View larger
DILMF17-01(RAC48) 104439 Y7-104439 EATON ELECTRIC Contactor, 3p+1N/O, 5HP/600VAC, SEMI F47
DILMF17-01(RAC48)
104439
Y7-104439
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The DILMF17-01(RAC48) 104439 Y7-104439 EATON ELECTRIC Contactor is a specialized switching device engineered for controlling electrical motors and industrial distribution circuits with high reliability. Contactors of this class provide automated remote management of power supplies in machinery and HVAC systems.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 42 V
- Rated control supply voltage AC 60 Hz (EF003979): 42 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Screw connection
- Operating voltage AC 50 Hz (EF008206): 230 V
- Operating voltage AC 60 Hz (EF008207): 230 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 35 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 18 A
- Rated operation power at AC-3, 400 V (EF001364): 7.5 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 10 A
- Rated operation power at AC-4, 400 V (EF008496): 4.5 kW
- Rated operation power NEMA (EF011960): 7.4 kW
- Modular version (EF001126): No
- Width (EF000008): 45 mm
More info
▲General specifications
IEC/EN 60947-4-1
CSA-C22.2 No. 60947-4-1-14
CE
UL 60947-4-1
UL File No.: E29096
UL
CSA
CSA File No.: 012528
CSA Class No.: 2411-03, 3211-04
Features & Functions
Built-in suppressor circuit
General
Also motors with efficiency class IE3
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-3: Normal AC induction motors: starting, switch off during running
Climatic environmental conditions
Electro Magnetic Compatibility
Electrical Rating
Short-circuit rating
125 A, max. CB, SCCR (UL/CSA)
125 A, max. Fuse, SCCR (UL/CSA)
10/100 kA, Fuse, SCCR (UL/CSA)
125/70 A, Class J, max. Fuse, SCCR (UL/CSA)
50/32 A, max. CB, SCCR (UL/CSA)
10/22 kA, CB, SCCR (UL/CSA)
50/32 A, max. CB, SCCR (UL/CSA)
10/100 kA, Fuse, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
1 A, 250 V DC, (UL/CSA)
A600, AC operated (UL/CSA)
Switching time
Magnet system
0.7 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
Motor Rating
Communication
Contacts
Special purpose ratings
40 A (600V 60Hz 3phase, 347V 60Hz 1phase)
18 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
10 HP, 600 V 60 Hz 3-ph, (UL/CSA)
3 HP, 240 V 60 Hz 3-ph, (UL/CSA)
11 A, 200 V 60 Hz 3-ph, (UL/CSA)
7.5 HP, 480 V 60 Hz 3-ph, (UL/CSA)
11 A, 480 V 60 Hz 3-ph, (UL/CSA)
3 HP, 200 V 60 Hz 3-ph, (UL/CSA)
11 A, 600 V 60 Hz 3-ph, (UL/CSA)
240 A, LRA 480 V 60 Hz 3phase; (CSA)
180 A, LRA 600 V 60 Hz 3phase; (CSA)
30 A, FLA 600 V 60 Hz 3phase; (CSA)
40 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
40 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)