Class No.: 2411-03, 3211-04
Features & Functions
General
10,000,000 Operations (DC operated)
5000 mechanical Operations/h (AC operated)
AC-3: Normal AC induction motors: starting, switch off during running
Ambient conditions, mechanical
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
2 x (0.75 - 2.5) mm²
1 x (0.75 - 4) mm²
2, Terminal screw, Pozidriv screwdriver
Electrical Rating
Short-circuit rating
60 A, max. CB, SCCR (UL/CSA)
45 A, max. Fuse, SCCR (UL/CSA)
30 kA, Fuse, SCCR (UL/CSA)
25 A, Class RK5, max. Fuse, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
Switching time
Magnet system
0.8 - 1.1 V AC/DC x Us
Communication
Contacts
Safety
400 V AC, Between the contacts, According to EN 61140
Special purpose ratings
20 A (480V 60Hz 3phase, 277V 60Hz 1phase)
6.1 A, 600 V 60 Hz 3-ph, (UL/CSA)
60 A, LRA 480 V 60 Hz 3phase; (CSA)
60 A, LRA 600 V 60 Hz 3phase; (CSA)
10 A, FLA 600 V 60 Hz 3phase; (CSA)
20 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
14 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)