View larger
DILA-31(220V50/60HZ)-PI 199639 Y7-199639 EATON ELECTRIC DILA-31(220V50/60HZ)-PI
DILA-31(220V50/60HZ)-PI
199639
Y7-199639
EATON - MOELLER
1 Pcs.
Automation > Contactor relay
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller DILA-31(220V50/60HZ)-PI contactor relay functions as a dedicated auxiliary switching device designed to manage control signals, interlock machine operations, and expand contact capacity in complex industrial panels. Such components ensure reliable signal routing across automated production lines. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 220 V
- Rated control supply voltage AC 60 Hz (EF003979): 220 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Rated operation current (EF007679): 16 A
- Rated operation current Ie, 400 V (EF001378): 4 A
- Mounting method (EF000003): DIN-rail/screw
- With LED indication (EF005950): No
- Suitable for manual operation (EF002978): No
- Interface (EF000594): No
- Operating voltage AC 50 Hz (EF008206): 17 V
- Operating voltage AC 60 Hz (EF008207): 17 V
- Operating voltage DC (EF008208): 24 V
- Voltage type (operating voltage) (EF005294): AC/DC
- Rated switch current (EF006706): 16 A
- Connection type auxiliary circuit (EF006820): Spring clamp connection
More info
▲General specifications
EN 60947-5-1
VDE 0660
Features & Functions
General
5 g, N/C auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
1 x (0.5 - 2.5) mm²
Electrical rating
10 A at 24 V, DC L/R ≤ 15 ms (with 1 contact in series)
6 A at 110 V, DC L/R ≤ 15 ms (with 3 contacts in series)
1 A at 220 V, DC L/R ≤ 15 ms (with 1 contact in series)
5 A at 220 V, DC L/R ≤ 15 ms (with 3 contacts in series)
6 A at 60 V, DC L/R ≤ 15 ms (with 1 contact in series)
10 A at 60 V, DC L/R ≤ 15 ms (with 2 contacts in series)
1 A at 220 V, DC L/R ≤ 50 ms (with 3 contacts in series)
3 A at 110 V, DC L/R ≤ 15 ms (with 1 contact in series)
4 A at 60 V, DC L/R ≤ 50 ms (with 3 contacts in series)
2 A at 110 V, DC L/R ≤ 50 ms (with 3 contacts in series)
16 A
400 V AC, Between auxiliary contacts, According to EN 61140
Magnet system
0.85 - 1.1 V AC x Uc
25 VA, AC, Dual-frequency coil at 60 Hz
Communication
Contacts
λ < 5 x 1/10⁷ (1 failure at 2,000,000 operations for Uₑ = 24 V DC, Umin = 17 V, Imin = 5.4 mA)