DILM820/22(RA110) 208224 Y7-208224 EATON ELECTRIC Contactor, 3p+2N/O+2N/C, 450kW/400V/AC3
DILM820/22(RA110)
208224
Y7-208224
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors more than 170 A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller part number DILM820/22(RA110) (Y7-208224) is an ultra-heavy-duty industrial contactor built to control massive electrical loads and large-scale industrial motors. Such massive switching devices form the backbone of high-power distribution systems, heavy manufacturing lines, and major infrastructure projects. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 48 V
- Rated control supply voltage AC 60 Hz (EF003979): 48 V
- Rated control supply voltage DC (EF003980): 48 V
- Voltage type for actuating (EF008242): AC/DC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Rail connection
- Operating voltage AC 50 Hz (EF008206): 48 V
- Operating voltage AC 60 Hz (EF008207): 48 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 1225 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 820 A
- Rated operation power at AC-3, 400 V (EF001364): 450 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 656 A
- Rated operation power at AC-4, 400 V (EF008496): 355 kW
- Rated operation power NEMA (EF011960): 522 kW
- Modular version (EF001126): No
- Width (EF000008): 250 mm
More info
▲General specifications
UL
IEC/EN 60947-4-1
CSA Class No.: 3211-04
CSA-C22.2 No. 60947-4-1-14
CE
CSA
VDE 0660
UL 60947-4-1
UL Category Control No.: NLDX
IEC/EN 60947
UL File No.: E29096
Global
5,000,000 Operations (AC operated)
200 Operations/h
1000 mechanical Operations/h (AC operated)
8 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-3: Normal AC induction motors: starting, switch off during running
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
General
Damp heat, cyclic, to IEC 60068-2-30
5,000,000 Operations (AC operated)
200 Operations/h
1000 mechanical Operations/h (AC operated)
8 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-3: Normal AC induction motors: starting, switch off during running
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Climatic environmental conditions
1 x (0.75 - 2.5) mm², Control circuit cables
1 x (0.75 - 2.5) mm², Control circuit cables
2/0 - 500 MCM, Main cables
M3.5, Terminal screw, Control circuit cables
1.2 Nm, Screw terminals, Control circuit cables
Terminal capacities
265 A at 690 V (Individual compensation, three-phase capacitors, open)
900 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
5400 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
5400 A, LRA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Electrical rating
2000 A, max. Fuse, SCCR (UL/CSA)
1200 A, max. CB, SCCR (UL/CSA)
85 kA, Fuse, SCCR (UL/CSA)
2000 A, max. Fuse, SCCR (UL/CSA)
1200 A, max. CB, SCCR (UL/CSA)
85 kA, Fuse, SCCR (UL/CSA)
85 kA, CB, SCCR (UL/CSA)
1200 A, max. CB, SCCR (UL/CSA)
265 A at 690 V (Individual compensation, three-phase capacitors, open)
900 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
5400 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
5400 A, LRA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Short-circuit rating
Conventional thermal current Ith
1 A, 250 V DC, (UL/CSA)
A600, AC operated (UL/CSA)
Switching capacity
Sealing - Pick-up phase (0 - 0.7 x Uc min: Contactor does not switch on
Sealing - Voltage interruptions (0 - 0.2 x Uc min ≤ 10 ms: Time is bridged successfully
Sealing - Voltage drops (0.2 - 0.6 x Uc min ≤12 ms: Time is bridged successfully
Sealing - Pick-up phase (0.7 x Uc min - 1.15 x Uc max): Contactor switches on with certainty
Sealing - Voltage drops (0.2 - 0.6 x Uc min) > 12 ms: Drop-out of the contactor
Sealing - Voltage drops (0.6 - 0.7 x Uc min: Contactor remains switched on
Sealing - Excess voltage (1.15 - 1.3 x Uc max): Contactor remains switched on
AC operated: 0.2 x US max - 0.6 x US min, AC operated
0.7 - 1.15 V AC x Us
700 W, Pull-in power, Coil in a cold state and 1.0 x Us
700 W, Pull-in power, Coil in a cold state and 1.0 x Us
26.4 VA, Coil in a cold state and 1.0 x Us
10.3 W, Coil in a cold state and 1.0 x Us
Magnet system
700 W, Pull-in power, Coil in a cold state and 1.0 x Us
700 W, Pull-in power, Coil in a cold state and 1.0 x Us
26.4 VA, Coil in a cold state and 1.0 x Us
10.3 W, Coil in a cold state and 1.0 x Us