View larger
DC1-345D8FB-A6SOE1 199436 Y7-199436 EATON ELECTRIC DC1-345D8FB-A6SOE1
DC1-345D8FB-A6SOE1
199436
Y7-199436
EATON - MOELLER
1 Pcs.
Automation > Frequency converter less than 1 kV
Power XL Frequency Converters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The DC1-345D8FB-A6SOE1 Eaton Moeller variable frequency drive delivers reliable motor control and speed variation for automated manufacturing equipment. Frequency drives optimize energy consumption and process precision by matching motor output to immediate operational needs. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Mains voltage (EF006780): 380 V
- Mains frequency (EF006783): 50/60 Hz
- Number of phases input (EF007117): 3
- Number of phases output (EF006998): 3
- Max. output frequency (EF007350): 500 Hz
- Max. output voltage (EF009560): 500 V
- Nominal output current I2N (EF009561): 5.8 A
- Power consumption (EF000346): 101.2 W
- Relative symmetric net frequency tolerance (EF007454): 10 %
- Relative symmetric net voltage tolerance (EF007453): 10 %
- Number of analogue outputs (EF001995): 1
- Number of analogue inputs (EF001994): 2
- Number of digital outputs (EF001993): 1
- Number of digital inputs (EF001992): 4
- With control element (EF001538): Yes
- Application in industrial area permitted (EF007294): Yes
More info
▲General specifications
IEC/EN 61800-5-1
UL Category Control No.: NMMS, NMMS7
RCM
IEC/EN 61800-3
UL File No.: E172143
UkrSEPRO
IEC/EN61800-5
UL 508C
Certified by UL for use in Canada
UL report applies to both US and Canada
CE marking
IEC/EN 61800-2
CSA-C22.2 No. 14
UL Listed
EAC
CUL
CE
RoHS, ISO 9001
Features & Functions
Parameterization: Fieldbus
Parameterization: Keypad
Parameterization: drivesConnect
7-digital display assembly
Local controls
PC connection
Radio interference suppression filter
Control unit
Additional PCB protection
Breaking resistance
Internal DC link
IGBT inverter
UV resistance
General
150 m, unscreened, maximum permissible cable length
300 m, unscreened, with motor choke, maximum permissible, Motor feeder
200 m, screened, with motor choke, maximum permissible cable length
C3 ≤ 25 m, maximum motor cable length
C2 ≤ 5 m, maximum motor cable length
CANopen®, built in
OP-Bus (RS485), built in
Modbus RTU, built in
NEMA 4X
Other bus systems
EtherNet/IP
MODBUS
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
Climatic environmental conditions
Max. 4000 m
Main circuit
PM motors
BLDC motors
U/f control
Speed control with slip compensation
Synchronous reluctance motors
480 V AC, 3-phase
480 V AC, 3-phase
Motor rating
Apparent power
Braking function
Max. 100 % of rated operational current Ie, variable, DC - Main circuit
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit