View larger
DILK50-10(24V50/60HZ) 294080 Y7-294080 EATON ELECTRIC Contactor for 3ph three-phase capacitors, 50kVAR
DILK50-10(24V50/60HZ)
294080
Y7-294080
EATON - MOELLER
1 Pcs.
Automation > Capacitor contactor
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller series DILK capacity contactor, catalog number 294080, is purpose-built for controlling and switching three-phase capacitor banks in power factor correction systems. These dedicated contactors mitigate high transient peak currents during switching operations to extend equipment lifespan. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product Name: Eaton Moeller® series DILK capacity contactor
- Catalog Number: 294080
- Model Code: DILK50-10(24V50/60HZ)
- EAN: 4015082940805
- Product Length/Depth: 147 mm
- Product Height: 190 mm
- Product Width: 55 mm
- Product Weight: 1.171 kg
- Certifications: VDE 0660 IEC/EN 60947
- Fitted with:: Series resistors
- Application: Contactors for power factor correction
- Connection: Screw terminals
- Lifespan, electrical: 150,000 Operations
- Operating frequency: 120 Operations/h
- Product category: DILK Contactors for capacitors
- Voltage type: AC
More info
▲General specifications
| Product Name | Eaton Moeller® series DILK capacity contactor |
| Catalog Number | 294080 |
| Model Code | DILK50-10(24V50/60HZ) |
| EAN | 4015082940805 |
| Product Length/Depth | 147 mm |
| Product Height | 190 mm |
| Product Width | 55 mm |
| Product Weight | 1.171 kg |
| Certifications | VDE 0660 IEC/EN 60947 |
Features & Functions
| Fitted with: | Series resistors |
General information
| Application | Contactors for power factor correction |
| Connection | Screw terminals |
| Lifespan, electrical | 150,000 Operations |
| Operating frequency | 120 Operations/h |
| Product category | DILK Contactors for capacitors |
| Protection | Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274) |
| Voltage type | AC |
Climatic environmental conditions
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature - max | 60 °C |
| Ambient operating temperature (enclosed) - min | 25 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
Electro magnetic compatibility
| Emitted interference | According to EN 60947-1 |
| Interference immunity | According to EN 60947-1 |
Terminal capacities
| Terminal capacity (copper band) | 1 x (6 x 9 x 0.8) mm (Number of segments x width x thickness), Main cables |
| Terminal capacity (flexible with ferrule) | 1 x (2.5 - 35) mm², Main cables |
| Terminal capacity (solid) | 1 x (2.5 - 16) mm², Main cables |
| Terminal capacity (solid/stranded AWG) | 12 - 2, Main Cables |
| Terminal capacity (stranded) | 1 x (16 - 50) mm², Main cables |
Electrical rating
| Rated operational power at AC-6B, 220/230 V, 50 Hz | 25 kW |
| Rated operational power at AC-6B, 380/400 V, 50 Hz | 50 kW |
| Rated operational power at AC-6B, 525 V, 50 Hz | 65 kW |
| Rated operational power at AC-6B, 690 V, 50 Hz | 85 kW |
Magnet system
| Arcing time | 10 ms |
| Drop-out voltage | AC operated: 0.6 - 0.3 x UC, AC operated |
| Duty factor | 100 % |
| Pick-up voltage | 0.8 - 1.15 V AC x Uc |
| Power consumption, pick-up, 50 Hz | 45 VA, Dual-frequency coil in a cold state and 1.0 x Us |
| Power consumption, pick-up, 60 Hz | 45 VA, Dual-frequency coil in a cold state and 1.0 x Us |
| Power consumption, sealing, 50 Hz | 4.1 W, Dual-frequency coil in a cold state and 1.0 x Us |
| Power consumption, sealing, 60 Hz | 4.1 W, Dual-frequency coil in a cold state and 1.0 x Us 1.5 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz |
| Rated control supply voltage (Us) at AC, 50 Hz - min | 24 V |
| Rated control supply voltage (Us) at AC, 50 Hz - max | 24 V |
| Rated control supply voltage (Us) at AC, 60 Hz - min | 24 V |
| Rated control supply voltage (Us) at AC, 60 Hz - max | 24 V |
| Switching time (AC operated, make contacts, closing delay) - min | 50 ms |
| Switching time (AC operated, make contacts, opening delay) - min | 40 ms |
Contacts
| Making capacity without damping (I-peak value) | 180 x Ie |
| Number of auxiliary contacts (normally closed contacts) | 0 |
| Number of auxiliary contacts (normally open contacts) | 0 |
| Number of contacts (normally closed) as main contact | 0 |
Special purpose ratings
| Special purpose rating of capacitor switching | 72.1 A, 240 V 60 Hz 3phase, (UL/CSA) 30 kVar, 240 V 60 Hz 3phase, (UL/CSA) 72.1 A, 480 V 60 Hz 3phase, (UL/CSA) 72.1 A, 600 V 60 Hz 3phase, (UL/CSA) 75 kVar, 600 V 60 Hz 3phase, (UL/CSA) 60 kVar, 480 V 60 Hz 3phase, (UL/CSA) |
Design verification
| Equipment heat dissipation, current-dependent Pvid | 21.3 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 7.1 W |
| Rated operational current for specified heat dissipation (In) | 72 A |
| Static heat dissipation, non-current-dependent Pvs | 4.1 W |
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |