View larger
DILEM-01-C(110V50HZ,120V60HZ) 231681 Y7-231681 EATON ELECTRIC Contactor, 3p+1N/C, 4kW/400V/AC3
DILEM-01-C(110V50HZ,120V60HZ)
231681
Y7-231681
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Contactor DILEM-01-C(110V50HZ,120V60HZ) manufactured by Eaton Moeller is a standard industrial control component designed to repeatedly establish and interrupt electrical power circuits. Engineers commonly deploy these units for switching electric motors and other inductive loads within automation panels.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 110 V
- Rated control supply voltage AC 60 Hz (EF003979): 120 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 3
- Type of electrical connection of main circuit (EF006819): Spring clamp connection
- Operating voltage AC 50 Hz (EF008206): 24 V
- Operating voltage AC 60 Hz (EF008207): 24 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 22 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 9 A
- Rated operation power at AC-3, 400 V (EF001364): 4 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 6.6 A
- Rated operation power at AC-4, 400 V (EF008496): 3 kW
- Rated operation power NEMA (EF011960): 3.7 kW
- Modular version (EF001126): No
- Width (EF000008): 45 mm
More info
▲General specifications
CSA Class No.: 3211-04
UL
IEC/EN 60947
CSA File No.: 012528
VDE 0660
UL 508
CSA-C22.2 No. 14-05
UL Category Control No.: NLDX
CSA
CE
UL File No.: E29096
Features & Functions
General
150,000 Operations (at 240 V, DC, L/R = 50 ms: 2 contacts in series 0.5 A)
7,000,000 Operations (Coil 50/60 Hz)
10,000,000 Operations
10 g, N/O main contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/C auxiliary contact, Basic unit without auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
20 g, N/O auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
20 g, N/C auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
2 x (1 - 2.5) mm²
Electrical rating
1.5 A at 100 V, DC L/R ≤ 15 ms (with 3 contacts in series)
2.5 A at 24 V, DC L/R ≤ 15 ms (with 1 contact in series)
0.5 A at 220 V, DC L/R ≤ 15 ms (with 3 contacts in series)
300 V AC, Between coil and auxiliary contacts, According to EN 61140
300 V AC, Between auxiliary contacts, According to EN 61140
300 V AC, Between coil and contacts, According to EN 61140
Short-circuit rating
5 kA, SCCR (UL/CSA)
6 A gG/gL, Max. Fuse 500V, Auxiliary contacts, Short-circuit rating without welding
10 A fast, Max. Fuse 500V, Auxiliary contacts, Short-circuit rating without welding
Conventional thermal current Ith
Switching capacity
0.5 A, 250 V DC, (UL/CSA)
P300, DC operated (UL/CSA)
Magnet system
0.8 - 1.1 V AC x Uc (voltage tolerance - single-voltage coil 50 Hz and dual-voltage coil 50 Hz, 60 Hz)
22 W, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz
22 W, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz
4.6 VA, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz