View larger
DILM9-10(110V50HZ,120V60HZ)-PI 199230 Y7-199230 EATON ELECTRIC DILM9-10(110V50HZ,120V60HZ)-PI
DILM9-10(110V50HZ,120V60HZ)-PI
199230
Y7-199230
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller DILM9-10(110V50HZ,120V60HZ)-PI contactor serves as a foundational component for starting motors and switching auxiliary loads in automated manufacturing environments. Industrial setups rely on these devices to manage repetitive high-current switching tasks safely via low-power command signals.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 110 V
- Rated control supply voltage AC 60 Hz (EF003979): 120 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Spring clamp connection
- Operating voltage AC 50 Hz (EF008206): 24 V
- Operating voltage AC 60 Hz (EF008207): 24 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 22 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 9 A
- Rated operation power at AC-3, 400 V (EF001364): 4 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 6 A
- Rated operation power at AC-4, 400 V (EF008496): 2.5 kW
- Rated operation power NEMA (EF011960): 0 kW
- Modular version (EF001126): No
- Width (EF000008): 45 mm
More info
▲General specifications
VDE 0660
UL Listed
CSA certified
UL Category Control No.: NLDX
CE marking
UL File No.: E29096
CSA Class No.: 2411-03, 3211-04
CSA File No.: 012528
Features & Functions
General
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Ambient conditions, mechanical
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
5.7 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
3.4 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Electro Magnetic Compatibility
Terminal capacities
2 x (0.75 - 2.5) mm²
2 x (0.5 - 2.5) mm²
2 x (0.5 - 2.5) mm², Control circuit cables
3.0 x 0.5 mm, Terminal screw
Electrical Rating
Short-circuit rating
5 kA, SCCR (UL/CSA)
60 A, max. CB, SCCR (UL/CSA)
16 A, max. CB, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
25 A, Class RK5/ 20 A Class J, max. Fuse, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
25 A, Class RK5/45 A, Class J, max. Fuse, SCCR (UL/CSA)
25 A, Class RK5/60 A, Class J, max. Fuse, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
10 A, 600 V AC, (UL/CSA)
P300, DC operated (UL/CSA)
Switching time
Magnet system
1.4 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
1.4 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Motor Rating
Communication
Contacts
Safety
400 V AC, Between coil and contacts, According to EN 61140
Special purpose ratings
18 A (600V 60Hz 3phase, 347V 60Hz 1phase)
9 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
2 HP, 240 V 60 Hz 3-ph, (UL/CSA)
4.8 A, 480 V 60 Hz 3-ph, (UL/CSA)
7.8 A, 200 V 60 Hz 3-ph, (UL/CSA)
6.8 A, 240 V 60 Hz 3-ph, (UL/CSA)
3 HP, 480 V 60 Hz 3-ph, (UL/CSA)
5 HP, 600 V 60 Hz 3-ph, (UL/CSA)
6.1 A, 600 V 60 Hz 3-ph, (UL/CSA)
10 A, FLA 600 V 60 Hz 3phase; (CSA)
60 A, LRA 480 V 60 Hz 3phase; (CSA)
60 A, LRA 600 V 60 Hz 3phase; (CSA)
18 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
14 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)