View larger
DILM7-10(220V50HZ,240V60HZ) 276549 Y7-276549 EATON ELECTRIC Power Contactor 3-pole + 1 NO 3 kW / 400 V / AC3..
DILM7-10(220V50HZ,240V60HZ)
276549
Y7-276549
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller DILM7-10(220V50HZ,240V60HZ) power contactor acts as a critical switching interface in motor control panels, safely managing power delivery to machinery based on incoming command triggers. Technicians install these units to automate motor operations in manufacturing lines, pump systems, and conveyor applications.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Manufacturer: Eaton Moeller
- Model Code: DILM7-10(220V50HZ,240V60HZ)
- Catalogue Code: 276549
- Pole Configuration: 3-pole with 1 NO contact
- Load Capacity: 3 kW / 400 V / AC3
- Coil Spec: 220 V 50 Hz, 240 V 60 Hz AC operation
- Termination: Screw terminals
More info
▲General specifications
IEC/EN 60947
UL 60947-4-1
CSA File No.: 012528
IEC/EN 60947-4-1
VDE 0660
CSA-C22.2 No. 60947-4-1-14
CSA Class No.: 2411-03, 3211-04
CE
CSA
UL Category Control No.: NLDX
UL
Features & Functions
General
AC-3: Normal AC induction motors: starting, switch off during running
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Ambient conditions, mechanical
3.4 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
3.4 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
5.7 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Electro Magnetic Compatibility
Terminal capacities
2 x (0.75 - 2,5) mm²
2 x (0.75 - 2.5) mm²
2 x (0.75 - 2.5) mm²
2, Terminal screw, Pozidriv screwdriver
Electrical Rating
Short-circuit rating
45 A, max. Fuse, SCCR (UL/CSA)
60 A, max. CB, SCCR (UL/CSA)
25 A, Class RK5/ 20 A Class J, max. Fuse, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
16 A, max. CB, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
1 A, 250 V DC, (UL/CSA)
P300, DC operated (UL/CSA)
Switching time
Magnet system
3.4 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
4.4 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Motor Rating
Communication
Contacts
Safety
400 V AC, Between the contacts, According to EN 61140
Special purpose ratings
12 A (600V 60Hz 3phase, 347V 60Hz 1phase)
7 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
3.9 A, 600 V 60 Hz 3-ph, (UL/CSA)
3.7 A, 200 V 60 Hz 3-ph, (UL/CSA)
3.4 A, 480 V 60 Hz 3-ph, (UL/CSA)
2 HP, 480 V 60 Hz 3-ph, (UL/CSA)
6 A, 240 V 60 Hz 3-ph, (UL/CSA)
0.75 HP, 200 V 60 Hz 3-ph, (UL/CSA)
1.5 HP, 240 V 60 Hz 3-ph, (UL/CSA)
60 A, LRA 480 V 60 Hz 3phase; (CSA)
10 A, FLA 480 V 60 Hz 3phase; (CSA)
10 A, FLA 600 V 60 Hz 3phase; (CSA)
12 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
14 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)