10.10 Temperature Rise
The panel builder is responsible for calculating the temperature increase. Eaton will provide temperature dissipation data for the devices.
10.11 Short Circuit Resistance
It is the responsibility of the panel builder. The specifications of the switchgear must be taken into account.
10.12 Electromagnetic Compatibility
It is the responsibility of the panel builder. The specifications of the switchgear must be taken into account.
10.13 Mechanical function
The device complies with the requirements, as long as the information in the instruction leaflet (IL) is respected.
10.2.2 Corrosion Resistance
Meets the requirements of the product standard.
10.2.3.1 Verification of the thermal stability of cabinets
Meets the requirements of the product standard.
10.2.3.2 Verification. Resistance of insulating materials in condic. Normal Heat
Meets the requirements of the product standard.
10.2.3.3. Res. mat. aisl. to excessive heat/fire by the effect of. internal
Meets the requirements of the product standard.
10.2.4 Resistance to ultraviolet (UV) radiation
Meets the requirements of the product standard.
10.2.5 Elevation
It does not apply, since it is necessary to evaluate the entire apparatus.
10.2.6 Mechanical impact
It does not apply, since it is necessary to evaluate the entire apparatus.
10.2.7 Registrations
Meets the requirements of the product standard.
10.3 Degree of protection of mounts
It does not apply, since it is necessary to evaluate the entire apparatus.
10.4 Effluvium distances and clearances
Meets the requirements of the product standard.
10.5 Protection against electric shock
It does not apply, since it is necessary to evaluate the entire apparatus.
10.6 Incorporation of Switching Devices and Components
It does not apply, since it is necessary to evaluate the entire apparatus.
10.7 Internal Electrical Connections and Circuits
It is the responsibility of the panel builder.
10.8 External Conductor Connections
It is the responsibility of the panel builder.
10.9.2 Power Frequency Electrical Resistance
It is the responsibility of the panel builder.
10.9.3 Impulse Voltage Supported
It is the responsibility of the panel builder.
10.9.4 Testing of Cabinets Made of Insulating Material
It is the responsibility of the panel builder.
Manoeuvring frequency
9,000 mechanical operations/h (AC drive)
Climatic Resistance
Moist, cyclic heat according to IEC 60068-2-30
Moist heat, constant, according to IEC 60068-2-78
Connecting to SmartWire-DT
Assigned Voltage Supported to Impulse (Uimp)
Category of use
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-3: AC Induction Motors: Start, Off During Operation
AC-4: AC Induction Motors: Start, Connection, Reverse, Idle
Ambient Operating Temperature - Max.
Ambient Operating Temperature - Min.
Ambient Operating Temperature (Closed) - Max.
Ambient Operating Temperature (Closed) - Min.
Ambient storage temperature - max.
Ambient storage temperature - min.
Motor power rated at 115/120 V, 60 Hz, single-phase
Motor power rated at 200/208 V, 60 Hz, three-phase
Motor power rated at 230/240 V, 60 Hz, single-phase
Motor power rated at 230/240 V, 60 Hz, three-phase
Motor power rated at 460/480 V, 60 Hz, three-phase
Motor power rated at 575/600 V, 60 Hz, three-phase
Conventional thermal current Ith (1 pole, in housing)
Conventional thermal current Ith (3 poles, in housing)
Conventional thermal current Ith at 55 °C (3 poles, open)
Conventional Thermal Current Ith of Main Contacts (1 Pole, Open)
Thermal Dissipation Capacity Pdiss
Protection
Finger and back of hand proof, Protection against direct contact when operated from the front (EN 50274)
Main Circuit Electrical Connection Type
Screwdriver Size
3.0 x 0.5 mm, screw terminal
3 x 0.5 mm, screw terminal
Number of auxiliary contacts (opening contacts)
Number of auxiliary contacts (normally open contacts)
Number of contacts (opening contacts) as the primary contact
Number of contacts (normally open contacts)
Number of primary contacts (normally open contacts)
Rated interrupting capacity at 220/230 V
Interrupting rating at 380/400 V
Rated interrupting capacity at 500 V
Rated interrupting capability at 660/690 V
Nominal control supply voltage (Us) in AC, 50 Hz - max.
Nominal control supply voltage (Us) in AC, 50 Hz - min.
Nominal control supply voltage (Us) in AC, 60 Hz - max.
Nominal control supply voltage (Us) in AC, 60 Hz - min.
Service life, mechanical
10,000,000 Operations (AC Drive)
Power Absorbed, Call, 50 Hz
27 VA, bi-frequency coil in cold state and 1.0 x Us
Safe sectioning
400 V AC, Between coil and contacts, According to EN 61140
400 V AC, Between contacts, according to EN 61140
Power Absorbed, Call, 60 Hz
25 VA, bi-frequency coil in cold state and 1.0 x Us
Power Absorbed, Retention, 50 Hz
1.2 W, bi-frequency coil in cold state and 1.0 x Us
1.4 W, bi-frequency coil in cold state and 1.0 x Us
Power Absorbed, Retention, 60 Hz
4.2 VA, bi-frequency coil in cold state and 1.0 x Us, at 60 Hz
3.3 VA, bi-frequency coil in cold state and 1.0 x Us, at 60 Hz
1.2 W, bi-frequency coil in cold state and 1.0 x Us
1.4 W, bi-frequency coil in cold state and 1.0 x Us
Cutting Power (Auxiliary Contacts, General Purpose)
1 A, 250 V DC, (UL/CSA)
10 A, 600 VAC, (UL/CSA)
Cutting power (auxiliary contacts, pilot function)
A600, AC Drive (UL/CSA)
P300, DC Drive (UL/CSA)
Terminal Capacity (Flexible with Terminal)
1 x (0.75 - 2.5) mm²
2 x (0.75 - 2.5) mm²
Impact Resistance
10 g, Auxiliary contact NO, Mechanical, according to IEC/EN 60068-2-27, Semi-sinusoidal shock 10 ms
3.4 g, NC auxiliary contact, mechanical, according to IEC/EN 60068-2-27 when mounted on a table, semi-sinusoidal shock 10 ms
7 g, Auxiliary contact NO, Mechanical, according to IEC/EN 60068-2-27, Semi-sinusoidal shock 10 ms
5.7 g, main contact NO, mechanical, according to IEC/EN 60068-2-27 when mounted on a table, 10 ms semi-sinusoidal impact
5 g, NC auxiliary contact, mechanical, according to IEC/EN 60068-2-27, semi-sinusoidal shock 10 ms
3.4 g, Auxiliary contact NO, mechanical, according to IEC/EN 60068-2-27 when mounted on a table, semi-sinusoidal shock 10 ms
Terminal Capacity (Rigid)
2 x (0.5 - 2.5) mm², Manoeuvring cables
1 x (0.5 - 0.25) mm²
Terminal Capacity (Rigid/Stranded AWG)
Cutting Power (Main Contacts, General Purpose)
20 A, Maximum Rated Motor Operating Intensity (UL/CSA)
Terminal Capacity (Flexible)
2 x (0.5 - 2.5) mm²
1 x (0.5 - 2.5) mm²
Nominal Control Supply Voltage (Us) in DC - Max.
Nominal Control Supply Voltage (Us) in DC - Min.
Rated Insulation Voltage (Ui)
Assigned closing power up to 690 V (cos phi according to IEC/EN 60947)
Assigned current of use (Ie) in AC-1, 380 V, 400 V, 415 V
Assigned current (Ie) in AC-3, 220 V, 230 V, 240 V
Assigned current (Ie) in AC-3, 380 V, 400 V, 415 V
Assigned Current of Use (Ie) in AC-3, 440 V
Assigned Operating Current (Ie) in AC-3, 500 V
Assigned Current of Use (Ie) in AC-3, 660 V, 690 V
Assigned current of use (Ie) in AC-4, 220 V, 230 V, 240 V
Assigned current (Ie) in AC-4, 400 V
Assigned Current of Use (Ie) in AC-4, 440 V
Assigned current of use (Ie) in AC-4, 500 V
Assigned current of use (Ie) in AC-4, 660 V, 690 V
Assigned Current of Use (Ie) in DC-1, 110 V
Assigned Current of Use (Ie) in DC-1, 220 V
Assigned Current of Use (Ie) in DC-1, 60 V
Rated power for use in AC-3, 240 V, 50 Hz
AC-3 rated power, 380/400 V, 50 Hz
Rated power for use in AC-3, 415 V, 50 Hz
AC-4 rated power, 220/230 V, 50 Hz
Rated power for use in AC-4, 240 V, 50 Hz
Rated power for use in AC-4, 380/400 V, 50 Hz
AC-4 rated power, 415 V, 50 Hz
Rated power for use in AC-4, 440 V, 50 Hz
Power rated for use in AC-4, 500 V, 50 Hz
Rated power for use in AC-4, 660/690 V, 50 Hz
Assigned Power of Use (NEMA)
Assigned Operating Voltage (Ue) in AC - Max.
Switching time (AC acc., contact closure, closing delay) - max.
Switching Time (AC Acc., Contact Shutdown, Shutdown Delay) - min.
Switching time (AC acc., contact closing, opening delay) - max.
Switching Time (AC Acc., Contact Closure, Opening Delay) - Min.
Nominal Short-Circuit Current (Basic Rating)
45 A, Max Fuse, SCCR (UL/CSA)
5 kA, SCCR (UL/CSA)
60 A, max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 480 V)
30/100 kA, Fuse, SCCR (UL/CSA)
16 A, max. CB, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
25 A, RK5 Class/ 20 A J Class, max. Fuse, SCCR (UL/CSA)
Short-circuit current rating (high fault at 600 V)
25 A, Class RK5/ 20 A, Class J, max. Fuse, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
25 A, Class RK5/ 45 A Class J, max. Fuse, SCCR (UL/CSA)
25 A, Class RK5/60 A, Class J, max. Fuse, SCCR (UL/CSA)
Nominal short-circuit protection (type 1 coordination) at 400 V
Suitable for
Motors with efficiency class IE3 are also available
Nominal short-circuit protection (type 1 coordination) at 690 V
Nominal short-circuit protection (type 2 coordination) at 400 V
Nominal short-circuit protection (type 2 coordination) at 690 V
Special Purpose Classification of Ballast Discharge Lamps
18 A (480 V 60 Hz three-phase, 277 V 60 Hz single-phase)
18 A (600 V 60 Hz three-phase, 347 V 60 Hz single-phase)
Special Application Classification of Defined Application Classification
54 A, LRA 480 V 60 Hz three-phase, 100,000 cycles per UL 1995, (UL/CSA)
9 A, FLA 480 V 60 Hz three-phase, 100,000 cycles according to UL 1995, (UL/CSA)
Special Purpose Classification of Elevator Control
2 HP, 200 V 60 Hz Three Phase, (UL/CSA)
2 HP, 240 V 60 Hz Three Phase, (UL/CSA)
4.8 A, 480 V 60 Hz Three-Phase, (UL/CSA)
7.8 A, 200 V 60 Hz Three-Phase, (UL/CSA)
6.8 A, 240 V 60 Hz Three-Phase, (UL/CSA)
3 HP, 480 V 60 Hz Three Phase, (UL/CSA)
5 HP, 600 V 60 Hz Three Phase, (UL/CSA)
6.1 A, 600 V 60 Hz Three Phase, (UL/CSA)
Refrigeration Control Special Purpose Rating (CSA only)
10 A, FLA 480 V 60 Hz three-phase; (CSA)
10 A, FLA 600 V 60 Hz three-phase; (CSA)
60 A, LRA 480 V 60 Hz three-phase; (CSA)
60 A, LRA 600 V 60 Hz three-phase; (CSA)
Special Purpose Classification of Heating Element
18 A, 480 V 60 Hz Three Phase, 277 V 60 Hz Single Phase, (UL / CSA)
18 A, 600 V 60 Hz Three Phase, 347 V 60 Hz Single Phase, (UL/CSA)
Special Purpose Classification of Tungsten Incandescent Lamps
14 A, 480 V 60 Hz Three Phase, 277 V 60 Hz Single Phase, (UL/CSA)
14 A, 600 V 60 Hz Three Phase, 347 V 60 Hz Single Phase, (UL/CSA)
AC service voltage at 50 Hz - Min.
AC operating voltage at 50 Hz - Max.
AC service voltage at 60 Hz - Min.
AC operating voltage at 60 Hz - Max.