View larger
DC1-124D3FN-A20CE1 185806 Y7-185806 EATON ELECTRIC Variable frequency drive, 230 V AC, 1-phase, 4.3 A, 0.75 ..
DC1-124D3FN-A20CE1
185806
Y7-185806
EATON - MOELLER
1 Pcs.
Automation > Frequency converter less than 1 kV
Power XL Frequency Converters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for smaller single-phase supplies, the Eaton Moeller DC1-124D3FN-A20CE1 variable frequency drive converts incoming AC power to drive three-phase motors with smooth speed adjustment and overload protection.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Mains voltage: 200 V
- Mains frequency: 50/60 Hz
- Number of phases input: 1
- Number of phases output: 3
- Max. output frequency: 500 Hz
- Max. output voltage: 250 V
- Nominal output current I2N: 4.3 A
- Power consumption: 45.75 W
- Relative symmetric net frequency tolerance: 10 %
- Relative symmetric net voltage tolerance: 10 %
- Number of analogue outputs: 1
- Number of analogue inputs: 2
- Number of digital outputs: 1
- Number of digital inputs: 4
- With control element: Yes
- Application in industrial area permitted: Yes
More info
▲General specifications
Safety requirements: IEC/EN 61800-5-1
UL Category Control No.: NMMS, NMMS7
Certified by UL for use in Canada
IEC/EN61800-5
CSA-C22.2 No. 14
IEC/EN61800-3
CUL
RoHS, ISO 9001
UkrSEPRO
CE
RCM
IEC/EN 61800-3
EAC
UL 508C
UL report applies to both US and Canada
UL File No.: E172143
UL
Features & Functions
Parameterization: drivesConnect mobile (App)
Parameterization: Fieldbus
Parameterization: Keypad
Internal DC link
IGBT inverter
Radio interference suppression filter
7-digital display assembly
PC connection
Additional PCB protection
General
150 m, unscreened, with motor choke, maximum permissible, Motor feeder
100 m, screened, with motor choke, maximum permissible, Motor feeder
C3 ≤ 25 m, Radio interference level, maximum motor cable length
C1 ≤ 1 m, Radio interference level, maximum motor cable length
C2 ≤ 5 m, Radio interference level, maximum motor cable length
75 m, unscreened, maximum permissible, Motor feeder
Modbus RTU, built in
SmartWire-DT, optional
OP-Bus (RS485), built in
Yes
NEMA Other
Other bus systems
CAN
EtherNet/IP
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
Climatic environmental conditions
Max. 4000 m
Main circuit
U/f control
Speed control with slip compensation
BLDC motors
PM motors
Synchronous reluctance motors
230 V AC, 3-phase
240 V AC, 1-phase
Motor rating
Apparent power
Braking function
Max. 30 % MN, Standard - Main circuit