View larger
DILM650/22(RAC500) 208220 Y7-208220 EATON ELECTRIC Contactor, 3p+2N/O+2N/C, 355kW/400V/AC3
DILM650/22(RAC500)
208220
Y7-208220
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors more than 170 A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller high-capacity contactor is built for controlling massive electrical loads and large industrial motors within heavy manufacturing plants. These robust switching devices provide the durability required for continuous, high-current power distribution.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 480 V
- Rated control supply voltage AC 60 Hz (EF003979): 480 V
- Rated control supply voltage DC (EF003980): 250 V
- Voltage type for actuating (EF008242): AC/DC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Rail connection
- Operating voltage AC 50 Hz (EF008206): 250 V
- Operating voltage AC 60 Hz (EF008207): 250 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 1041 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 650 A
- Rated operation power at AC-3, 400 V (EF001364): 355 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 512 A
- Rated operation power at AC-4, 400 V (EF008496): 280 kW
- Rated operation power NEMA (EF011960): 373 kW
- Modular version (EF001126): No
- Width (EF000008): 250 mm
More info
▲General specifications
CSA-C22.2 No. 60947-4-1-14
UL
UL File No.: E29096
IEC/EN 60947-4-1
CSA
CE
IEC/EN 60947
UL Category Control No.: NLDX
UL 60947-4-1
CSA File No.: 012528
VDE 0660
Global
5,000,000 Operations (AC operated)
200 Operations/h
1000 mechanical Operations/h (DC operated)
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
AC-3: Normal AC induction motors: starting, switch off during running
General
Damp heat, constant, to IEC 60068-2-78
5,000,000 Operations (AC operated)
200 Operations/h
1000 mechanical Operations/h (DC operated)
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
AC-3: Normal AC induction motors: starting, switch off during running
Climatic environmental conditions
2 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Control circuit cables
18 - 14, Control circuit cables
M10, Terminal screw, Main connections
1.2 Nm, Screw terminals, Control circuit cables
Terminal capacities
265 A at 690 V (Individual compensation, three-phase capacitors, open)
725 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
4350 A, LRA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
725 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Electrical rating
30 kA, SCCR (UL/CSA)
2000 A, max. Fuse, SCCR (UL/CSA)
85 kA, CB, SCCR (UL/CSA)
1200 A, max. CB, SCCR (UL/CSA)
85 kA, Fuse, SCCR (UL/CSA)
2000 A, max. Fuse, SCCR (UL/CSA)
85 kA, CB, SCCR (UL/CSA)
85 kA, Fuse, SCCR (UL/CSA)
265 A at 690 V (Individual compensation, three-phase capacitors, open)
725 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
4350 A, LRA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
725 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Short-circuit rating
Conventional thermal current Ith
15 A, 600 V AC, (UL/CSA)
A600, AC operated (UL/CSA)
Switching capacity
Sealing - Pick-up phase (0 - 0.7 x Uc min: Contactor does not switch on
Sealing - Voltage interruptions (0 - 0.2 x Uc min ≤ 10 ms: Time is bridged successfully
Sealing - Voltage drops (0.2 - 0.6 x Uc min) > 12 ms: Drop-out of the contactor
Sealing - Voltage drops (0.2 - 0.6 x Uc min ≤12 ms: Time is bridged successfully
Sealing - Pick-up phase (0.7 x Uc min - 1.15 x Uc max): Contactor switches on with certainty
Sealing - Voltage interruptions 0 - 0.2 x Uc min) > 10 ms: Drop-out of the contactor
Sealing - Excess voltage (1.15 - 1.3 x Uc max): Contactor remains switched on
AC operated: 0.2 x US max - 0.6 x US min, AC operated
0.7 - 1.15 V DC x Us
800 VA, Pull-in power, Coil in a cold state and 1.0 x Us
800 VA, Pull-in power, Coil in a cold state and 1.0 x Us
12.4 W, Coil in a cold state and 1.0 x Us
28.8 VA, Coil in a cold state and 1.0 x Us
Magnet system
800 VA, Pull-in power, Coil in a cold state and 1.0 x Us
800 VA, Pull-in power, Coil in a cold state and 1.0 x Us
12.4 W, Coil in a cold state and 1.0 x Us
28.8 VA, Coil in a cold state and 1.0 x Us