View larger
DC1-34014FB-A6SOE1 199440 Y7-199440 EATON ELECTRIC DC1-34014FB-A6SOE1
DC1-34014FB-A6SOE1
199440
Y7-199440
EATON - MOELLER
1 Pcs.
Automation > Frequency converter less than 1 kV
Power XL Frequency Converters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller DC1-34014FB-A6SOE1 variable frequency drive delivers reliable motor speed control across a broad range of industrial applications. These devices are commonly installed in machine building environments to regulate pumps, fans, and conveyors efficiently.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product Name: Eaton DC1 Variable frequency drive
- Catalog Number: 199440
- Model Code: DC1-34014FB-A6SOE1
- EAN: 4015081978298
- Product Length/Depth: 238 mm
- Product Height: 310 mm
- Product Width: 210.5 mm
- Product Weight: 7 kg
- Functions: 4-quadrant operation possible
- Communication interface: SmartWire-DT, optional OP-Bus (RS485), built in Modbus RTU, built in CANopen®, built in
- Connection to SmartWire-DT: No
- Degree of protection: IP66 NEMA 4X
- Electromagnetic compatibility: 1st and 2nd environments (according to EN 61800-3)
- Frame size: FS3
- Mounting position: Vertical
- Product category: Variable frequency drives
More info
▲General specifications
| Product Name | Eaton DC1 Variable frequency drive |
| Catalog Number | 199440 |
| Model Code | DC1-34014FB-A6SOE1 |
| EAN | 4015081978298 |
| Product Length/Depth | 238 mm |
| Product Height | 310 mm |
| Product Width | 210.5 mm |
| Product Weight | 7 kg |
| Certifications | UL 508C Certified by UL for use in Canada UkrSEPRO UL IEC/EN61800-5 UL report applies to both US and Canada CSA-C22.2 No. 14 UL File No.: E172143 CUL IEC/EN 61800-2 CE marking IEC/EN 61800-5-1 EAC UL Listed IEC/EN 61800-3 RoHS, ISO 9001 CE RCM UL Category Control No.: NMMS, NMMS7 |
| Catalog Notes |
|
Features & Functions
| Features | Parameterization: Fieldbus Parameterization: drivesConnect mobile (App) Parameterization: drivesConnect Parameterization: Keypad |
| Fitted with: | PC connection UV resistance Internal DC link Brake chopper Control unit Radio interference suppression filter Additional PCB protection Local controls IGBT inverter 7-digital display assembly Breaking resistance |
| Functions | 4-quadrant operation possible |
General information
| Cable length | 100 m, screened, maximum permissible cable length 200 m, screened, with motor choke, maximum permissible cable length C2 ≤ 5 m, maximum motor cable length C3 ≤ 25 m, maximum motor cable length 300 m, unscreened, with motor choke, maximum permissible, Motor feeder 150 m, unscreened, maximum permissible cable length |
| Communication interface | SmartWire-DT, optional OP-Bus (RS485), built in Modbus RTU, built in CANopen®, built in |
| Connection to SmartWire-DT | No |
| Degree of protection | IP66 NEMA 4X |
| Electromagnetic compatibility | 1st and 2nd environments (according to EN 61800-3) |
| Frame size | FS3 |
| Mounting position | Vertical |
| Product category | Variable frequency drives |
| Product category | Variable frequency drives |
| Protection | Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4) |
| Protocol | CAN MODBUS EtherNet/IP Other bus systems |
| Radio interference class | Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary. |
| Suitable for | Branch circuits, (UL/CSA) |
Climatic environmental conditions
| Altitude | Above 1000 m with 1 % derating per 100 m Max. 4000 m |
| Ambient operating temperature - min | -20 °C |
| Ambient operating temperature - max | 40 °C |
| Ambient storage temperature - min | -40 °C |
| Ambient storage temperature - max | 60 °C |
| Climatic proofing | < 95 average relative humidity (RH), no condensation, no corrosion |
Main circuit
| Efficiency | 97 % (η) |
| Heat dissipation at current/speed | 109.2 W at 50% current and 50% speed 128.4 W at 50% current and 90% speed 145.9 W at 100% current and 0% speed 169.6 W at 100% current and 50% speed 204.2 W at 100% current and 90% speed 78.2 W at 25% current and 0% speed 85.3 W at 25% current and 50% speed 96.8 W at 50% current and 0% speed |
| Input current ILN at 150% overload | 17.2 A |
| Leakage current at ground IPE - max | 12.7 mA |
| Mains switch-on frequency | Maximum of one time every 30 seconds |
| Mains voltage - min | 380 V |
| Mains voltage - max | 480 V |
| Operating mode | Sensorless vector control (SLV) BLDC motors Synchronous reluctance motors U/f control Speed control with slip compensation PM motors |
| Output frequency - min | 0 Hz |
| Output frequency - max | 500 Hz |
| Output voltage (U2) | 480 V AC, 3-phase 400 V AC, 3-phase |
| Overload current IL at 150% overload | 21 A |
| Rated control supply voltage | 10 V DC (Us, max. 10 mA) |
| Rated frequency - min | 48 Hz |
| Rated frequency - max | 62 Hz |
| Rated operational current (Ie) | 14 A at 150% overload (at an operating frequency of 6 kHz and an ambient air temperature of +40 °C) |
| Rated operational power at 380/400 V, 50 Hz, 3-phase | 5.5 kW |
| Rated operational voltage | 480 V AC, 3-phase 400 V AC, 3-phase |
| Resolution | 0.1 Hz (Frequency resolution, setpoint value) |
| Short-circuit protection rating | 20 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring |
| Starting current - max | 175 %, IH, max. starting current (High Overload), For 2.5 seconds every 600 seconds, Power section |
| Supply frequency | 50/60 Hz |
| Switching frequency | 8 kHz, 4 - 24 kHz adjustable (audible), fPWM, Power section, Main circuit |
| System configuration type | AC supply systems with earthed center point |
| Voltage rating - max | 480 V |
Motor rating
| Assigned motor current IM at 400 V, 50 Hz, 150% overload | 11.3 A |
| Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload | 14 A |
| Assigned motor power at 460/480 V, 60 Hz, 3-phase | 10 HP |
Apparent power
| Apparent power at 400 V | 9.67 kVA |
| Apparent power at 480 V | 11.64 kVA |
Braking function
| Braking resistance | 100 Ω |
| Braking torque | Max. 30 % MN, Standard - Main circuit Max. 100 % of rated operational current Ie with external braking resistor - Main circuit Max. 100 % of rated operational current Ie, variable, DC - Main circuit |
| Switch-on threshold for the braking transistor | 780 VDC |
Control circuit
| Number of inputs (analog) | 2 (parameterizable, 0 - 10 V DC, 0/4 - 20 mA) |
| Number of inputs (digital) | 4 (parameterizable, 10 - 30 V DC) |
| Number of outputs (analog) | 1 |
| Number of outputs (digital) | 1 |
| Number of relay outputs | 1 (parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1)) |
Design verification
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 0 W |
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |