DILA-XHIT22 101044 Y7-101044 EATON ELECTRIC Auxiliary contact module, raised, 2N/O+2N/C, surface mounting, s..
DILA-XHIT22
101044
Y7-101044
EATON - MOELLER
5 Pcs.
Automation > Auxiliary contact block
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Eaton Moeller DILA-XHIT22 101044 Y7-101044 EATON ELECTRIC Auxiliary contact module, raised, 2N/O+2N/C, surface mounting, s.. is a raised auxiliary contact module utilized to expand control relay switching capacity with multiple normally open and normally closed circuits. Raised configurations facilitate easier wiring access and accommodate complex interlocking schemes in industrial control panels.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Number of contacts as change-over contact (EF008257): 0
- Number of contacts as normally open contact (EF008256): 2
- Number of contacts as normally closed contact (EF008255): 2
- Number of fault-signal switches (EF007613): 0
- Rated operation current Ie at AC-15, 230 V (EF001385): 4 A
- Type of electric connection (EF003961): Screw connection
- Model (EF000010): Clip-on
- Mounting method (EF000003): Front fastening
More info
▲General specifications
CSA
CE
CSA File No.: 012528
IEC/EN 60947
UL 508
CSA-C22.2 No. 14-05
IEC/EN 60947-4-1
UL
UL File No.: E29184
UL Category Control No.: NKCR
VDE 0660
Features & Functions
Switching elements according to EN 50005
General
5 g, N/C auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
6000 V
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
2 x (0.75 - 2.5) mm², Screw terminals
1 x (0.75 - 2.5) mm², Screw terminals
2, Terminal screw, Pozidriv screwdriver
Electrical rating
1 A at 60 V, DC L/R ≤ 50 ms (with 3 contacts in series)
0.25 A at 220 V, DC L/R ≤ 50 ms (with 3 contacts in series)
2.5 A at 24 V, DC L/R ≤ 50 ms (with 3 contacts in series)
3 A at 110 V, DC L/R ≤ 15 ms (with 1 contact in series)
0.5 A at 110 V, DC L/R ≤ 50 ms (with 3 contacts in series)
10 A at 24 V, DC L/R ≤ 15 ms (with 1 contact in series)
1 A at 220 V, DC L/R ≤ 15 ms (with 1 contact in series)
400 V AC, Between auxiliary contacts, According to EN 61140
10 A, 600 V AC, (UL/CSA)
P300, DC operated (UL/CSA)