View larger
DILM25-11(24V50/60HZ)-PI 199286 Y7-199286 EATON ELECTRIC DILM25-11(24V50/60HZ)-PI
DILM25-11(24V50/60HZ)-PI
199286
Y7-199286
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Eaton Moeller DILM25-11(24V50/60HZ)-PI contactor is an essential electromechanical switching device engineered to regulate electrical power flow to motors and automated machinery. Panel builders rely on these components to safely execute start and stop commands triggered by low-voltage control logic. Please note that pricing, product availability, and shipping lead times are confirmed per enquiry through an RFQ.
- Product Name: Eaton Moeller® series DILM contactor
- Catalog Number: 199286
- Model Code: DILM25-11(24V50/60HZ)-PI
- EAN: 4015081973705
- Product Length/Depth: 115 mm
- Product Height: 85 mm
- Product Width: 45 mm
- Product Weight: 0.441 kg
- Catalog Notes: Also tested according to AC-3e.
- Fitted with:: Mirror contact
- Number of poles: Three-pole
- Application: Contactors for Motors
- Connection: Push in terminals
- Frame size: FS2
More info
▲General specifications
| Product Name | Eaton Moeller® series DILM contactor |
| Catalog Number | 199286 |
| Model Code | DILM25-11(24V50/60HZ)-PI |
| EAN | 4015081973705 |
| Product Length/Depth | 115 mm |
| Product Height | 85 mm |
| Product Width | 45 mm |
| Product Weight | 0.441 kg |
| Certifications | VDE 0660 IEC/EN 60947 UL Listed CSA certified UL Category Control No.: NLDX CE marking UL File No.: E29096 CSA Class No.: 2411-03, 3211-04 CSA File No.: 012528 |
| Catalog Notes | Also tested according to AC-3e. |
Features & Functions
| Fitted with: | Mirror contact |
| Number of poles | Three-pole |
| Number of poles | Three-pole |
| Number of poles | Three-pole |
General information
| Application | Contactors for Motors |
| Connection | Push in terminals |
| Frame size | FS2 |
| Lifespan, mechanical | 10,000,000 Operations (AC operated) |
| Operating frequency | 5000 mechanical Operations/h (AC operated) |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product category | Contactors |
| Protection | Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274) |
| Rated impulse withstand voltage (Uimp) | 8000 V AC |
| Suitable for | Also motors with efficiency class IE3 |
| Utilization category | AC-4: Normal AC induction motors: starting, plugging, reversing, inching AC-1: Non-inductive or slightly inductive loads, resistance furnaces AC-3: Normal AC induction motors: starting, switch off during running |
| Voltage type | AC |
Ambient conditions, mechanical
| Shock resistance | 5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 6.5 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 8 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 2 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms |
Climatic environmental conditions
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature - max | 60 °C |
| Ambient operating temperature (enclosed) - min | -25 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
| Ambient storage temperature - min | -40 °C |
| Ambient storage temperature - max | 80 °C |
| Climatic proofing | Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
Electro magnetic compatibility
| Emitted interference | According to EN 60947-1 |
| Interference immunity | According to EN 60947-1 |
Terminal capacities
| Terminal capacity (flexible) | 2 x (0.5 - 2.5) mm² 1 x (1 - 10) mm² 2 x (1-6) mm² 1 x (0.5 - 2.5) mm² |
| Terminal capacity (flexible with ferrule) | 1 x (0.5 - 1.5) mm², Control circuit cables 2 x (1 - 4) mm² 1 x (1 - 6) mm² 2 x (0.5 - 1.5) mm², Main cables |
| Terminal capacity (flexible with unisolated ferrule) | 1 x (0.75 - 2.5) mm², Main cables 2 x (0.75 - 2.5) mm², Main cables 1 x (0.75 - 2.5) mm², Control circuit cables 2 x (0.75 - 2.5) mm², Control circuit cables 1 x (0.5 - 2.5) mm², Control circuit cables 2 x (0.5 - 2.5) mm², Control circuit cables 1 x (1 - 6) mm², Main cables 2 x (1 - 6) mm², Main cables |
| Terminal capacity (flexible with ultrasonic welded cable end) | 1 x (0.75 - 2.5) mm², Main cables 2 x (0.75 - 2.5) mm², Main cables 1 x (0.75 - 2.5) mm², Control circuit cables 2 x (0.75 - 2.5) mm², Control circuit cables 1 x (0.5 - 2.5) mm², Control circuit cables 2 x (0.5 - 2.5) mm², Control circuit cables 1 x (1 - 10) mm², Main cables 2 x (1 - 6) mm², Main cables |
| Terminal capacity (solid) | 2 x (0.5 - 2.5) mm², Control circuit cables 1 x (0.5 - 0.25) mm² 1 x (1 - 6) mm² 2 x (1 - 6) mm² |
| Terminal capacity (solid/stranded AWG) | 18 - 8, Main cables 20 - 14 |
| Screwdriver size | 3 x 0.5 mm, Terminal screw 3.0 x 0.5 mm, Terminal screw |
Electrical rating
| Rated breaking capacity at 220/230 V | 250 A |
| Rated breaking capacity at 380/400 V | 250 A |
| Rated breaking capacity at 500 V | 250 A |
| Rated breaking capacity at 660/690 V | 150 A |
| Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V | 45 A |
| Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V | 25 A |
| Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V | 25 A |
| Rated operational current (Ie) at AC-3, 440 V | 25 A |
| Rated operational current (Ie) at AC-3, 500 V | 25 A |
| Rated operational current (Ie) at AC-3, 660 V, 690 V | 15 A |
| Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V | 13 A |
| Rated operational current (Ie) at AC-4, 440 V | 13 A |
| Rated operational current (Ie) at AC-4, 500 V | 13 A |
| Rated operational current (Ie) at AC-4, 660 V, 690 V | 10 A |
| Rated operational current (Ie) at DC-1, 60 V | 40 A |
| Rated operational current (Ie) at DC-1, 110 V | 40 A |
| Rated operational current (Ie) at DC-1, 220 V | 40 A |
| Rated making capacity up to 690 V (cos phi to IEC/EN 60947) | 350 A |
| Rated operational power at AC-3, 240 V, 50 Hz | 8.5 kW |
| Rated operational power at AC-3, 380/400 V, 50 Hz | 11 kW |
| Rated operational power at AC-3, 415 V, 50 Hz | 14.5 kW |
| Rated operational power at AC-4, 220/230 V, 50 Hz | 3.5 kW |
| Rated operational power at AC-4, 240 V, 50 Hz | 4 kW |
| Rated operational power at AC-4, 415 V, 50 Hz | 6.5 kW |
| Rated operational power at AC-4, 440 V, 50 Hz | 7 kW |
| Rated operational power at AC-4, 500 V, 50 Hz | 8 kW |
| Rated operational power at AC-4, 660/690 V, 50 Hz | 8.5 kW |
| Rated operational voltage (Ue) at AC - max | 690 V |
| Rated insulation voltage (Ui) | 690 V |
Short-circuit rating
| Short-circuit current rating (basic rating) | 5 kA, 125 A max. fuse CLASS RK5, SCCR (UL/CSA) 5 kA, 125 A max. CB, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 480 V) | 100 kA, 70 A CLASS J max. fuse, SCCR (UL/CSA) 30 kA, 30 A CLASS RK5, SCCR (UL/CSA) 65 kA, 32 A max. CB, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 600 V) | 100 kA, 70 A CLASS J max. fuse, SCCR (UL/CSA) 30 kA, 30 A CLASS RK5, SCCR (UL/CSA) |
| Short-circuit protection rating (type 1 coordination) at 400 V | 100 A gG/gL |
| Short-circuit protection rating (type 1 coordination) at 690 V | 50 A gG/gL |
| Short-circuit protection rating (type 2 coordination) at 400 V | 35 A gG/gL |
| Short-circuit protection rating (type 2 coordination) at 690 V | 35 A gG/gL |
Conventional thermal current Ith
| Conventional thermal current Ith (1-pole, enclosed) | 90 A |
| Conventional thermal current Ith (3-pole, enclosed) | 36 A |
| Conventional thermal current Ith at 55°C (3-pole, open) | 42 A |
| Conventional thermal current Ith of main contacts (1-pole, open) | 100 A |
Magnet system
| Arcing time | 10 ms |
| Duty factor | 100 % |
| Pick-up voltage | 0.8 - 1.1 V AC x Uc |
| Power consumption, pick-up, 50 Hz | 62 VA, Dual-frequency coil in a cold state and 1.0 x Us 58 VA, Dual-frequency coil in a cold state and 1.0 x Us |
| Power consumption, pick-up, 60 Hz | 58 VA, Dual-frequency coil in a cold state and 1.0 x Us 62 VA, Dual-frequency coil in a cold state and 1.0 x Us |
| Power consumption, sealing, 50 Hz | 2.1 W, Dual-frequency coil in a cold state and 1.0 x Us |
| Power consumption, sealing, 60 Hz | 2.1 W, Dual-frequency coil in a cold state and 1.0 x Us 9.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz 6.5 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz |
| Rated control supply voltage (Us) at AC, 50 Hz - min | 24 V |
| Rated control supply voltage (Us) at AC, 50 Hz - max | 24 V |
| Rated control supply voltage (Us) at AC, 60 Hz - min | 24 V |
| Rated control supply voltage (Us) at AC, 60 Hz - max | 24 V |
| Switching time (AC operated, make contacts, closing delay) - min | 16 ms |
| Switching time (AC operated, make contacts, closing delay) - max | 22 ms |
| Switching time (AC operated, make contacts, opening delay) - min | 8 ms |
| Switching time (AC operated, make contacts, opening delay) - max | 14 ms |
Motor rating
| Assigned motor power at 115/120 V, 60 Hz, 1-phase | 2 HP |
| Assigned motor power at 200/208 V, 60 Hz, 3-phase | 7.5 HP |
| Assigned motor power at 230/240 V, 60 Hz, 1-phase | 5 HP |
| Assigned motor power at 230/240 V, 60 Hz, 3-phase | 10 HP |
| Assigned motor power at 460/480 V, 60 Hz, 3-phase | 15 HP |
| Assigned motor power at 575/600 V, 60 Hz, 3-phase | 20 HP |
Communication
| Connection to SmartWire-DT | No |
Contacts
| Number of contacts (normally closed contacts) | 1 |
| Number of contacts (normally open contacts) | 1 |
| Number of auxiliary contacts (normally closed contacts) | 1 |
| Number of auxiliary contacts (normally open contacts) | 1 |
| Number of contacts (normally closed) as main contact | 0 |
Safety
| Safe isolation | 400 V AC, Between coil and contacts, According to EN 61140 400 V AC, Between the contacts, According to EN 61140 |
Design verification
| Heat dissipation capacity Pdiss | 0 W |
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |