Request QuoteProduct Overview
Industrial systems rely on high-capacity units like the Eaton Moeller DG1-34087FN-C21C variable frequency drive to govern heavy motor loads. These drives adjust frequency and voltage dynamically to match processing demands and improve system longevity.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Mains voltage (EF006780): 380 V
- Mains frequency (EF006783): 50/60 Hz
- Number of phases input (EF007117): 3
- Number of phases output (EF006998): 3
- Max. output frequency (EF007350): 400 Hz
- Max. output voltage (EF009560): 500 V
- Nominal output current I2N (EF009561): 87 A
- Power consumption (EF000346): 1217 W
- Relative symmetric net frequency tolerance (EF007454): 10 %
- Relative symmetric net voltage tolerance (EF007453): 10 %
- Number of analogue outputs (EF001995): 2
- Number of analogue inputs (EF001994): 2
- Number of digital outputs (EF001993): 1
- Number of digital inputs (EF001992): 8
- With control element (EF001538): Yes
- Application in industrial area permitted (EF007294): Yes
More info
▲General specifications
CE
UL Category Control No.: NMMS, NMMS7
IEC/EN61800-5
C-Tick
IEC/EN 61800-3
IEC/EN61800-3
CUL
RoHS, ISO 9001
UL508
UkrSEPRO
UL File No.: E134360
Specification for general requirements: IEC/EN 61800-2
CSA-C22.2 No. 274-13
UL report applies to both US and Canada
Certified by UL for use in Canada
Safety requirements: IEC/EN 61800-5
UL
Features & Functions
Externally accessible fan
Parameterization: Fieldbus
Parameterization: Keypad
Parameterization: Power Xpert inControl
General
C3 ≤ 50 m, Radio interference level, maximum motor cable length
C2 ≤ 10 m, Radio interference level, maximum motor cable length
IP21
Radio interference suppression filter
Internal DC link
Additional PCB protection
PC connection
Control unit
DC link choke
IGBT inverter
C1: with external filter, for conducted emissions only
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
UPS drop test (for weights inside the UPS frame)
Storage and transportation: maximum 15 g, 11 ms (inside the packaging)
Resistance: 5 - 15.8 Hz, Amplitude 1 mm (peak)
Resistance: 5 - 150 Hz, According to EN 61800-5-1, IEC/EN 60068-2-6
Climatic environmental conditions
Above 1000 m with 1 % derating per 100 m
Max. 3000 m
Max. 2000 m for Corner Grounded TN Systems
Main circuit
U/f control
Sensorless vector control (SLV)
Speed control with slip compensation
480 V AC, 3-phase
400 V AC, 3-phase
500 V AC, 3-phase
400 V AC, 3-phase
Motor rating
Apparent power
Braking function
Max. 30 % MN, Standard - Main circuit
Adjustable to 150 % (I/Ie), DC - Main circuit
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit
Control circuit
Communication
DeviceNet, optional
CANopen®, optional
SmartWire-DT, optional
PROFIBUS, optional
BACnet MS/TP, built in
Modbus RTU, built in
Ethernet IP, built in
In conjunction with DXG-NET-SWD SmartWire DT module
DeviceNet
MODBUS
PROFINET IO
TCP/IP
CAN
Other bus systems
BACnet
EtherNet/IP