View larger
DILM32-11(24V50/60HZ)-PI 199291 Y7-199291 EATON ELECTRIC DILM32-11(24V50/60HZ)-PI
DILM32-11(24V50/60HZ)-PI
199291
Y7-199291
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Incorporating spring clamp connections for secure wiring, the Eaton Moeller DILM32-11(24V50/60HZ)-PI power contactor acts as a dependable switching device for automated motor control systems. Electrical engineers deploy such units to handle frequent switching cycles across various manufacturing machinery and power distribution applications.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 24 V
- Rated control supply voltage AC 60 Hz (EF003979): 24 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Spring clamp connection
- Operating voltage AC 50 Hz (EF008206): 24 V
- Operating voltage AC 60 Hz (EF008207): 24 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 45 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 32 A
- Rated operation power at AC-3, 400 V (EF001364): 15 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 15 A
- Rated operation power at AC-4, 400 V (EF008496): 7 kW
- Rated operation power NEMA (EF011960): 0 kW
- Modular version (EF001126): No
- Width (EF000008): 45 mm
More info
▲General specifications
VDE 0660
UL Listed
CSA certified
UL Category Control No.: NLDX
CE marking
UL File No.: E29096
CSA Class No.: 2411-03, 3211-04
CSA File No.: 012528
Features & Functions
General
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-3: Normal AC induction motors: starting, switch off during running
Ambient conditions, mechanical
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
6.5 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
8 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
2 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Electro Magnetic Compatibility
Terminal capacities
2 x (1 - 4) mm²
1 x (0.5 - 1.5) mm², Control circuit cables
1 x (1 - 6) mm²
1 x (0.5 - 2.5) mm²
1 x (1 - 10) mm²
2 x (1-6) mm²
1 x (0.5 - 0.25) mm²
1 x (1 - 6) mm²
2 x (0.5 - 2.5) mm², Control circuit cables
18 - 8, Main cables
3 x 0.5 mm, Terminal screw
Electrical Rating
Short-circuit rating
32 A, max. CB, SCCR (UL/CSA)
Conventional thermal current
Switching time
Magnet system
58 VA, Dual-frequency coil in a cold state and 1.0 x Us
58 VA, Dual-frequency coil in a cold state and 1.0 x Us
9.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
6.5 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Motor Rating
Communication
Contacts
Safety
400 V AC, Between coil and contacts, According to EN 61140