View larger
DC1-124D3FN-A6SOE1 199402 Y7-199402 EATON ELECTRIC DC1-124D3FN-A6SOE1
DC1-124D3FN-A6SOE1
199402
Y7-199402
EATON - MOELLER
1 Pcs.
Automation > Frequency converter less than 1 kV
Power XL Frequency Converters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller variable frequency drive (DC1-124D3FN-A6SOE1) provides advanced motor control capabilities for industrial automation systems, enabling precise adjustments to speed and torque parameters. This power conversion unit allows facility managers to enhance process accuracy and reduce mechanical wear on equipment. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Mains voltage (EF006780): 200 V
- Mains frequency (EF006783): 50/60 Hz
- Number of phases input (EF007117): 1
- Number of phases output (EF006998): 3
- Max. output frequency (EF007350): 500 Hz
- Max. output voltage (EF009560): 250 V
- Nominal output current I2N (EF009561): 4.3 A
- Power consumption (EF000346): 45.75 W
- Relative symmetric net frequency tolerance (EF007454): 10 %
- Relative symmetric net voltage tolerance (EF007453): 10 %
- Number of analogue outputs (EF001995): 1
- Number of analogue inputs (EF001994): 2
- Number of digital outputs (EF001993): 1
- Number of digital inputs (EF001992): 4
- With control element (EF001538): Yes
- Application in industrial area permitted (EF007294): Yes
More info
▲General specifications
IEC/EN 61800-3
IEC/EN61800-5
RoHS, ISO 9001
UL Listed
CUL
CE marking
UL report applies to both US and Canada
UL 508C
RCM
IEC/EN 61800-5-1
CSA-C22.2 No. 14
Certified by UL for use in Canada
IEC/EN 61800-2
UL Category Control No.: NMMS, NMMS7
UkrSEPRO
EAC
CE
UL
Features & Functions
Parameterization: drivesConnect
Parameterization: drivesConnect mobile (App)
Parameterization: Fieldbus
UV resistance
Local controls
Internal DC link
PC connection
Radio interference suppression filter
IGBT inverter
Control unit
Additional PCB protection
General
75 m, unscreened, maximum permissible, Motor feeder
C2 ≤ 5 m, maximum motor cable length
C1 ≤ 1 m, maximum motor cable length
150 m, unscreened, with motor choke, maximum permissible, Motor feeder
C3 ≤ 25 m, maximum motor cable length
100 m, screened, with motor choke, maximum permissible, Motor feeder
OP-Bus (RS485), built in
CANopen®, built in
Modbus RTU, built in
NEMA 4X
Other bus systems
MODBUS
EtherNet/IP
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
C1: for conducted emissions only
Climatic environmental conditions
Above 1000 m with 1 % derating per 100 m
Main circuit
Speed control with slip compensation
Synchronous reluctance motors
PM motors
U/f control
BLDC motors
230 V AC, 3-phase
240 V AC, 1-phase
Motor rating
Apparent power
Braking function
Max. 30 % MN, Standard - Main circuit