Request QuoteProduct Overview
Eaton Moeller DILA-22(24V50/60HZ)-PI contactor relay serves as an auxiliary switching unit for control panels, safety interlocks, and automation logic networks. These devices facilitate precise signal routing and electrical sequencing.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 24 V
- Rated control supply voltage AC 60 Hz (EF003979): 24 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Rated operation current (EF007679): 16 A
- Rated operation current Ie, 400 V (EF001378): 4 A
- Mounting method (EF000003): DIN-rail/screw
- With LED indication (EF005950): No
- Suitable for manual operation (EF002978): No
- Interface (EF000594): No
- Operating voltage AC 50 Hz (EF008206): 17 V
- Operating voltage AC 60 Hz (EF008207): 17 V
- Operating voltage DC (EF008208): 24 V
- Voltage type (operating voltage) (EF005294): AC/DC
- Rated switch current (EF006706): 16 A
- Connection type auxiliary circuit (EF006820): Spring clamp connection
More info
▲General specifications
EN 60947-5-1
VDE 0660
CSA File No.: 012528
CSA Class No.: 3211-03
UL File No.: E29184
UL 508
CSA-C22.2 No. 14-05
CE marking
UL Category Control No.: NKCR
UL
CSA
Features & Functions
General
5 g, N/C auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
1 x (0.5 - 1.5) mm², Control circuit cables
1 x (0.5 - 0.25) mm²
Electrical rating
2 A at 110 V, DC L/R ≤ 50 ms (with 3 contacts in series)
10 A at 24 V, DC L/R ≤ 15 ms (with 1 contact in series)
4 A at 24 V, DC L/R ≤ 50 ms (with 3 contacts in series)
4 A at 60 V, DC L/R ≤ 50 ms (with 3 contacts in series)
1 A at 220 V, DC L/R ≤ 50 ms (with 3 contacts in series)
6 A at 110 V, DC L/R ≤ 15 ms (with 3 contacts in series)
5 A at 220 V, DC L/R ≤ 15 ms (with 3 contacts in series)
6 A at 60 V, DC L/R ≤ 15 ms (with 1 contact in series)
1 A at 220 V, DC L/R ≤ 15 ms (with 1 contact in series)
10 A at 60 V, DC L/R ≤ 15 ms (with 2 contacts in series)
16 A
400 V AC, Between auxiliary contacts, According to EN 61140
1 A, 250 V DC, (UL/CSA)
P300, DC operated (UL/CSA)
Magnet system
0.8 - 1.1 V AC x Uc (voltage tolerance - dual frequency coil 50/60 Hz)
27 VA, AC, Dual-frequency coil at 60 Hz