View larger
DILM38-10(415V50HZ,480V60HZ) 112431 Y7-112431 EATON ELECTRIC Power Contactor 3-pole + 1 NO 18.5 kW / 400 V /..
DILM38-10(415V50HZ,480V60HZ)
112431
Y7-112431
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Power Contactor 3-pole + 1 NO 18.5 kW / 400 V /.. manufactured by Eaton Moeller under part number DILM38-10(415V50HZ,480V60HZ) is an electromechanical switching unit designed to regulate power delivery to industrial motors and heavy electrical loads. These components are frequently deployed in automated assembly lines and HVAC systems.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 415 V
- Rated control supply voltage AC 60 Hz (EF003979): 480 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Screw connection
- Operating voltage AC 50 Hz (EF008206): 24 V
- Operating voltage AC 60 Hz (EF008207): 24 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 45 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 38 A
- Rated operation power at AC-3, 400 V (EF001364): 18.5 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 15 A
- Rated operation power at AC-4, 400 V (EF008496): 7 kW
- Rated operation power NEMA (EF011960): 14.9 kW
- Modular version (EF001126): No
- Width (EF000008): 45 mm
More info
▲General specifications
EN 60947-4-1
IEC 60947-4-1
CSA Std. C22.2 No. 14-05
VDE
VDE 0660
CSA
IEC/EN 60947
UL
Features & Functions
General
AC-3: Normal AC induction motors: starting, switch off during running
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Ambient conditions, mechanical
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
6.9 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
5.3 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Electro Magnetic Compatibility
Terminal capacities
2 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 10) mm², Main cables
1 x (0.75 - 16) mm², Main cables
2 x (0.75 - 2.5) mm², Control circuit cables
1 x (0.75 - 16) mm², Main cables
2 x (0.75 - 10) mm², Main cables
18 - 14, Control circuit cables
M3.5, Terminal screw, Control circuit cables
0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver
3.2 Nm, Screw terminals, Main cables
Electrical Rating
Short-circuit rating
Conventional thermal current
Switching time
Magnet system
7.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
8.7 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Communication
Contacts
Safety
440 V AC, Between coil and contacts, According to EN 61140