Engineered for robust direct current applications, the DILDC400/22(RDS250) Eaton Moeller DC contactor handles heavy loads in industrial power systems. Such high-capacity contactors are fundamental for controlling large DC currents in specialized manufacturing and renewable energy installations. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 110 V
- Rated control supply voltage AC 60 Hz (EF003979): 110 V
- Rated control supply voltage DC (EF003980): 110 V
- Voltage type for actuating (EF008242): DC
- Number of normally open contacts as main contact (EF001374): 2
- Type of electrical connection of main circuit (EF006819): Connection rail
- Operating voltage DC (EF008208): 110 V
- Rated operation power at DC-3 / DC-5 at 440 V (EF007026): 0 kW
- Modular version (EF001126): No
- Width (EF000008): 160 mm
- Height (EF000040): 219 mm
- Depth (EF000049): 248 mm
More info
▲General specifications
UL508
IEC/EN 60947-5-1
CSA
UL Category Control No.: NRNT
CSA Class No.: C321124
CE
IEC/EN 60947-4-1
UL File No.: E338590
CSA-C22.2 No. 14-05
UL
Global
1,000,000 Operations (DC operated)
1000 mechanical Operations/h (AC operated)
1000 mechanical Operations/h (DC operated)
10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
General
Damp heat, constant, to IEC 60068-2-78
10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Climatic environmental conditions
1 x (0.75 - 2.5) mm², Control circuit cables
1 x (0.75 - 2.5) mm², Control circuit cables
1/0 - 500 MCM, Main cables
M3.5, Terminal screw, Control circuit cables
2, Terminal screw, Control circuit cables, Pozidriv screwdriver
24 Nm, Main cable connection screw/bolt
Terminal capacities
Max. 630 A gR 1000 V DC (max. short-circuit current 30 kA), Fuse, Type “1” coordination, 400 V DC, Main conducting paths
Max. 630 A gR 1000 V DC (max. short-circuit current 30 kA), Fuse, Type “1” coordination, 690 V DC, Main conducting paths
Max. 630 A gR 1000 V DC (max. short-circuit current 6 kA), Fuse, Type “2” coordination, 400 V DC, Main conducting paths
Max. 630 A gR 1000 V DC (max. short-circuit current 6 kA), Fuse, Type “2” coordination, 690 V DC, Main conducting paths
Max. 630 A gR 1000 V DC (max. short-circuit current 30 kA), Fuse, Type “1” coordination, 1000 V DC, Main conducting paths
1000 V, Between control inputs and main contacts, According to EN 61140
1000 V, Between auxiliary contacts and main contacts, According to EN 61140
Electrical rating
1 A, 250 V DC, (UL/CSA)
P300, DC operated (UL/CSA)
Max. 630 A gR 1000 V DC (max. short-circuit current 30 kA), Fuse, Type “1” coordination, 400 V DC, Main conducting paths
Max. 630 A gR 1000 V DC (max. short-circuit current 30 kA), Fuse, Type “1” coordination, 690 V DC, Main conducting paths
Max. 630 A gR 1000 V DC (max. short-circuit current 6 kA), Fuse, Type “2” coordination, 400 V DC, Main conducting paths
Max. 630 A gR 1000 V DC (max. short-circuit current 6 kA), Fuse, Type “2” coordination, 690 V DC, Main conducting paths
Max. 630 A gR 1000 V DC (max. short-circuit current 30 kA), Fuse, Type “1” coordination, 1000 V DC, Main conducting paths
1000 V, Between control inputs and main contacts, According to EN 61140
1000 V, Between auxiliary contacts and main contacts, According to EN 61140
Switching capacity
AC operated: 0.2 x US max - 0.6 x US min, AC operated
0.7 - 1.15 V DC x Us
550 W, Pull-in power, Coil in a cold state and 1.0 x Us
600 VA, Pull-in power, Coil in a cold state and 1.0 x Us
18 VA, Coil in a cold state and 1.0 x Us
9.5 W, Coil in a cold state and 1.0 x Us
Magnet system
600 VA, Pull-in power, Coil in a cold state and 1.0 x Us
18 VA, Coil in a cold state and 1.0 x Us
9.5 W, Coil in a cold state and 1.0 x Us