View larger
DB1-345D8FB-N2CC 197565 Y7-197565 EATON ELECTRIC DB1-345D8FB-N2CC
DB1-345D8FB-N2CC
197565
Y7-197565
EATON - MOELLER
10 Pcs.
Automation > Frequency converter less than 1 kV
Power XL Frequency Converters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller variable frequency drive offers reliable motor speed regulation to optimize mechanical processes in industrial settings. These electronic devices are typically installed inside electrical enclosures to govern pumps, fans, and conveyor systems with high precision. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product Name: Eaton DB1 Variable frequency drive
- Catalog Number: 197565
- Model Code: DB1-345D8FB-N2CC
- EAN: 4015081943340
- Product Length/Depth: 89 mm
- Product Height: 193 mm
- Product Width: 140 mm
- Product Weight: 1.15 kg
- Communication interface: Modbus RTU OP-Bus (RS485) CANopen®
- Connection to SmartWire-DT: No
- Degree of protection: IP20 NEMA Other
- Electromagnetic compatibility: 1st and 2nd environments (according to EN 61800-3)
- Frame size: FS2
- Number of slots: 1 (expansion)
- Product Category: Variable frequency drives
- Protection: Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
More info
▲General specifications
| Product Name | Eaton DB1 Variable frequency drive |
| Catalog Number | 197565 |
| Model Code | DB1-345D8FB-N2CC |
| EAN | 4015081943340 |
| Product Length/Depth | 89 mm |
| Product Height | 193 mm |
| Product Width | 140 mm |
| Product Weight | 1.15 kg |
| Certifications | Certified by UL for use in Canada IEC/EN 61800-3 UL report applies to both US and Canada CE IEC/EN 61800-2 IEC/EN61800-3 UL Category Control No.: NMMS, NMMS7 UL File No.: E172143 RCM UL IEC/EN61800-5 CSA-C22.2 No. 14 RoHS, ISO 9001 Safety: EN 61800-5-1: 2003 UL 508C CUL CSA-C22.2 No. 274 IEC/EN 61800-5-1 CE marking |
| Catalog Notes | The brake resistors are assigned based on the maximum rated power of the variable frequency drive. Additional brake resistors and designs (e.g. different duty cycles) are available upon request. |
Features & Functions
| Features | Tool-less swapping of fan Temperature-controlled fan Parameterization: Fieldbus Parameterization: Keypad Parameterization: drivesConnect Parameterization: drivesConnect mobile (App) |
| Fitted with: | Radio interference suppression filter Internal DC link IGBT inverter Breaking resistance PC connection Additional PCB protection |
General information
| Cable length | C2 ≤ 3 m, maximum motor cable length C3 ≤ 10 m, maximum motor cable length C1 ≤ 1 m, maximum motor cable length 10 m, screened, maximum permissible cable length |
| Communication interface | Modbus RTU OP-Bus (RS485) CANopen® |
| Connection to SmartWire-DT | No |
| Degree of protection | IP20 NEMA Other |
| Electromagnetic compatibility | 1st and 2nd environments (according to EN 61800-3) |
| Frame size | FS2 |
| Number of slots | 1 (expansion) |
| Product Category | Variable frequency drives |
| Protection | Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4) |
| Protocol | CAN MODBUS Other bus systems |
| Radio interference class | C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary. C1: for conducted emissions only |
| Suitable for | Branch circuits, (UL/CSA) |
Ambient conditions, mechanical
| Mounting position | Depending on the cooling As required |
| Shock resistance | 15 g, Mechanical, According to IEC/EN 60068-2-27, 11 ms |
| Vibration | Resistance: According to EN 61800-5-1 |
Climatic environmental conditions
| Altitude | Above 1000 m with 1 % derating per 100 m Max. 2000 m Max. 1000 m |
| Ambient operating temperature - min | -10 °C |
| Ambient operating temperature - max | 50 °C |
| Ambient operating temperature at 150% overload - min | -10 °C |
| Ambient operating temperature at 150% overload - max | 60 °C |
| Ambient storage temperature - min | -40 °C |
| Ambient storage temperature - max | 60 °C |
| Climatic proofing | < 95 average relative humidity (RH), no condensation, no corrosion |
Main circuit
| Efficiency | 97 % (η) |
| Heat dissipation at current/speed | 40 W at 25% current and 0% speed 45 W at 25% current and 50% speed 54 W at 50% current and 0% speed 55 W at 50% current and 50% speed 62 W at 100% current and 0% speed 62 W at 50% current and 90% speed 72 W at 100% current and 50% speed 82 W at 100% current and 90% speed |
| Input current ILN at 150% overload | 7.5 A |
| Leakage current at ground IPE - max | 3.5 mA (at 3 x 400 V) |
| Mains switch-on frequency | Maximum of one time every 30 seconds |
| Mains voltage - min | 380 V |
| Mains voltage - max | 480 V |
| Operating mode | Speed control with slip compensation U/f control BLDC motors PM motors Sensorless vector control (SLV) Synchronous reluctance motors |
| Output frequency - min | 0 Hz |
| Output frequency - max | 500 Hz |
| Output voltage (U2) | 480 V AC, 3-phase 400 V AC, 3-phase |
| Overload current IL at 150% overload | 8.7 A |
| Rated control supply voltage | 10 V DC (Us, max. 10 mA) |
| Rated frequency - min | 48 Hz |
| Rated frequency - max | 62 Hz |
| Rated operational current (Ie) at 150% overload | 5.8 A |
| Rated operational power at 380/400 V, 50 Hz | 2.2 kW |
| Rated operational voltage | 480 V AC, 3-phase 400 V AC, 3-phase |
| Resolution | 0.1 Hz (Frequency resolution, setpoint value) |
| Short-circuit protection rating | 10 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring |
| Starting current - max | 175 %, IH, max. starting current (High Overload), For 3.75 seconds every 600 seconds, Power section |
| Supply frequency | 50/60 Hz |
| Switching frequency | 8 kHz, 4 - 32 kHz adjustable (audible), fPWM, Power section, Main circuit |
| System configuration type | AC supply systems with earthed center point |
| Voltage rating - max | 480 VAC |
Motor rating
| Assigned motor current IM at 400 V, 50 Hz, 150% overload | 5.8 A |
| Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload | 5.8 A |
| Assigned motor power at 460/480 V, 60 Hz | 3 HP |
Apparent power
| Apparent power at 400 V | 2.32 kVA |
| Apparent power at 480 V | 2.78 kVA |
Braking function
| Braking resistance | 100 Ω |
| Braking torque | Max. 100 % of rated operational current Ie, variable, DC - Main circuit Max. 100 % of rated operational current Ie with external braking resistor - Main circuit Max. 30 % MN, Standard - Main circuit |
| Switch-on threshold for the braking transistor | 780 VDC |
Control circuit
| Number of inputs (analog) | 2 |
| Number of inputs (digital) | 4 |
| Number of outputs (analog) | 1 |
| Number of outputs (digital) | 1 |
| Number of relay outputs | 1 (parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1)) |
| Rated control voltage (Uc) | 24 V DC (external, max. 100 mA) |
Design verification
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 0 W |
| Rated operational current for specified heat dissipation (In) | 5.8 A |
| Static heat dissipation, non-current-dependent Pvs | 0 W |
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |