EATON - MOELLER DC1-S24D3FN-A6SOE1 DC1-S24D3FN-A6SOE1 199388 Y7-199388 EATON ELECTRIC DC1-S24D3FN-A6SOE1 View larger
Images are for illustrative purposes only. Please refer to data sheet for details

DC1-S24D3FN-A6SOE1 199388 Y7-199388 EATON ELECTRIC DC1-S24D3FN-A6SOE1

DC1-S24D3FN-A6SOE1

199388

Y7-199388

EATON - MOELLER

1 Pcs.

DC1-S24D3FN-A6SOE1 Eaton DC1 Variable frequency drive, 230 V AC, 1-phase, 4.3 A, 0.37 kW, IP66/NEMA 4X, Radio interference suppression filter, 7-digital display assembly, Local controls, Additional PCB protection, UV resistant, FS1 Variable frequency drive, Part group reference (e.g. DIL): DC1, Rated operational voltage: Ue = 230 V AC, 1-phase, 240 V AC, single-phase, Output voltage with Ve: U2 = 230 V AC, single-phase, 240 V AC, single-phase, Mains voltage (50/60Hz): ULN = 200 (-10%) - 240 (+10%) V, Rated operational current At 150% overload: Ie = 4.3 A, Note: Rated operational current at an operating frequency of 6 kHz and an ambient air temperature of +40 °C, Note: Overload cycle for 60 s every 600 s, Assigned motor rating Note: For AC motors with internal and external ventilation with 50/60 Hz without additional start capacitor, Overload cycle for 60 s every 600 s , at 230 V, 50 Hz, Assigned motor rating 150 % Overload: P = 0.37 kW, 150 % Overload: IM = 4.3 A, Assigned motor rating Note: at 220 - 240 V, 60 Hz, Assigned motor rating 150 % Overload: P = 0.5 HP, Assigned motor rating 150 % Overload: IM = 4.3 A, Degree of Protection: IP66/NEMA 4X, Interface/field bus (built-in): OP-Bus (RS485)/Modbus RTU, CANopen®, Fieldbus connection (optional): SmartWire-DT, Fitted with: Radio interference suppression filter, 7-digital display assembly, Local controls, Additional PCB protection, UV resistant, Frame size: FS1, Standards: General requirements: IEC/EN 61800-2, EMV requirements: IEC/EN 61800-3 , Safety requirements: IEC/EN 61800-5-1

Automation > Frequency converter less than 1 kV
Power XL Frequency Converters

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General specifications

Product Name
Eaton DC1 Variable frequency drive
Catalog Number
199388
Model Code
DC1-S24D3FN-A6SOE1
EAN
4015081977772
Product Length/Depth
162 mm
Product Height
232 mm
Product Width
161 mm
Product Weight
2.5 kg
Certifications
CUL
EAC
CE
UkrSEPRO
UL File No.: E172143
CE marking
IEC/EN 61800-2
IEC/EN 61800-3
UL 508C
IEC/EN 61800-5-1
UL Category Control No.: NMMS, NMMS7
UL
UL Listed
UL report applies to both US and Canada
RCM
CSA-C22.2 No. 14
IEC/EN61800-5
RoHS, ISO 9001
Certified by UL for use in Canada

Features & Functions

Features
Parameterization: Fieldbus
Parameterization: drivesConnect
Parameterization: Keypad
Parameterization: drivesConnect mobile (App)
Fitted with:
Local controls
UV resistance
7-digital display assembly
PC connection
Radio interference suppression filter
Control unit
Additional PCB protection
IGBT inverter
Internal DC link

General

Cable length
75 m, unscreened, maximum permissible, Motor feeder
50 m, screened, maximum permissible, Motor feeder
C3 ≤ 25 m, maximum motor cable length
150 m, unscreened, with motor choke, maximum permissible, Motor feeder
C1 ≤ 1 m, maximum motor cable length
C2 ≤ 5 m, maximum motor cable length
100 m, screened, with motor choke, maximum permissible, Motor feeder
Communication interface
CANopen®, built in
OP-Bus (RS485), built in
SmartWire-DT, optional
Modbus RTU, built in
Connection to SmartWire-DT
No
Degree of protection
NEMA 4X
IP66
Electromagnetic compatibility
1st and 2nd environments (according to EN 61800-3)
Frame size
FS1
Mounting position
Vertical
Product category
Variable frequency drives
Protection
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
Protocol
EtherNet/IP
MODBUS
CAN
Other bus systems
Radio interference class
C1: for conducted emissions only
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Suitable for
Branch circuits, (UL/CSA)

Climatic environmental conditions

Altitude
Max. 4000 m
Above 1000 m with 1 % derating per 100 m
Ambient operating temperature - min
-20 °C
Ambient operating temperature - max
40 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
60 °C
Climatic proofing
< 95 average relative humidity (RH), no condensation, no corrosion

Main circuit

Efficiency
97 % (η)
Input current ILN at 150% overload
6 A
Leakage current at ground IPE - max
2.49 mA
Mains switch-on frequency
Maximum of one time every 30 seconds
Mains voltage - min
200 V
Mains voltage - max
240 V
Operating mode
U/f control
PM motors
Sensorless vector control (SLV)
BLDC motors
Synchronous reluctance motors
Speed control with slip compensation
Output frequency - min
0 Hz
Output frequency - max
500 Hz
Output voltage (U2)
230 V AC, single-phase
240 V AC, single-phase
Overload current IL at 150% overload
6.45 A
Rated control supply voltage
10 V DC (Us, max. 10 mA)
Rated frequency - min
48 Hz
Rated frequency - max
62 Hz
Rated operational current (Ie)
4.3 A at 150% overload (at an operating frequency of 6 kHz and an ambient air temperature of +40 °C)
Rated operational voltage
230 V AC, 1-phase
240 V AC, 1-phase
Resolution
0.1 Hz (Frequency resolution, setpoint value)
Short-circuit protection rating
10 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
Starting current - max
175 % IH
Supply frequency
50/60 Hz
Switching frequency
8 kHz, 4 - 32 kHz adjustable (audible), fPWM, Power section, Main circuit
System configuration type
AC supply systems with earthed center point
Voltage rating - max
240 V

Motor rating

Assigned motor current IM at 220 - 240 V, 60 Hz, 150% overload
4.3 A
Assigned motor current IM at 230 V, 50 Hz, 150% overload
4.3 A
Assigned motor power at 230/240 V, 60 Hz, 1-phase
0.5 HP

Apparent power

Apparent power at 230 V
0.99 kVA
Apparent power at 240 V
1.03 kVA

Braking function

Braking torque
Max. 100 % of rated operational current Ie, variable, DC - Main circuit

Control circuit

Number of inputs (analog)
2
Number of inputs (digital)
4
Number of outputs (analog)
1
Number of outputs (digital)
1
Number of relay outputs
1 (parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))

ETIM for 199388 Low-voltage industrial controls and switchgear (EC001857)
Feature Name Feature Value
Mains voltage (EF006780) 200 V
Mains frequency (EF006783) 50/60 Hz
Number of phases input (EF007117) 1
Number of phases output (EF006998) 1
Max. output frequency (EF007350) 500 Hz
Max. output voltage (EF009560) 250 V
Nominal output current I2N (EF009561) 4.3 A
Max. output at quadratic load at rated output voltage (EF007366) 0.37 kW
Max. output at linear load at rated output voltage (EF007364) 0.37 kW
Power consumption (EF000346) 45.75 W
Relative symmetric net frequency tolerance (EF007454) 10 %
Relative symmetric net voltage tolerance (EF007453) 10 %
Number of analogue outputs (EF001995) 1
Number of analogue inputs (EF001994) 2
Number of digital outputs (EF001993) 1
Number of digital inputs (EF001992) 4
With control element (EF001538) Yes
Application in industrial area permitted (EF007294) Yes
Application in domestic- and commercial area permitted (EF007295) Yes
Supporting protocol for TCP/IP (EF003050) No
Supporting protocol for PROFIBUS (EF003052) No
Supporting protocol for CAN (EF003053) Yes
Supporting protocol for INTERBUS (EF003054) No
Supporting protocol for ASI (EF003051) No
Supporting protocol for KNX (EF003055) No
Supporting protocol for Modbus (EF003057) Yes
Supporting protocol for Data-Highway (EF003058) No
Supporting protocol for DeviceNet (EF003059) No
Supporting protocol for SUCONET (EF003060) No
Supporting protocol for LON (EF003017) No
Supporting protocol for PROFINET IO (EF007525) No
Supporting protocol for PROFINET CBA (EF007524) No
Supporting protocol for SERCOS (EF006657) No
Supporting protocol for Foundation Fieldbus (EF007522) No
Supporting protocol for EtherNet/IP (EF007521) Yes
Supporting protocol for AS-Interface Safety at Work (EF007519) No
Supporting protocol for DeviceNet Safety (EF007520) No
Supporting protocol for INTERBUS-Safety (EF006662) No
Supporting protocol for PROFIsafe (EF007526) No
Supporting protocol for SafetyBUS p (EF007527) No
Supporting protocol for BACnet (EF011944) No
Supporting protocol for other bus systems (EF003062) Yes
Number of HW-interfaces industrial Ethernet (EF003020) 0
Number of interfaces PROFINET (EF006932) 0
Number of HW-interfaces RS-232 (EF003021) 0
Number of HW-interfaces RS-422 (EF003022) 0
Number of HW-interfaces RS-485 (EF003023) 1
Number of HW-interfaces serial TTY (EF003024) 0
Number of HW-interfaces USB (EF003025) 0
Number of HW-interfaces parallel (EF003026) 0
Number of HW-interfaces other (EF003027) 0
With optical interface (EF003028) No
With PC connection (EF006107) Yes
Integrated breaking resistance (EF007293) No
4-quadrant operation possible (EF006803) No
Type of converter (EF006978) U converter
Degree of protection (IP) (EF005474) IP66
Degree of protection (NEMA) (EF011959) 4X
Height (EF000040) 232 mm
Width (EF000008) 161 mm
Depth (EF000049) 162 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.